01-09
Check Item
Check contents
Judgement
Present Status
Ref. circuit name : _________________________________, Ref. address: ______________ (00 99)
Refrigerant
system
piping
Outlook
Insulation & Fastening
Insulated without gap & properly fastened (Yes / No)
Yes / No
Suction line filter
Is there any external filter in the suction line
Yes / No
Oil Trap
If Distance between OUs 2m ,
Place oil trap both at suction & at Discharge line
Yes / No
Not applicable
Piping
Actual Pipe Length
Between Master OU and farthest IU
( 541ft./165m)
(feet)
Between first separation tube and farthest IU ( 197ft./60m)
(feet)
Total Pipe Length
( 3280ft./1000m)
(feet)
Between OU and OU branch kit
( 9ft./3m)
(feet)
Between farthest OU and first OU branch kit ( 39ft./12m)
(feet)
Between RB units (for multi type RB series connection) (
3ft./1m)
(feet)
Height Difference
Between OU and IU (when OU is installed above)
( 164ft./50m)
(feet)
Between OU and IU (when OU is installed below)
( 131ft./40m)
(feet)
Between IUs
( 49ft./15m)
(feet)
Between OUs
( 1.6ft./0.5m)
(feet)
Between RB units
( 49ft./15m)
(feet)
Between RB unit and IU
( 16ft./5m)
(feet)
Check Item
Check contents
Judgement
Present Status
Ref. circuit name: ____________________________________, Ref. address: _____(00 99)
For single
type & multi
type RB Units
Piping layout
(Between RB & IU)
Existence of additional RB in between RB branch port and indoor
unit is prohibited
Correct
Not correct
For multi type
RB Unit
Branch port piping layout
(RB branch port vs. IU
connection pattern)
1)
Number of free branch port more than one is prohibited
Correct
Not correct
For single type
RB unit
For multi type
RB unit
1 free blanch
2 free branch
3 free branch
1-2-6 Piping installation inspection sheet 1/2
Other check point of separation tube
Bending of connection pipe toward separation tube.
Like the figure, adjust the pipe angle so as to be within 3-degree angle.
( 3° )
( 3° )
0 to 26 mm
19-11/16in. (0.5m)
0 to 26 mm
Connection pipe
Separation tube
to Outdoor unit
to Outdoor unit
Leave the distance 19-11/16in.(0.5m) or more for straight part to outdoor unit branch kit.
to Outdoor unit
to Outdoor unit
to Outdoor unit
to Outdoor unit
to Outdoor unit
to RB unit or
Indoor unit (To
main pipe
19-11/16in.(0.5m) or
more
19-11/16in.(0.5m) or more
to RB unit or
Indoor unit (To
main pipe
Содержание Airstage UTP-RU01AH
Страница 1: ...SERVICE MANUAL 208 230V 60Hz ...
Страница 5: ...1 TEST RUN ...
Страница 6: ......
Страница 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 59: ...3 INDOOR UNIT OPERATION ...
Страница 60: ......
Страница 82: ......
Страница 83: ...4 TROUBLE SHOOTING ...
Страница 84: ......
Страница 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Страница 208: ...5 APPENDING DATA UNIT ...
Страница 209: ......
Страница 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Страница 216: ...SLIM DUCT SLIM CONCEALED FLOOR TYPE MODELS ARUL7TLAV ARUL9TLAV ARUL12TLAV ARUL14TLAV ARUL18TLAV 05 07 ...
Страница 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Страница 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Страница 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Страница 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Страница 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Страница 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Страница 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Страница 225: ...MODEL UTP RU01CH 05 16 ...
Страница 226: ...MODEL UTP RU04BH 05 17 ...
Страница 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Страница 228: ...MODELS AAUA96TLAV 05 19 ...
Страница 229: ...MODELS ARUV12TLAV ARUV18TLAV ARUV24TLAV ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV 5 2 5 Vertical Air Handler 05 20 ...
Страница 230: ...6 DISASSEMBLY PROCESS ...
Страница 245: ......