Trouble shooting 80
Outdoor air unit - No Power
Forecast of Cause :
1. Power Supply failure 2. Outside cause 3. Electrical Component defective
Is not the breaker down?
Check Point 1 : Power supply
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may
cause harmonic wave).
Check the complete insulation of grounding.
OK
Check protector open / short
If the protector is open circuit, replace it.
Check Point 2 : Check Protector (20A)
04-88
+1
OK (No short circuit)
Check AC line (L-N) open / short
Check Point 3 : Check AC line
NG (Short circuit)
Disconnect the wire between Filter PCB and reactor,
check short circuit of AC line.
If there is short circuit, replace the Filter PCB.
Check Point 4 : Check short circuit Filter PCB
OK (No short circuit)
Connect the disconnected wire(s) on the check point 4,
disconnect the wire between Diode bridge and Capacitor,
check short circuit of AC line.
If there is short circuit, replace the Diode bridge.
Check Point 5 : Check short circuit Diode bridge
OK (No short circuit)
Connect the disconnected wire(s) on the check point 5,
disconnect the wire between Capacitor and Filter PCB,
check short circuit of AC line.
If there is short circuit, replace the Capacitor.
Check Point 6 : Check short circuit Capacitor
OK (No short circuit)
Connect the disconnected wire(s) on the check point 6,
disconnect the wire of Fan motor, check short circuit of
AC line.
If there is short circuit, replace the Power supply PCB.
Check Point 7 :
Check short circuit Power supply PCB
OK (No short circuit)
Check open / short of FAN motor
Refer to the Service Parts Information 21
If there is short circuit, replace FAN motor.
Check Point 8 : Check Fan Motor
Disconnect the connector (CN200) on the Power supply PCB
and check the short circuit
1. DC12V line ( CN200 Pin 1- 5 )
2. DC 5V Line ( CN200 Pin 1 - 3 )
3. DC 15V-1 Line ( CN500 Pin 3 - 4 )
4. DC 15V-2 Line ( CN530 Pin 3 - 4 )
If one of them is short circuit, replace the Power supply PCB
Check Point 9 : Short circuit check on DC circuit
Disconnect the CN10 (EEV1) on the Main PCB, and check short circuit
on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, replace the EEV coil.
Check Point 10 : Check short circuit of actuators (for DC12V)
Disconnect the CNC01 (WRC) on the Main PCB, and check short circuit
on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, check the WRC wire, WRC.
Disconnect the CNB01 (Ext.Out) on the Main PCB, and check short circuit
on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, check the Ext. device or wiring.
Disconnect the CN2 (TransmissionPCB) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, replace the Transmission PCB.
Disconnect the CN22 (Interconnecting wire) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 5.
If the short circuit disappears, replace the Filter PCB.
If the short circuit appears after disconnecing actuators, replace the Main
PCB.
Disconnect the CN14 (SW PCB) on the Main PCB, and check short circuit
on Main PCB CN 4 Pin 1 - 3.
If the short circuit disappears, replace the SW PCB.
Check Point 11 : Check short circuit of actuators (for DC5V)
Disconnect the CN18 (Receiver unit *Option) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 3.
If the short circuit disappears, check the wire, Receiver unit.
Disconnect the CN2 (Transmission PCB) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 3.
If the short circuit disappears, replace the Transmission PCB.
Disconnect the CN21 (Interconnecting wire) on the Main PCB, and check
short circuit on Main PCB CN 4 Pin 1 - 3.
If the short circuit disappears, replace the Power supply PCB.
If the short circuit appears after disconnecing actuators, replace the
Main PCB.
OK (No short circuit)
OK (No short circuit)
OK (No short circuit)
Содержание Airstage UTP-RU01AH
Страница 1: ...SERVICE MANUAL 208 230V 60Hz ...
Страница 5: ...1 TEST RUN ...
Страница 6: ......
Страница 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 59: ...3 INDOOR UNIT OPERATION ...
Страница 60: ......
Страница 82: ......
Страница 83: ...4 TROUBLE SHOOTING ...
Страница 84: ......
Страница 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Страница 208: ...5 APPENDING DATA UNIT ...
Страница 209: ......
Страница 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Страница 216: ...SLIM DUCT SLIM CONCEALED FLOOR TYPE MODELS ARUL7TLAV ARUL9TLAV ARUL12TLAV ARUL14TLAV ARUL18TLAV 05 07 ...
Страница 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Страница 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Страница 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Страница 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Страница 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Страница 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Страница 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Страница 225: ...MODEL UTP RU01CH 05 16 ...
Страница 226: ...MODEL UTP RU04BH 05 17 ...
Страница 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Страница 228: ...MODELS AAUA96TLAV 05 19 ...
Страница 229: ...MODELS ARUV12TLAV ARUV18TLAV ARUV24TLAV ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV 5 2 5 Vertical Air Handler 05 20 ...
Страница 230: ...6 DISASSEMBLY PROCESS ...
Страница 245: ......