Outdoor Unit Low Pressure Value and Outdoor Total Electric Current Curve (Cooling)
Model Name : AG*V09/ 12LAC
[Condition]
Ambient temperature : Indoor / Outdoor - Same temperature
Amount of refrigerant : Regulation amount
Piping length : 5m (Difference of elevation 1m)
Power voltage : 50Hz - 230V
Operating condition : TEST mode (Cooling), Hi-speed Fan, Upward blowoff position, Front blowoff,
1 fan operating, With deodorizing filter
Measurement method : Low side pressure shall be measured with a pressure gauge from service valve.
Total outdoor electric current shall be measured with a clamp meter from connection cord.
Caution : Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Colling mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor Low Pressure Curve
AG*V09LAC
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
08-02
0.70
0.80
0.90
1.00
1.10
1.20
1.30
17.5
20
22.5
25
27.5
30
32.5
In/outdoor ambient temperature (°C)
Lo
w
-p
re
ss
ur
e
of
o
ut
do
or
u
ni
t (
M
P
a)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
0.70
0.80
0.90
1.00
1.10
1.20
1.30
17.5
20
22.5
25
27.5
30
32.5
In/outdoor ambient temperature (°C)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
AG*V12LAC
Lo
w
-p
re
ss
ur
e
of
o
ut
do
or
u
ni
t (
M
P
a)
AG*V09LAC
1.60
1.70
1.80
1.90
2.00
2.10
2.20
17.5
20
22.5
25
27.5
30
32.5
In/outdoor ambient temperature (°C)
O
ut
do
or
to
ta
l e
le
ct
ric
c
ur
re
nt
(A
)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
2.60
2.80
3.00
3.20
3.40
3.60
3.80
17.5
20
22.5
25
27.5
30
32.5
In/outdoor ambient temperature (°C)
O
ut
do
or
to
ta
l e
le
ct
ric
c
ur
re
nt
(A
)
Relative Humidity 50%
Relative Humidity 60%
Relative Humidity 70%
AG*V12LAC
Содержание AG * V12LAC Series
Страница 4: ...1 SPECIFICATIONS R410A FLOOR type INVERTER ...
Страница 6: ...2 DIMENSIONS R410A FLOOR type INVERTER ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A FLOOR type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A FLOOR type INVERTER ...
Страница 12: ...CIRCUIT DIAGRAM Models AG V09LAC AO V09LAC AG V12LAC AO V12LAC 04 01 INDOOR UNIT OUTDOOR UNIT ...
Страница 13: ...CIRCUIT DIAGRAM Models AG V14LAC AO V14LAC 04 02 INDOOR UNIT OUTDOOR UNIT ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A FLOOR type INVERTER ...
Страница 35: ...6 REFRIGERANT CAUTION R410A R410A FLOOR type INVERTER ...
Страница 62: ...9 REPLACEMENT PARTS R410A FLOOR type INVERTER ...
Страница 80: ...10 INSTALLATION MANUAL R410A FLOOR type INVERTER ...
Страница 89: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2007 Printed in Japan ...