En-14

Error display

Error code*

Description

LED1

(orange)

LED2

(green)

LED3

(green)

(4)

(4)

44

Human sensor error

(5)

(4)

45

Refrigerant leakage sensor error
Sensor error, and harness 
disconnection/connection failure 
may have occurred.

(1)

(5)

51

Indoor unit fan motor error

(3)

(5)

53

Drain pump error

(4)

(5)

54

Electric air cleaner reverse VDD 
error

(5)

(5)

55

Filter set error

(7)

(5)

57

Damper error 

(8)

(5)

58

Intake grille error

(9)

(5)

59

Indoor unit fan motor 2 error
(Left side fan)

(10)

(5)

5A

Indoor unit fan motor 3 error
(Right side fan)

(15)

(5)

5U

Indoor unit error

(1)

(6)

61

Outdoor unit reverse/missing 
phase and wiring error

(2)

(6)

62

Outdoor unit main PCB 
model information error or 
communication error

(3)

(6)

63

Inverter error 

(4)

(6)

64

Active filter error, PFC circuit error 

(5)

(6)

65

• Trip terminal L error
• IPM temp error

(8)

(6)

68

Outdoor unit rush current limiting 
resister temp. rise error

(10)

(6)

6A

Display PCB microcomputers 
communication error

(1)

(7)

71

Discharge temp. sensor error

(2)

(7)

72

Compressor temp. sensor error

(3)

(7)

73

Outdoor unit Heat Ex. liquid temp. 
sensor error

(4)

(7)

74

Outdoor temp. sensor error

(5)

(7)

75

Suction Gas temp. sensor error

(6)

(7)

76

• 2-way valve temp. sensor error
• 3-way valve temp. sensor error

(7)

(7)

77

Heat sink temp. sensor error

(2)

(8)

82

• Sub-cool Heat Ex. gas inlet 

temp. sensor error

• Sub-cool Heat Ex. gas outlet 

temp. sensor error

(3)

(8)

83

Liquid pipe temp. sensor error

(4)

(8)

84

Current sensor error

(6)

(8)

86

• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error

(4)

(9)

94

Trip detection

(5)

(9)

95

Compressor rotor position 
detection error (permanent stop) 

(7)

(9)

97

Outdoor unit fan motor 1 error

Error display

Error code*

Description

LED1

(orange)

LED2

(green)

LED3

(green)

(8)

(9)

98

Outdoor unit fan motor 2 error

(9)

(9)

99

4-way valve error

(10)

(9)

9A

Coil (expansion valve) error

(1)

(10)

A1

Discharge temp. error

(3)

(10)

A3

Compressor temp. error

(4)

(10)

A4

High pressure error

(5)

(10)

A5

Low pressure error

(8)

(10)

A8

Refrigerant leakage suspicion

(11)

(10)

AC

Heat sink temp error

(2)

(13)

J2

Branch boxes error 
[Multi-split type]

Display mode   : 0.5s ON / 0.5s OFF

   : 0.1s ON / 0.1s OFF
 (  ) : Number of flashing

 

Error code on the wired remote controller (option)

Check the error

1. 

 

If an error occurs, an error icon appears on the “Monitor mode screen”.
Touch the [Status] on the “Monitor mode screen”. The “Status” screen is dis-
played.

2. 

  Touch the [Error Information] on the “Status” screen. The “Error Information” 

screen is displayed. (If there are no errors, the [Error Information] will not be 
displayed.)

3. 

  2-digit numbers correspond to the error code in the table.

Touch the [Next page] (or [Previous page]) to switch to other connected indoor 
units.

1.  

2.  

3.  

Set Temp.

Mode

Menu

Status

Fan

Fri 10:00AM

Unoccupied

Status

Air Flow Direction

VT

Off

1

3

Off

HZ

Economy

Individual

Anti Freeze

Page  1/  4

Monitor

Next
Page

Error
Information

02-01

14,15, 41, 44

Error Information

Page  1/ 5

Address

Error Code

Back

Next
Page

]1]1

10. REFRIGERANT LEAK DETECTION FUNCTION

 

System operation after refrigerant leak detection:

•  Indoor unit starts diffusion operation by high fan speed.  
•  Due to safety reasons, a remote controller cannot stop this operation.
•  

Indoor unit indicates Error code A8 (TIMER lamp [8], OPERATION lamp [10]).
[   ]: Number of flashing

•  Indoor unit makes a warning beep.

(The beep stops by pressing [START/STOP] of the remote controller or [MANUAL 
AUTO] on the indoor unit.)

•  System stops the cooling/heating operation. Forced cooling operation is not available.

9378533080-04_IM.indb   14

9378533080-04_IM.indb   14

2022/2/14   15:13:15

2022/2/14   15:13:15

Содержание AGHG12KVCA

Страница 1: ...ut continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn Be aware that refrigerants may not contain an odour Keep any required ventilation openings clear of obstruction If the power cable or the connection cable is damaged it must be replaced by the manufacturer its service agent or similar qualified persons...

Страница 2: ...quipment being used is suitable for use with flam mable refrigerants i e nonsparking adequately sealed or intrinsically safe 2 4 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available at hand Have a dry powder or CO2 fire extinguisher adjacent to the charging area 2 5 No ign...

Страница 3: ...ore carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its details It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is ava...

Страница 4: ...be purchased separately Additional materials Connection pipe assembly Wall cap Connection cable 4 conductor Saddle Wall pipe Drain hose Decorative tape Tapping screws Vinyl tape Putty Sealant Refrigeration armored tape Insulated staples or clamps for connecting wire refer to your electrical cables Clamps or saddles to secure refrigerant pip ing Refrigeration lubricant 1 1 2 3 Pipe requirement CAUT...

Страница 5: ...ote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise under some signal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit When installing pipes shorter tha...

Страница 6: ...e top of the indoor unit on the indoor unit wall hook bracket 124 423 703 154 438 Unit mm WARNING Fix the indoor unit with 4 screws surely If improperly installed might cause to injury due to the toppling or falling Install the indoor unit at the place that has adequate strength Install the indoor unit so that the installed unit can withstand the weight of adult body weight If improperly installed...

Страница 7: ... from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R32 clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicated in t...

Страница 8: ...cable clamp always fasten the cable at the plastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the ground earth wire Improper earthing grounding work can cause electric shocks Do not use the ground earth screw for the indoor unit to the outdoor unit unless it is specified When the flare nut is tightened properly by your hand ...

Страница 9: ...ON WORK 4 1 Before install optional remote controller When you use optional remote controller some functions may not be used Please use the recommended optional remote controller CAUTION Before installing be sure to disconnect all power supply Don t touch the heat exchanger During installing or removing operation be sure not to have wire caught by parts or draw it hard Or it may result troubles to...

Страница 10: ...he following condition DC 12 V to 24 V 1 mA to 15 mA Operation behavior Input signal type Edge ON OFF When function setting is Operation Stop mode 1 Input signal Command OFF ON Operation ON OFF Stop When function setting is Forced stop mode Input signal Command OFF ON Forced stop ON OFF Normal When the forced stop is triggered indoor unit stops and Operation Stop operation by a remote controller i...

Страница 11: ...fore reconnecting it The function setting will not become active unless the power supply is disconnected and then reconnected 5 1 Function details Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Function num ber Settin...

Страница 12: ...s Error status Setting record Record any changes to the settings in the following table Function number Function setting Setting value 11 Filter sign 30 Room temperature control for indoor unit sensor Cooling 31 Heating 35 Room temperature control for wired remote controller sensor Cooling 36 Heating 40 Auto restart 42 Room temperature sensor switching 44 Remote controller custom code 46 External ...

Страница 13: ...d remote controller error codes will ap pear on the remote control display Refer to the lamp blinking patterns and error codes in the table An error display is displayed only during operation The error code table contains errors irrelevant to this product as well Error display on the indoor unit TIMER LED1 TIMER Lamp orange LED2 OPERATION lamp green LED3 ECONOMY lamp green OPERATION ECONOMY For wi...

Страница 14: ...otor 1 error Error display Error code Description LED1 orange LED2 green LED3 green 8 9 98 Outdoor unit fan motor 2 error 9 9 99 4 way valve error 10 9 9A Coil expansion valve error 1 10 A1 Discharge temp error 3 10 A3 Compressor temp error 4 10 A4 High pressure error 5 10 A5 Low pressure error 8 10 A8 Refrigerant leakage suspicion 11 10 AC Heat sink temp error 2 13 J2 Branch boxes error Multi spl...

Отзывы: