...In a Snowy Area (for Heat Pump-type Systems)

Install the outdoor unit on a raised platform that is higher than 
drifting snow.

When Connecting Refrigerant Tubing

•  Keep all tubing runs as short as possible.
• Use the 

fl

 are method for connecting tubing.

•  Apply refrigerant lubricant to the matching surfaces of the 

fl

 are and union tubes before connecting them, then tighten 

the nut with a torque wrench for a leak-free connection.

•  Check carefully for leaks before opening the refrigerant 

valves.

When Servicing

•  Turn the power OFF at the main circuit breaker panel 

before opening the unit to check or repair electrical parts 
and wiring.

•  Keep your fingers and clothing away from any moving 

parts.

•  Clean up the site after you finish, remembering to check 

that no metal scraps or bits of wiring have been left inside 
the unit being serviced.

•  After installation, explain correct operation to the customer, 

using the operating manual.

 WARNING

Never touch electrical components immediately 
after the power supply has been turned off. Electri-
cal shock may occur. After turning off the power, 
always wait 5 minutes or more before touching 
electrical components.

Cancer and Reproductive Harm - www.P65Warnings.ca.gov.

2. ABOUT THIS PRODUCT

2.1. Precautions for using R410A refrigerant

The basic installation work procedures are the same 
as conventional refrigerant models. 
However, pay careful attention to the following points:

  Since the working pressure is 1.6 times higher than 

that of conventional refrigerant (R22) models, some 
of the piping and installation and service tools are 
special. (See the following table.)

 

Especially, when replacing a conventional refriger-
ant (R22) model with a new refrigerant R410A model, 
always replace the conventional piping and 

fl

 are nuts 

with the R410A piping and 

fl

 are nuts.

   Models that use refrigerant R410A have a different 

charging port thread diameter to prevent errone-
ous charging with conventional refrigerant (R22) 
and for safety. Therefore, check beforehand. 
[The charging port thread diameter for R410A is 
1/2-20 UNF.]

   Be careful that foreign matter (oil, water, etc.) 

does not enter the piping than with conventional 
refrigerant (R22) models. Also, when storing the 
piping, securely seal the openings by pinching, 
taping, etc.

   When charging the refrigerant, take into account 

the slight change in the composition of the gas 
and liquid phases. A always charge from the liquid 
phase where refrigerant composition is stable.

2.2. Special tools for R410A refrigerant

Tool name

Contents of change

Gauge 

manifold

Pressure is high and cannot be measured 
with a R22 gauge. To prevent erroneous 
mixing of other refrigerants, the diameter 
of each port has been changed.
It is recommended the gauge with seals 
-30 inHg to 768 psi (-0.1 to 5.3 MPa) for 
high pressure. -30 inHg to 551 psi (-0.1 to 
3.8 MPa) for low pressure.

Charge 

hose 

To increase pressure resistance, the hose 
material and base size were changed. 

Vacuum 

pump 

A conventional vacuum pump can be used 
by installing a vacuum pump adapter. 

Gas leakage 

detector

Special gas leakage detector for HFC 
refrigerant R410A.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable 
that the amount of residual oil is less than 0.004 oz/100 ft 
(40 mg/10 m). Do not use copper pipes having a collapsed, 
deformed or discolored portion (especially on the interior 
surface). Otherwise, the expansion value or capillary tube 
may become blocked with contaminants. As an air conditioner 
using R410A incurs pressure higher than when using R22, it 
is necessary to choose adequate materials. Thicknesses of 
copper pipes used with R410A are as shown in the table. (Refer 
to “3.1. Type of copper pipe and insulation material”) Never 
use copper pipes thinner than that in the table even when it is 
available on the market. 

9374318599-02_IM.indb   2

9374318599-02_IM.indb   2

9/26/2018   11:04:19 AM

9/26/2018   11:04:19 AM

Содержание AirStage AU12

Страница 1: ...assette compacte UNIDAD INTERIOR Tipo casete INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9374318599 02_IM indb 1 9374318599 02_IM indb 1 9 26 2018 11 04 17 AM 9 26 2018 11 04 17 AM ...

Страница 2: ...TION This symbol refers to a hazard or unsafe practice which can result in personal injury and the potential for product or property damage Hazard alerting symbols Electrical Safety alert If Necessary Get Help These instructions are all you need for most installation sites and maintenance conditions If you require help for a special problem contact our sales service outlet or your certified dealer...

Страница 3: ...ve a different charging port thread diameter to prevent errone ous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be careful that foreign matter oil water etc does not enter the piping than with conventional refrigerant R22 models Also when storing the piping securely seal the openings by pinching tapin...

Страница 4: ...Fujitsu General products are manufactured to metric units and tolerances United States custom ary units are provided for reference only In cases where exact dimensions and tolerances are re quired always refer to metric units 2 4 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non prescribed parts can cause se...

Страница 5: ...or connecting the outdoor unit to the indoor unit and insulation material is available for purchase locally When you purchase them please specify the following Deoxidized annealed copper pipe for refrigerant piping as shown in the table MODEL Diameter Liquid pipe Gas pipe AU7 9 12 1 4 in 6 35 mm 3 8 in 9 52 mm AU18 1 4 in 6 35 mm 1 2 in 12 70 mm Use pipe with water resistant heat insulation CAUTIO...

Страница 6: ...m or more 3 4 Electrical requirement Always make the air conditioner power supply a special branch circuit and provide a special switch and receptacle Do not extend the power cable WARNING Refer to local codes for acceptable cable type Cable Cable size Remarks Connection cable 14AWG 3 cable Earth Ground 1Φ 208 230 V Max Cable Length Limit voltage drop to less than 2 In crease cable gauge if voltag...

Страница 7: ...d or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the unit is only attached to the ceiling panel frame there is a risk that the unit will come loose Please take precaution When fastening the hangers make the bolt positions uniform Perform final tightening by tightening the double nut firmly 20 7 8 530 Hanging bolt position A Cassette gr...

Страница 8: ...door section of drain pipe If it is impossible to have sufficient gradient of pipe per form drain lift up Pipe size Drain pipe 3 4 in O D 1 1 16 in Hanging fittings 59 1 16 to 6 ft 3 4in 1 5 to 2 m 3 4 in Downward gradient 1 100 to 1 50 Rise PROHIBITED Trap Air bleeding When lifting up drain Height of inclined pipe should be less than 27 9 16 in 700 mm from the ceiling Arise dimension over this ra...

Страница 9: ...ause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 80 use heat insulation that is 9 16 in 15 mm or thicker and if the expected humidity exceeds 8...

Страница 10: ... sharp bends If the pipe is bent repeatedly at the same place it will break If pipes are shaped by hand be careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them anymore Do not bend or stretch the pipes more than 3 times 6 3 3 Pipe connection CAUTION Be sure to conn...

Страница 11: ...ith those of outdoor unit or branch box Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal blocks In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Connect the connection cables firmly to the terminal board Imperfect inst...

Страница 12: ...n in terminal label Earth Ground both the indoor outdoor and branch box units by attaching a earth ground cable Unit must be earthed grounded in compliance with the applicable local and national cables Be sure to refer to the diagrams for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wir ing instructions or limitations Wired ...

Страница 13: ...ntroller PC board and PC board parts directly with your hands Do not wire the remote controller cable together with or parallel to the connection cables and power sup ply cables of the INDOOR UNIT OUTDOOR UNIT and BRANCH BOX It may cause erroneous operation When installing cable near a source of electromagnetic waves use shielded wire Do not set the DIP switches either on the air condi tioner or t...

Страница 14: ...ller DIP switches Example 1 2 3 4 5 6 DIP switch 1 Front case back side OFF ON ON Factory setting NO SW state Detail OFF ON DIP switch 1 SW 1 Cannot be used Do not change SW 2 Dual remote controller setting Refer to DUAL REMOTE CONTROLLERS in 10 SPECIAL INSTALLATION METHODS SW 3 Use prohibited Do not change SW 4 Use prohibited Do not change SW 5 Use prohibited Do not change SW 6 Invalidity Validit...

Страница 15: ...he grille assembly is directionally relative to the air conditioner body Install so that there is no gap between the grille assembly and the air conditioner body The cassette grille is equipped with an accessory to prevent the grill to completely open Be sure to read the Installation manual included with the cassette grille before installation 10 FUNCTION SETTING This procedure changes the functio...

Страница 16: ...iption 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication 2 Ceiling height Select the appropriate ceiling height according to the place of installation Factory setting Function number Setting value Setting description 20 00 Standard 2 7 m 9 ft 01 High ceiling 3 0 m 10 ft The ceiling height values are for the 4 way outlet Do not change this setting i...

Страница 17: ...lation Heat insulation conditions differ according to the installed environment Standard insulation 00 allows system to rapidly respond to the cooling or heating load changes High insulation 01 is when the heat insulation structure of the building is high and does not require system to rapidly respond to cooling or heating load changes When High insulation 01 is selected Overheating overcooling is...

Страница 18: ...ting according to the installed environment To change this setting set Function 42 to Both 01 Ensure that the Thermo Sensor icon is displayed on the remote controller screen Factory setting Function number Setting value Setting description 92 For cooling 93 For heating 00 No correction 0 0 F 0 0 C 01 No correction 0 0 F 0 0 C 02 1 F 0 5 C More Cooling Less Heating 03 2 F 1 0 C 04 3 F 1 5 C 05 4 F ...

Страница 19: ...tion indicator lamp and Timer indicator lamp will simultaneously flash during the test run mode Heating test run will begin in a few minutes when HEAT is selected by the remote controller reverse cycle model only 13 OPTIONAL KIT INSTALLATION WARNING Refer to local codes for acceptable cable type This air conditioner can be connected with the following optional kits Fresh air intake kit External in...

Страница 20: ...tage error stoppage permanently Voltage error can restore Over current protected operation stoppage permanently PFC hardware error 6 5 Outdoor unit IPM error Trip terminal L error 6 10 Outdoor unit Display panel error Microcomputers communication error 7 1 Outdoor unit Discharge thermistor error Discharge thermistor 1 error 7 2 Outdoor unit Compressor thermistor error Compressor thermistor 1 error...

Страница 21: ... the wired remote controller Self diagnosis If an error occurs the following display will be shown Er will appear in the set room temperature display Error code Example Self diagnosis 9374318599 02_IM indb 20 9374318599 02_IM indb 20 9 26 2018 11 04 23 AM 9 26 2018 11 04 23 AM ...

Отзывы: