1-2. Outdoor unit
Type
Inverter heat pump
Model name
AOYG36KRTA
AOYG45KRTA
Power supply
3N 400 V ~ 50 Hz
Power supply intake
Outdoor unit
Available voltage range
342—457 V
Starting current
A
5.7
7.7
Fan
Airflow rate
Cooling
m
3
/h
3,750
4,450
Heating
3,750
4,450
Type × Q'ty
Propeller × 1
Motor output
W
100
120
Sound pressure level *1
Cooling
dB (A)
55
57
Heating
55
57
Sound power level
Cooling
dB (A)
70
71
Heating
70
71
Heat exchanger type
Dimensions
(H × W × D)
mm
Main1: 756 × 905 × 18.20
Main2: 756 × 905 × 18.20
Main1: 966 × 905 × 18.19
Main2: 966 × 905 × 18.19
Sub: 966 × 543 × 18.19
Fin pitch
Main1: 1.45
Main2: 1.45
Main1: 1.45
Main2: 1.45
Sub: 1.45
Rows × Stages
Main1: 1 × 36
Main2: 1 × 36
Main1: 1 × 46
Main2: 1 × 46
Sub: 1 × 46
Pipe type
Copper
Fin
Type (Material)
Aluminum
Surface treatment
Blue fin
Compressor
Type
DC Twin rotary
Motor output
W
1,500
2,180
Refrigerant
Type (Global warming potential)
R32 (675)
Factory charge
g
1,900
2,700
Refrigerant oil
Type
FW68D
RmM68AF
Amount
cm
3
600
800
Enclosure
Material
Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
788 × 940 × 320
998 × 940 × 320
Gross
966 × 1,027 × 445
1,176 × 1,027 × 445
Weight
Net
kg
53
67
Gross
62
77
Connection pipe
Size
Liquid
mm (in)
Ø 9.52 (3/8)
Gas
Ø 15.88 (5/8)
Method
Flare
Pre-charge length
m
30
Max. length
50
Max. height difference
30
Operation range
Cooling
°C
-15 to 46
Heating
-15 to 24
Drain hose
Material
LDPE
Size
mm
Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5.0 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• This data is based on EN 14511 standard.
1-2. Outdoor unit
- (01-3) -
1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Содержание ABYG36KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Страница 40: ......
Страница 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Страница 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Страница 106: ......
Страница 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...