En-14
Error display
Error code*
Description
LED1
(orange)
LED2
(green)
LED3
(green)
●
(4)
●
(4)
44
Human sensor error
●
(5)
●
(4)
45
Refrigerant leakage sensor error
Sensor error, and harness
disconnection/connection failure
may have occurred.
●
(1)
●
(5)
51
Indoor unit fan motor error
●
(3)
●
(5)
53
Drain pump error
●
(4)
●
(5)
54
Electric air cleaner reverse VDD
error
●
(5)
●
(5)
55
Filter set error
●
(7)
●
(5)
57
Damper error
●
(8)
●
(5)
58
Intake grille error
●
(9)
●
(5)
59
Indoor unit fan motor 2 error
(Left side fan)
●
(10)
●
(5)
5A
Indoor unit fan motor 3 error
(Right side fan)
●
(15)
●
(5)
5U
Indoor unit error
●
(1)
●
(6)
61
Outdoor unit reverse/missing
phase and wiring error
●
(2)
●
(6)
62
Outdoor unit main PCB
model information error or
communication error
●
(3)
●
(6)
63
Inverter error
●
(4)
●
(6)
64
Active filter error, PFC circuit error
●
(5)
●
(6)
65
• Trip terminal L error
• IPM temp error
●
(8)
●
(6)
68
Outdoor unit rush current limiting
resister temp. rise error
●
(10)
●
(6)
6A
Display PCB microcomputers
communication error
●
(1)
●
(7)
71
Discharge temp. sensor error
●
(2)
●
(7)
72
Compressor temp. sensor error
●
(3)
●
(7)
73
Outdoor unit Heat Ex. liquid temp.
sensor error
●
(4)
●
(7)
74
Outdoor temp. sensor error
●
(5)
●
(7)
75
Suction Gas temp. sensor error
●
(6)
●
(7)
76
• 2-way valve temp. sensor error
• 3-way valve temp. sensor error
●
(7)
●
(7)
77
Heat sink temp. sensor error
●
(2)
●
(8)
82
• Sub-cool Heat Ex. gas inlet
temp. sensor error
• Sub-cool Heat Ex. gas outlet
temp. sensor error
●
(3)
●
(8)
83
Liquid pipe temp. sensor error
●
(4)
●
(8)
84
Current sensor error
●
(6)
●
(8)
86
• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error
●
(4)
●
(9)
94
Trip detection
●
(5)
●
(9)
95
Compressor rotor position
detection error (permanent stop)
●
(7)
●
(9)
97
Outdoor unit fan motor 1 error
Error display
Error code*
Description
LED1
(orange)
LED2
(green)
LED3
(green)
●
(8)
●
(9)
98
Outdoor unit fan motor 2 error
●
(9)
●
(9)
99
4-way valve error
●
(10)
●
(9)
9A
Coil (expansion valve) error
●
(1)
●
(10)
A1
Discharge temp. error
●
(3)
●
(10)
A3
Compressor temp. error
●
(4)
●
(10)
A4
High pressure error
●
(5)
●
(10)
A5
Low pressure error
●
(8)
●
(10)
A8
Refrigerant leakage suspicion
●
(11)
●
(10)
AC
Heat sink temp error
●
(2)
●
(13)
J2
Branch boxes error
[Multi-split type]
Display mode : 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
■
Error code on the wired remote controller (option)
Check the error
1.
If an error occurs, an error icon appears on the “Monitor mode screen”.
Touch the [Status] on the “Monitor mode screen”. The “Status” screen is dis-
played.
2.
Touch the [Error Information] on the “Status” screen. The “Error Information”
screen is displayed. (If there are no errors, the [Error Information] will not be
displayed.)
3.
2-digit numbers correspond to the error code in the table.
Touch the [Next page] (or [Previous page]) to switch to other connected indoor
units.
1.
2.
3.
Set Temp.
Mode
Menu
Status
Fan
Fri 10:00AM
Unoccupied
Status
Air Flow Direction
VT
Off
1
3
Off
HZ
Economy
Individual
Anti Freeze
Page 1/ 4
Monitor
Next
Page
Error
Information
02-01
14,15, 41, 44
Error Information
Page 1/ 5
Address
Error Code
Back
Next
Page
]1]1
10. REFRIGERANT LEAK DETECTION FUNCTION
■
System operation after refrigerant leak detection:
• Indoor unit starts diffusion operation by high fan speed.
• Due to safety reasons, a remote controller cannot stop this operation.
•
Indoor unit indicates Error code A8 (TIMER lamp [8], OPERATION lamp [10]).
[ ]: Number of flashing
• Indoor unit makes a warning beep.
(The beep stops by pressing [START/STOP] of the remote controller or [MANUAL
AUTO] on the indoor unit.)
• System stops the cooling/heating operation. Forced cooling operation is not available.