background image

En-11

Strip 3/8 in. (10 mm)

Sleeve

Ring terminal

Screw with 
special washer

Screw with 
special washer

Ring terminal

Ring 
terminal

Wire

Wire

Terminal block

Terminal 
board

Table 1

Tightening torque

M4 screw

11 to 16 lbf·in (1.2 to 1.8 N·m)

 WARNING

Use ring terminals and tighten the terminal screws to the 
speci

fi

 ed torques, otherwise, abnormal overheating may 

be produced and possibly cause heavy damage inside the 
unit.

7.1. Wiring system diagram

 WARNING

Disconnect switch for over current protection given 
in the system diagram is to be installed between the 
indoor unit and the outdoor unit, branch box.

 CAUTION

Tighten the indoor unit connection cable and power 
supply indoor and outdoor unit, branch box terminal 
board connections 

fi

 rmly with the terminal board 

screws. Faulty connection may cause a 

fi

 re.

If the indoor unit connection cable and power sup-
ply are wired incorrectly, the air conditioner may be 
damaged.
Connect the indoor unit connection cable by match-
ing the numbers of the outdoor, branch box and 
indoor units terminal board numbers as shown in 
terminal label.
Earth (Ground) both the indoor, outdoor and branch 
box units by attaching a earth (ground) cable.
Unit must be earthed (grounded) in compliance with 
the applicable local and national cables.
Be sure to refer to the diagrams for do correct 

fi

 eld 

wiring. Wrong wiring causes malfunction of the unit.
Check local electrical rules and also any speci

fi

 c wir-

ing instructions or limitations.

Wired remote controller cable

Red
White
Black

Indoor 

unit side

Connection cable to outdoor unit or BRANCH BOX

INDOOR UNIT SIDE

INDOOR 

UNIT

OUTDOOR UNIT 

or BRANCH BOX

TERMINAL

DISCONNECT 

SWITCH

(Locally purchased)

Earth 

(ground) line

14AWG
(Inter-unit)
Power lines

Power line

Control line

Remote controller line

Disconnect Switch - Locally purchased if required by local 
code.
Select the correct capacity of disconnect switch according to 
the load.

7.2. Connection cable preparation

Keep the earth (ground) wire longer than the other wires.

Power supply cable 
or connection cable

13/16 in. (20 mm)

1-3/16 in. (30 mm) or more

Earth 
(Ground) 
wire

• Use a 4-core wire cable.

7.3. Connection of wiring

(1)  Remove the control box cover and install each connec-

tion wire.

Screw

Control box cover

9374318599-02_IM.indb   11

9374318599-02_IM.indb   11

9/26/2018   11:04:20 AM

9/26/2018   11:04:20 AM

Содержание AirStage AU12

Страница 1: ...assette compacte UNIDAD INTERIOR Tipo casete INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9374318599 02_IM indb 1 9374318599 02_IM indb 1 9 26 2018 11 04 17 AM 9 26 2018 11 04 17 AM ...

Страница 2: ...TION This symbol refers to a hazard or unsafe practice which can result in personal injury and the potential for product or property damage Hazard alerting symbols Electrical Safety alert If Necessary Get Help These instructions are all you need for most installation sites and maintenance conditions If you require help for a special problem contact our sales service outlet or your certified dealer...

Страница 3: ...ve a different charging port thread diameter to prevent errone ous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be careful that foreign matter oil water etc does not enter the piping than with conventional refrigerant R22 models Also when storing the piping securely seal the openings by pinching tapin...

Страница 4: ...Fujitsu General products are manufactured to metric units and tolerances United States custom ary units are provided for reference only In cases where exact dimensions and tolerances are re quired always refer to metric units 2 4 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non prescribed parts can cause se...

Страница 5: ...or connecting the outdoor unit to the indoor unit and insulation material is available for purchase locally When you purchase them please specify the following Deoxidized annealed copper pipe for refrigerant piping as shown in the table MODEL Diameter Liquid pipe Gas pipe AU7 9 12 1 4 in 6 35 mm 3 8 in 9 52 mm AU18 1 4 in 6 35 mm 1 2 in 12 70 mm Use pipe with water resistant heat insulation CAUTIO...

Страница 6: ...m or more 3 4 Electrical requirement Always make the air conditioner power supply a special branch circuit and provide a special switch and receptacle Do not extend the power cable WARNING Refer to local codes for acceptable cable type Cable Cable size Remarks Connection cable 14AWG 3 cable Earth Ground 1Φ 208 230 V Max Cable Length Limit voltage drop to less than 2 In crease cable gauge if voltag...

Страница 7: ...d or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries If the unit is only attached to the ceiling panel frame there is a risk that the unit will come loose Please take precaution When fastening the hangers make the bolt positions uniform Perform final tightening by tightening the double nut firmly 20 7 8 530 Hanging bolt position A Cassette gr...

Страница 8: ...door section of drain pipe If it is impossible to have sufficient gradient of pipe per form drain lift up Pipe size Drain pipe 3 4 in O D 1 1 16 in Hanging fittings 59 1 16 to 6 ft 3 4in 1 5 to 2 m 3 4 in Downward gradient 1 100 to 1 50 Rise PROHIBITED Trap Air bleeding When lifting up drain Height of inclined pipe should be less than 27 9 16 in 700 mm from the ceiling Arise dimension over this ra...

Страница 9: ...ause water leaks Use heat insulation with heat resistance above 248 F 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 80 use heat insulation that is 9 16 in 15 mm or thicker and if the expected humidity exceeds 8...

Страница 10: ... sharp bends If the pipe is bent repeatedly at the same place it will break If pipes are shaped by hand be careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them anymore Do not bend or stretch the pipes more than 3 times 6 3 3 Pipe connection CAUTION Be sure to conn...

Страница 11: ...ith those of outdoor unit or branch box Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal blocks In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Connect the connection cables firmly to the terminal board Imperfect inst...

Страница 12: ...n in terminal label Earth Ground both the indoor outdoor and branch box units by attaching a earth ground cable Unit must be earthed grounded in compliance with the applicable local and national cables Be sure to refer to the diagrams for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wir ing instructions or limitations Wired ...

Страница 13: ...ntroller PC board and PC board parts directly with your hands Do not wire the remote controller cable together with or parallel to the connection cables and power sup ply cables of the INDOOR UNIT OUTDOOR UNIT and BRANCH BOX It may cause erroneous operation When installing cable near a source of electromagnetic waves use shielded wire Do not set the DIP switches either on the air condi tioner or t...

Страница 14: ...ller DIP switches Example 1 2 3 4 5 6 DIP switch 1 Front case back side OFF ON ON Factory setting NO SW state Detail OFF ON DIP switch 1 SW 1 Cannot be used Do not change SW 2 Dual remote controller setting Refer to DUAL REMOTE CONTROLLERS in 10 SPECIAL INSTALLATION METHODS SW 3 Use prohibited Do not change SW 4 Use prohibited Do not change SW 5 Use prohibited Do not change SW 6 Invalidity Validit...

Страница 15: ...he grille assembly is directionally relative to the air conditioner body Install so that there is no gap between the grille assembly and the air conditioner body The cassette grille is equipped with an accessory to prevent the grill to completely open Be sure to read the Installation manual included with the cassette grille before installation 10 FUNCTION SETTING This procedure changes the functio...

Страница 16: ...iption 11 00 Standard 2500 hours 01 Long interval 4400 hours 02 Short interval 1250 hours 03 No indication 2 Ceiling height Select the appropriate ceiling height according to the place of installation Factory setting Function number Setting value Setting description 20 00 Standard 2 7 m 9 ft 01 High ceiling 3 0 m 10 ft The ceiling height values are for the 4 way outlet Do not change this setting i...

Страница 17: ...lation Heat insulation conditions differ according to the installed environment Standard insulation 00 allows system to rapidly respond to the cooling or heating load changes High insulation 01 is when the heat insulation structure of the building is high and does not require system to rapidly respond to cooling or heating load changes When High insulation 01 is selected Overheating overcooling is...

Страница 18: ...ting according to the installed environment To change this setting set Function 42 to Both 01 Ensure that the Thermo Sensor icon is displayed on the remote controller screen Factory setting Function number Setting value Setting description 92 For cooling 93 For heating 00 No correction 0 0 F 0 0 C 01 No correction 0 0 F 0 0 C 02 1 F 0 5 C More Cooling Less Heating 03 2 F 1 0 C 04 3 F 1 5 C 05 4 F ...

Страница 19: ...tion indicator lamp and Timer indicator lamp will simultaneously flash during the test run mode Heating test run will begin in a few minutes when HEAT is selected by the remote controller reverse cycle model only 13 OPTIONAL KIT INSTALLATION WARNING Refer to local codes for acceptable cable type This air conditioner can be connected with the following optional kits Fresh air intake kit External in...

Страница 20: ...tage error stoppage permanently Voltage error can restore Over current protected operation stoppage permanently PFC hardware error 6 5 Outdoor unit IPM error Trip terminal L error 6 10 Outdoor unit Display panel error Microcomputers communication error 7 1 Outdoor unit Discharge thermistor error Discharge thermistor 1 error 7 2 Outdoor unit Compressor thermistor error Compressor thermistor 1 error...

Страница 21: ... the wired remote controller Self diagnosis If an error occurs the following display will be shown Er will appear in the set room temperature display Error code Example Self diagnosis 9374318599 02_IM indb 20 9374318599 02_IM indb 20 9 26 2018 11 04 23 AM 9 26 2018 11 04 23 AM ...

Отзывы: