(3).COOLING OPERATION
Switch the airflow [AUTO], and the
(Fig.6)
indoor fan motor will run according
airflow change - over ( Cooling:AUTO )
to a room temperature, as shown in
When the room
Figure 6.
temperature rises
On the other hand, if switched in
[HIGH]
[QUIET], the indoor motor
+2.5°C
will run at a constant airflow of [COOL]
operation modes QUIET, LOW, MED,
HIGH, as shown in Table 5.
+1.5°C
+1°C
LOW mode
When the room
temperature lowers
(Room temperature) D (Setting temperature)
(4).DRY OPERATION
(5).HEATING OPERATION
Switch the airflow [AUTO], and the
(Fig.7)
indoor fan motor will run according
airflow change - over ( Heating:AUTO)
to a room temperature, as shown in
When the room
Figure 7.
temperature rises
On the other hand, if switched
LOW mode
[HIGH]
[QUIET], the indoor motor
-1°C
will run at a constant airflow of [HEAT]
-1.5°C
operation modes QUIET, LOW, MED,
HIGH, as shown in Table 5.
-2°C
-2.5°C
HIGH mode
When the room
temperature lowers
(Room temperature) D (Setting temperature)
(6).COOL AIR PREVENTION CONTROL (Heating mode)
Indoor heat exchanger Indoor heat exchanger
temperature temperature
42°C
Hi
39°C
Me
37°C
Lo
Cool air prevention
30°C
S-Lo
Refer to the table 4.
Durring the dry mode operation, the fan speed
setting can not be changed.
The maximum value of the indoor fan speed is set as shown in Figure 8, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
(Fig.8 : Cool Air Prevention Control)
05-06
34°C
24°C
29°C
31°C
HIGH mode
MED mode
+2°C
MED mode
Содержание AG * V12LAC Series
Страница 4: ...1 SPECIFICATIONS R410A FLOOR type INVERTER ...
Страница 6: ...2 DIMENSIONS R410A FLOOR type INVERTER ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A FLOOR type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A FLOOR type INVERTER ...
Страница 12: ...CIRCUIT DIAGRAM Models AG V09LAC AO V09LAC AG V12LAC AO V12LAC 04 01 INDOOR UNIT OUTDOOR UNIT ...
Страница 13: ...CIRCUIT DIAGRAM Models AG V14LAC AO V14LAC 04 02 INDOOR UNIT OUTDOOR UNIT ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A FLOOR type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A FLOOR type INVERTER ...
Страница 62: ...9 REPLACEMENT PARTS R410A FLOOR type INVERTER ...
Страница 80: ...10 INSTALLATION MANUAL R410A FLOOR type INVERTER ...
Страница 89: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2007 Printed in Japan ...