22. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
When the discharge temperature becomes higher than Temperature , the compressor frequency
is decreased 20rps (24L) or 10rps (30L), and it continues to decrease the frequency
for 20rps (24L) or 10rps (30L) every 120 seconds until the temperature
becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the control of the control of the
compressor frequency is released.
When the discharge temperature becomes higher than Temperature , the compressor is stopped
and the indoor unit LED starts blinking.
AO*G24LFL / LFCC / 30LFT
104°C
101°C
110°C
( Table 19 : Discharge Temperature Over Rise Prevension Control / Release Temperature )
Temperature
Temperature
Temperature
2. CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
( Table 20-1 : Current Release Operation Value / Release Value for AO*G24LFL / LFCC / 30LFT )
01-18
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
AO*G24LFL
OT (Control / Release)
7.0A / 6.5A
7.0A / 6.5A
9.5A / 9.0A
12.0A / 11.5A
50°C
46°C
40°C
OT : Outdoor Temperature
AO*G24LFL
OT (Control / Release)
10.5A / 10.0A
13.0A / 12.5A
15.0A / 14.5A
17.0A / 16.5A
17°C
12°C
5°C
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
AO*G24LFCC
OT (Control / Release)
7.0A / 6.5A
7.0A / 6.5A
9.5A / 9.0A
12.0A / 11.5A
50°C
46°C
40°C
OT : Outdoor Temperature
AO*G24LFCC
OT (Control / Release)
10.5A / 10.0A
13.0A / 12.5A
15.0A / 14.5A
17.0A / 16.5A
17°C
12°C
5°C
[ Heating ]
OT : Outdoor Temperature
[ Cooling ]
AO*G30LFT
OT (Control / Release)
9.0A / 8.5A
10.0A / 9.5A
13.0A / 12.5A
16.0A / 15.5A
50°C
46°C
40°C
OT : Outdoor Temperature
AO*G30LFT
OT (Control / Release)
11.0A / 10.5A
13.0A / 12.5A
15.0A / 14.5A
18.0A / 17.5A
17°C
12°C
5°C
Содержание AO*G24LFLAO*G24LFCC
Страница 3: ......
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 25: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ......
Страница 64: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 75: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Oct 2012 Printed in Japan ...