01-08
Check Item
Check contents
Judgement
Present Status
Number of ref. circuit connected in the network system : ______, Ref. addresses :_______ _______________(00
99)
VRF
Network
System
Network
Configuration
No. of IUs & OUs
For one VRF Network System
(IU
400 & OU
100)
IU number : _____
OU number: _____
No. of System Controller
One System Controller per VRF Network System
No. of Touch panel controller (TPC)
Connectable Nos. 16
Total 16 Nos.
Per VRF Network System
(including one Network
Converter for LonWorks)
TPC: _____
No. of Central RC (CRC)
Connectable Nos. 16
CRC: ______
No. of Network Convert for Group RC
Connectable Nos. 64
Group RC: _____
No. of Signal Amplifier (SA) 40
Detail contents
:
No. of SA (filter mode OFF) 8
No. of SA (filter mode ON ) 32
One per 1640ft.(500m) transmission line length OR,
One per 1312ft.(400m) transmission line length
between units OR,
One per every 64 number of connected units OR,
One per every master OU if total number of
connected Indoor Units 320
Number of Signal
Amplifier :________
No. of Network Convertor ( 100)
One for each separate Room Air
-
conditioning system
Total:_______
No. of BACnet Gateway
One BACnet Gateway per VRF Network System
Total: _______
Terminal Register
One per Network Segment (refer to table -9)
Total: _______
No. of Network Convertor for LonWorks
One per VRF Network System (IU 128 & OU
100)
NOTE: Special VRF Network system configuration
IU number : _____
OU number: _____
Check Item
Check contents
Judgement
Present Status
Number of ref. circuit connected in the network system : ______, Ref. addresses :_______________________(00 99)
VRF
Network
System
Terminal
Resistance of
transmission
line
Terminal resistance of transmission line:
From device with connected terminal
resistance (OU or SA) to the most
distance device
50 ohm ( Resistance value) 180 ohm
OK /
Not OK
In- between
OU (add____) & SA (add___)
OK /
Not OK
In- between
SA (add____) & RB (add___)
OK /
Not OK
In- between
OU (add____) & SA (add___)
1-2-5 Transmission wire installation inspection sheet 3/3
Содержание Airstage UTP-RU01AH
Страница 1: ...SERVICE MANUAL 208 230V 60Hz ...
Страница 5: ...1 TEST RUN ...
Страница 6: ......
Страница 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 59: ...3 INDOOR UNIT OPERATION ...
Страница 60: ......
Страница 82: ......
Страница 83: ...4 TROUBLE SHOOTING ...
Страница 84: ......
Страница 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Страница 208: ...5 APPENDING DATA UNIT ...
Страница 209: ......
Страница 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Страница 216: ...SLIM DUCT SLIM CONCEALED FLOOR TYPE MODELS ARUL7TLAV ARUL9TLAV ARUL12TLAV ARUL14TLAV ARUL18TLAV 05 07 ...
Страница 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Страница 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Страница 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Страница 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Страница 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Страница 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Страница 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Страница 225: ...MODEL UTP RU01CH 05 16 ...
Страница 226: ...MODEL UTP RU04BH 05 17 ...
Страница 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Страница 228: ...MODELS AAUA96TLAV 05 19 ...
Страница 229: ...MODELS ARUV12TLAV ARUV18TLAV ARUV24TLAV ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV 5 2 5 Vertical Air Handler 05 20 ...
Страница 230: ...6 DISASSEMBLY PROCESS ...
Страница 245: ......