7-10. Prevention to restart for 3 minutes (3 minutes st)
When the compressor fails to start for the number of times below, it does not enter operation status
for 3 minutes.
Retry number
30
Retry set number
3
When the compressor fails to start in the retry set number above, the compressor is stopped.
7-11. 4-way valve control
• If heating mode is selected at the compressor start, 4-way valve is energized for heating.
• When the air conditioner is switched between cooling and heating mode, compressor is stopped,
and the 4-way valve is switched when the 3 minutes passes and the compressor is started.
7-12. Human sensor for energy saving
If no one enters the room for the set time, the set temperature is automatically controlled. (When
someone comes back into the room, the human sensor detect this, and automatically revert to the
original settings.)
Operation mode
Operation details
(If there is no one in the room for a while)
Cooling/Dry
The setting temperature is increased by maximum 2°C.
(Maximum setting temperature: 30°C)
Heating
The setting temperature is decreased by maximum 2°C.
(Minimum setting temperature: 16°C)
Auto
Energy saving function is performed automatically for the selected mode
(cooling/heating/dry).
Details about detection with the human sensor:
The human sensor detects whether there are people in the room by looking for movement by people
in the room.
7-13. Peak cut operation
The current value is limited to reduce the power consumption by external input.
Peak cut level
Level 1
Level 2
Level 3
Level 4
Peak cut for rated capacity
Forced thermostat
off
50%
75%
100%
NOTES:
• During defrost operation, peak cut operation becomes invalid.
• Even during the peak cut operation, the operations of current overload, economy, and low noise
are effective and the outdoor unit operates by lowest current of them.
7-10. Prevention to restart for 3 minutes (3 minutes st)
- (04-27) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABYG36KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Страница 40: ......
Страница 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Страница 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Страница 106: ......
Страница 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...