2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 3°C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is some degrees higher than a set temperature,
the compressor will be stopped.
* When the room temperature is b2.5°C to -3°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
( Table 2 : Compressor Frequency Range )
01-02
minimum
frequency
maximum
frequency
AO*G24LFL
AO*G30LFT
16rps
133rps
16rps
90rps
3. DRY OPERATION
3-1 INDOOR UNIT CONTROL
The compressor rotation frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table3.
However, after the compressor is driven, the indoor unit shall run at operation frequency of
68rps (24L), 43rps (30L), for a minute.
Ts+0.5°C
Ts -1.5°C
Ts -0.5°C
Ts+1.5°C
( Table3 : Compressor frequency )
( Fig.2 : Compressor Control based on Room Temperature )
Operating
frequency
38rps
18rps
0rps
24LFL
X zone
J zone
Y zone
Operating
frequency
J zone
Y zone
X zone
34rps
16rps
0rps
24LFCC
Room Room
temperature temperature
X zone
J zone
Y zone
AO*G24LFCC
14rps
120rps
Operating
frequency
J zone
Y zone
X zone
29rps
16rps
0rps
30LFT
Содержание AO*G24LFLAO*G24LFCC
Страница 3: ......
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 25: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ......
Страница 64: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 75: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Oct 2012 Printed in Japan ...