![Fujitsu AG * V12LAC Series Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/fujitsu/ag-v12lac-series/ag-v12lac-series_service-instruction_118098060.webp)
Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AG*V14LAC
[Condition]
Ambient temperature : Indoor 15 - 23degC, Outdoor 2 - 12degC
Amount of refrigerant : Regulation amount
Piping length : 5m (Difference of elevation 1m)
Power voltage : 50Hz - 230V
Operating condition : TEST mode (Heating), Hi-speed Fan, Upward blowoff position, Front blowoff,
1 fan operating, With deodorizing filter
Measurement method : High side pressure shall be measured with a pressure gauge from service valve.
Total outdoor electric current shall be measured with a clamp meter from connection cord.
Caution : Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AG*V14LAC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
08-05
3.00
3.10
3.20
3.30
3.40
3.50
3.60
0
2
4
6
8
10
12
14
Outdoor ambient temperature (°C)
H
ig
h-
pr
es
su
re
o
f o
ut
do
or
u
ni
t (
M
P
a)
AG*V14LAC
Outdoor ambient temperature (°C)
O
ut
do
or
to
ta
l e
le
ct
ric
c
ur
re
nt
(A
)
4.50
5.00
5.50
6.00
6.50
7.00
7.50
0
2
4
6
8
10
12
14
15°C
20°C
23°C
(Indoor ambient temp.)
15°C
20°C
23°C
(Indoor ambient temp.)
Содержание AG * V12LAC Series
Страница 4: ...1 SPECIFICATIONS R410A FLOOR type INVERTER ...
Страница 6: ...2 DIMENSIONS R410A FLOOR type INVERTER ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A FLOOR type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A FLOOR type INVERTER ...
Страница 12: ...CIRCUIT DIAGRAM Models AG V09LAC AO V09LAC AG V12LAC AO V12LAC 04 01 INDOOR UNIT OUTDOOR UNIT ...
Страница 13: ...CIRCUIT DIAGRAM Models AG V14LAC AO V14LAC 04 02 INDOOR UNIT OUTDOOR UNIT ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A FLOOR type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A FLOOR type INVERTER ...
Страница 62: ...9 REPLACEMENT PARTS R410A FLOOR type INVERTER ...
Страница 80: ...10 INSTALLATION MANUAL R410A FLOOR type INVERTER ...
Страница 89: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2007 Printed in Japan ...