01-16
Compressor OFF
Outdoor fan motor OFF
30 sec later four - way valve OFF
35 sec later compressor ON
3. Defrost Flow Chart
The defrosting shall proceed by the integrating operation time, outdoor temperature
and outdoor heat exchanger temperature as follows.
(Not defrosted for 10 minutes)
Heating operation start : Compressor ON
Outdoor heat exchanger temperature:
Over +13°C
or
Compressor ON time: Maximum 15 minutes
Defrost end
Compressor
integrating
operation:
Over 17 min.
Outdoor
heat exchanger
temperature:
Below - 9°C
Outdoor
heat exchanger
temperature:
Below - 5°C
Compressor
integrating
operation:
Over 35 min.
2nd and later defrost
Integrating defrost
(Constant monitoring)
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Defrost start
Tn-Tn10 < - 5deg
Tn-Tnb < - 2deg
However, Tn <- 6°C
Compressor
OFF count :
40 times
(Less than 10min.)
1st defrost
Compressor
integrating
operation:
Over 57 min.
Compressor
integrating
operation:
Over 210 min.
Outdoor
heat exchanger
temperature:
Below - 3°C
Compressor
integrating
operation:
Over 210 min.
Outdoor
heat exchanger
temperature:
Below - 5°C
=
(Ta - Tn > 5°C)
=
(and after 5
minutes,
if the - 5°C)
(and after 30
minutes,
if the - 3°C)
Tn - 25°C
Содержание AO*G24LFLAO*G24LFCC
Страница 3: ......
Страница 4: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 25: ...2 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 63: ......
Страница 64: ...3 APPENDING DATA R410A WALL MOUNTED type INVERTER ...
Страница 75: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Oct 2012 Printed in Japan ...