Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AS*G24LFCA / LFCC
[Condition]
Ambient
temperature
Indoor / Outdoor - Same temperature
Refrigerant
amount
Standard amount
Piping
length
7.5m * (Height difference 1m)
˴
AS*G24LFCC: 5m
Power
voltage
50Hz - 240V
Operation
condition
TEST mode (Cooling), Hi Fan, Horizontal direction, Front air flow
Measuring
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Cooling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AS*G24LFCA
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*G24LFCA
Measure the low pressure with the pressure meter at the service valve. Measure the outdoor
unit overall current with the current clamp meter at Power Cable.
03-05
0.5
0.6
0.7
0.8
0.9
1.0
1.1
16
18
20
22
24
26
28
30
32
Low-pressure of outdoor unit [MPa]
[50Hz-240V]
RH70%
RH60%
RH50%
In/Outdoor ambient temperature [ C]
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
16
18
20
22
24
26
28
30
32
In/Outdoor ambient temperature [ C]
Outdoor total electric current [A]
RH70%
RH60%
RH50%
[50Hz-240V]
3-2. Outdoor unit Pressure Value and Total Electric Current Curve
AS*G24LFCC
0.6
0.7
0.8
0.9
1.0
1.1
1.2
16
18
20
22
24
26
28
30
32
Low-pressure of outdoor unit [MPa]
[50Hz-240V]
RH70%
RH60%
RH50%
In/Outdoor ambient temperature [ C]
AS*G24LFCC
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
16
18
20
22
24
26
28
30
32
In/Outdoor ambient temperature [ C]
Outdoor total electric current [A]
RH70%
RH60%
RH50%
[50Hz-240V]
Содержание AO*G24LFLAO*G24LFCC
Страница 3: ......
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 25: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ......
Страница 64: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 75: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Oct 2012 Printed in Japan ...