1-4. Compressor frequency at normal start-up
¢
Model: AOYG36KRTA
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Frequency VI
Frequency VII
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Time 7
Frequency VIII
Time 8
• Normal operation
Frequency
(rps)
I
II
III
IV
V
VI
VII
VIII
25
42
53
61
65
75
85
92
Time (sec)
1
2
3
4
5
6
7
8
90
150
270
330
390
450
570
630
• Special operation
Frequency
(rps)
I
II
III
IV
V
VI
VII
VIII
25
42
53
61
65
75
85
92
Time (sec)
1
2
3
4
5
6
7
8
225
305
605
665
725
785
855
1,000
NOTES:
• Normal operation:
– Cooling and dry mode
• Below 3 hours from the compressor stop and the compressor thermistor ≥ 15 °C
• After defrost operation
– Other than when the compressor starts for the first time since the breaker turns on
• Special operation:
– Other than the normal operation condition
– When the compressor starts for the first time since the breaker turns on
1-4. Compressor frequency at normal start-up
- (04-3) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABYG36KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Страница 40: ......
Страница 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Страница 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Страница 106: ......
Страница 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...