4-4-2 Work procedure after the backup operation
1. Refrigerant shortage at the backup operation
1. On Cooling operation
<How to judge, when refrigerant is deficient>
Refrigerant shortage is judged by the information from "Service tool" during backup operation.
The outdoor unit shall enter the Cooling Main mode or Heating Main mode.
When excessive refrigerant accumulates in the defective outdoor unit during the backup operation,
it becomes capacity shortage by refrigerant shortage.
Running indoor unit's EEV is fully open condition.
>>> It displays corresponding indoor unit's EEV on the chart at the bottom of the monitor.
If there is no sign of closing the EEV from fully opened condition.
It often creates "Low pressure protection stop".
>>> When LPS < 14.5psi(0.1MPa) for 10 minutes or When LPS < 7.25psi(0.05Mpa)
If one of this condition happens 5 times within 180 minutes, the system stops permanently.
2. On Heating operation
EEV1 opens at 480 pulse. (fully open)
EEV2 opens at 480 pulse. (fully open)
Suction superheat is too high, when the condition is following
TH9 < Th7, TH10 < TH8, TH2 TH3
LPS : Low pressure sensor detection value
EEV1 : Expansion valve #1
EEV2 : Expansion valve #2
TH2 : Outdoor temperature sensor detection value
TH3 : Suction temperature sensor detection value
TH7 : Heat -Ex.1 gas temparture sensor detection value
TH8 : Heat -Ex.2 gas temparture sensor detection value
TH9 : Heat -Ex.1 liquid temparture sensor detection value
TH10 : Heat -Ex.2 liquid temparture sensor detection value
The meaning of the sign
It often creates "Low pressure protection stop".
>>> When LPS < 14.5psi(0.1MPa) for 10 minutes or When LPS < 7.25psi(0.05Mpa)
If one of this condition happens 5 times within 180 minutes, the system stops permanently.
Note: The suctin SH can be larger temprary at the start up, oil recovery, defrosting.
Even if the lowpressure protection does not occur, keep watching the operating condition for a while.
04-93
Содержание Airstage UTP-RU01AH
Страница 1: ...SERVICE MANUAL 208 230V 60Hz ...
Страница 5: ...1 TEST RUN ...
Страница 6: ......
Страница 34: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 59: ...3 INDOOR UNIT OPERATION ...
Страница 60: ......
Страница 82: ......
Страница 83: ...4 TROUBLE SHOOTING ...
Страница 84: ......
Страница 186: ...04 96 0 24 AOUA120 208 230 AOUA72 90 0 19 RED WHITE BLACK U V W ...
Страница 208: ...5 APPENDING DATA UNIT ...
Страница 209: ......
Страница 215: ...CASSETTE TYPE MODELS AUUB18TLAV AUUB24TLAV AUUB30TLAV AUUB36TLAV 05 06 ...
Страница 216: ...SLIM DUCT SLIM CONCEALED FLOOR TYPE MODELS ARUL7TLAV ARUL9TLAV ARUL12TLAV ARUL14TLAV ARUL18TLAV 05 07 ...
Страница 217: ...MEDIUM STATIC PRESSURE DUCT TYPE MODEL ARUM24TLAV 05 08 MODEL ARUM30TLAV ARUM36TLAV ...
Страница 218: ...HIGH STATIC PRESSURE DUCT TYPE MODELS ARUH36TLAV ARUH48TLAV ARUH60TLAV 05 09 ...
Страница 219: ...FLOOR CEILING TYPE MODELS ABUA12TLAV ABUA14TLAV ABUA18TLAV ABUA24TLAV 05 10 ...
Страница 220: ...CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV INDOOR UNITS INDOOR UNITS 05 11 ...
Страница 221: ...WALL MOUNTED TYPE MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 05 12 ...
Страница 222: ...MODELS ASUB18TLAV ASUB24TLAV 05 13 ...
Страница 224: ...MODEL UTP RU01AH MODEL UTP RU01BH 5 2 3 RB Unit 05 15 ...
Страница 225: ...MODEL UTP RU01CH 05 16 ...
Страница 226: ...MODEL UTP RU04BH 05 17 ...
Страница 227: ...MODELS AAUA48TLAV 5 2 4 Outdoor Air Unit 05 18 MODELS AAUA72TLAV ...
Страница 228: ...MODELS AAUA96TLAV 05 19 ...
Страница 229: ...MODELS ARUV12TLAV ARUV18TLAV ARUV24TLAV ARUV30TLAV ARUV36TLAV ARUV48TLAV ARUV60TLAV 5 2 5 Vertical Air Handler 05 20 ...
Страница 230: ...6 DISASSEMBLY PROCESS ...
Страница 245: ......