Rush Current Limiting Resistor
Temp Rise Protection
Inverter PCB
1. Magnetic relay (for INV) coil side wiring disconnection, open
2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open
3. Magnetic relay activation circuit defective
4. Main PCB to Inverter PCB wiring disconnection, open
5. Main PCB output
AC208- 230V
on CN130 defective
Main PCB defective (output
AC208- 230V
on CN130 for Magnetic relay (INV) defective)
"Protection stop by "Rush current limiting resistor temperature rise detection''
of inverter PCB" was generated 2 times.
OK
OK
OK
Check Point 1 : Check the magnetic relay (for invertert) coil side wiring
Connector and wiring connection state check
Cable open check
Cable open check
Check Point 2 : Check Power supply to Filter PCB (INV) to inverter PCB wiring
Connector and wiring connection state check
Check Point 3-1 : Magnetic relay activation circuit
Chack the DC Voltage (12V) of
CN330 on
INVERTER PCB
Check Point 5 : Main PCB output
AC208- 230V
for Magnetic relay
Check the
AC208- 230V
of CN130 on Main PCB
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 6 8. 2
Error Code : 9 U / 6 8
Trouble shooting 33 E68. 2
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
OK
OK
Check Point 4 : Check the wiring (Main PCB to Inverter PCB)
Replace Inverter PCB
NG
Check the wiring connection.
(CN138 on Main PCB to CN330 on Inverter PCB)
Check Point 6 : Replace Main PCB
Change Main PCB and set up the original address.
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
04-42
Содержание Airstage UTP-RU01AH
Страница 1: ...SERVICE MANUAL 208 230V 60Hz ...
Страница 5: ...1 TEST RUN ...
Страница 6: ......
Страница 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 59: ...3 INDOOR UNIT OPERATION ...
Страница 60: ......
Страница 82: ......
Страница 83: ...4 TROUBLE SHOOTING ...
Страница 84: ......
Страница 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Страница 208: ...5 APPENDING DATA UNIT ...
Страница 209: ......
Страница 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Страница 216: ...SLIM DUCT SLIM CONCEALED FLOOR TYPE MODELS ARUL7TLAV ARUL9TLAV ARUL12TLAV ARUL14TLAV ARUL18TLAV 05 07 ...
Страница 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Страница 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Страница 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Страница 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Страница 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Страница 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Страница 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Страница 225: ...MODEL UTP RU01CH 05 16 ...
Страница 226: ...MODEL UTP RU04BH 05 17 ...
Страница 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Страница 228: ...MODELS AAUA96TLAV 05 19 ...
Страница 229: ...MODELS ARUV12TLAV ARUV18TLAV ARUV24TLAV ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV 5 2 5 Vertical Air Handler 05 20 ...
Страница 230: ...6 DISASSEMBLY PROCESS ...
Страница 245: ......