En-6

3.3. Pipe installation

3.3.1. Indoor unit piping direction

The piping can be connected in the 6 directions indicated by (1), (2), (3), (4), (5) and (6) in 
the figure. When the piping is connected in direction (2) or (5), cut along the piping groove 
in the side of the base with a hacksaw.
When connecting the piping in direction (3), (6) cut a notch in the thin wall at the front 
bottom of the base.

(1) Right rear 

outlet

(2) Right outlet

(3) Right bottom 

outlet

(4) Left rear 

outlet

(5) Left outlet

(Rear)

(6) Left bottom 

outlet

3.3.2. Cutting the hole in the wall for connecting the pipes

(1) Cut a 65 mm diameter hole in the wall at the position shown in the following.
(2) Cut the hole so that the outside end is lower (5 to 10 mm) than the inside end.
(3) Always align the center of the wall hole. If misaligned, water leakage will occur.
(4) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap 

with vinyl tape, and stick the pipe through the hole.

(5) For the left piping and the right piping, cut the hole a little lower so that drain water will 

flow freely.

 

For right rear or left rear piping

(The following figure is a front view of the indoor unit installation location.)

Unit: mm

For right rear 
piping

48

59

550

59

Ø65

Ø65

For left rear 
piping

 

For right or left piping

8

16

5

54

54

8

16

5

For right 
piping

For left 
piping

Unit: mm

 

For right bottom or left bottom piping

29

64

182

29

5

3

1

0

5

For right bot-
tom piping

Unit: mm

For left bot-
tom piping

 

* Locally purchased

Fasten with vinyl tape *

5~10 mm

Wall pipe *

Wall cap *

(Inside)

(Outside)

Wall

 WARNING

Always use the wall pipe. If the wall pipe is not used, the cable that is connected between 
the indoor unit and the outdoor unit may touch metal, and cause an electric leakage.

3.3.3. Indoor unit installation

•  Use the included and fasten the indoor unit at 4 locations (

) each at top and the 

middle of the unit.

•  When the unit is set to the wall, use the wall hook bracket and hook the top of the 

indoor unit on the indoor unit wall hook bracket.

124

423

703

154

438

Unit: mm

 WARNING

•  Fix the indoor unit with 4 screws surely. If improperly installed, might cause to injury 

due to the toppling or falling.

•  Install the indoor unit at the place that has adequate strength. Install the indoor unit 

so that the installed unit can withstand the weight of adult body weight.
If improperly installed, might cause accidental injury due to the toppling or falling.

3.3.4. Installing the wall hook bracket

(1)  Install the wall hook bracket so that it is correctly positioned horizontally and vertically. 

If the wall hook bracket is tilted, water will drip to the floor.

(2)  Install the wall hook bracket so that it is strong enough to support the weight of the 

unit.

•  Fasten the wall hook bracket to the wall with 5 or more screws through the holes near 

the outer edge of the bracket.

•  Check that there is no rattle at the wall hook bracket.

Weight

Leveling 
method

Hook the indoor unit to the wall 
hook bracket (2 positions)

Tapping screws 
(large, accessories)

 CAUTION

Install the wall hook bracket level, both horizontally and vertically.

3.3.5. Forming the drain hose and pipe

 CAUTION

•  Insert drain hose and drain cap securely. Drain should slope down to avoid water 

leakage.

•  When inserting the drain hose, no other material than water should be applied. 

Application of other material than water will cause deterioration of the hose, and may 
cause water leakage.

•  After you remove a drain hose, be sure to attach the drain cap.
•  When you secure the piping and drain hose with tape, arrange the drain hose so that 

it is at the bottom of the piping.

•  For drain hose piping in low temperature environment, you need to apply freeze 

protection to prevent a frozen drain hose. 
After cooling operation is performed in low temperature environment (when outdoor 
temperature under 0 °C), water in the drain hose could be frozen. Frozen drain 
water will block the water flow in the hose, and may cause water leakage at the 
indoor unit.

(1) Pass the refrigerant pipe through the piping hole to indoor side.
(2) Arrange the pipes according to the direction of piping.

9378533080-04_IM.indb   6

9378533080-04_IM.indb   6

2022/2/14   15:13:14

2022/2/14   15:13:14

Содержание AGHG12KVCA

Страница 1: ...ut continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware that refrigerants may not contain an odour Keep any required ventilation openings clear of obstruction If the power cable or the connection cable is damaged it must be replaced by the manufacturer its service agent or similar qualified persons...

Страница 2: ...quipment being used is suitable for use with flam mable refrigerants i e nonsparking adequately sealed or intrinsically safe 2 4 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available at hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area 2 5 No ign...

Страница 3: ...ore carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is ava...

Страница 4: ...be purchased separately Additional materials Connection pipe assembly Wall cap Connection cable 4 conductor Saddle Wall pipe Drain hose Decorative tape Tapping screws Vinyl tape Putty Sealant Refrigeration armored tape Insulated staples or clamps for connecting wire refer to your electrical cables Clamps or saddles to secure refrigerant pip ing Refrigeration lubricant 1 1 2 3 Pipe requirement CAUT...

Страница 5: ...ote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit When installing pipes shorter tha...

Страница 6: ...e top of the indoor unit on the indoor unit wall hook bracket 124 423 703 154 438 Unit mm WARNING Fix the indoor unit with 4 screws surely If improperly installed might cause to injury due to the toppling or falling Install the indoor unit at the place that has adequate strength Install the indoor unit so that the installed unit can withstand the weight of adult body weight If improperly installed...

Страница 7: ... from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R32 clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicated in t...

Страница 8: ...cable clamp always fasten the cable at the plastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the ground earth wire Improper earthing grounding work can cause electric shocks Do not use the ground earth screw for the indoor unit to the outdoor unit unless it is specified When the flare nut is tightened properly by your hand ...

Страница 9: ...ON WORK 4 1 Before install optional remote controller When you use optional remote controller some functions may not be used Please use the recommended optional remote controller CAUTION Before installing be sure to disconnect all power supply Don t touch the heat exchanger During installing or removing operation be sure not to have wire caught by parts or draw it hard Or it may result troubles to...

Страница 10: ...he following condition DC 12 V to 24 V 1 mA to 15 mA Operation behavior Input signal type Edge ON OFF When function setting is Operation Stop mode 1 Input signal Command OFF ON Operation ON OFF Stop When function setting is Forced stop mode Input signal Command OFF ON Forced stop ON OFF Normal When the forced stop is triggered indoor unit stops and Operation Stop operation by a remote controller i...

Страница 11: ...fore reconnecting it The function setting will not become active unless the power supply is disconnected and then reconnected 5 1 Function details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function num ber Settin...

Страница 12: ...s Error status Setting record Record any changes to the settings in the following table Function number Function setting Setting value 11 Filter sign 30 Room temperature control for indoor unit sensor Cooling 31 Heating 35 Room temperature control for wired remote controller sensor Cooling 36 Heating 40 Auto restart 42 Room temperature sensor switching 44 Remote controller custom code 46 External ...

Страница 13: ...d remote controller error codes will ap pear on the remote control display Refer to the lamp blinking patterns and error codes in the table An error display is displayed only during operation The error code table contains errors irrelevant to this product as well Error display on the indoor unit TIMER LED1 TIMER Lamp orange LED2 OPERATION lamp green LED3 ECONOMY lamp green OPERATION ECONOMY For wi...

Страница 14: ...otor 1 error Error display Error code Description LED1 orange LED2 green LED3 green 8 9 98 Outdoor unit fan motor 2 error 9 9 99 4 way valve error 10 9 9A Coil expansion valve error 1 10 A1 Discharge temp error 3 10 A3 Compressor temp error 4 10 A4 High pressure error 5 10 A5 Low pressure error 8 10 A8 Refrigerant leakage suspicion 11 10 AC Heat sink temp error 2 13 J2 Branch boxes error Multi spl...

Отзывы: