Model: AOYG45KRTA
Fan speed is defined by outdoor temperature and compressor frequency.
Unit: rpm
Fan step
Cooling or dry
Heating
13
990
—
12
920
—
11
860
—
10
800
990
9
740
900
8
650
820
7
600
740
6
530
650
5
490
540
4
400
460
3
330
380
2
270
290
1
200
200
S-HIGH
—
990
• When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed.
• When the compressor frequency decreases, the outdoor fan speed also changes to the lower
speed.
NOTE:
After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 990 rpm
3-2. Outdoor fan control
- (04-13) -