•
Heating mode
F zone
7°C
E zone
2°C
D zone
-7°C
C zone
B zone
A zone
-10°C
-15°C
G zone
12°C
H zone
16°C
I zone
20°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOYG36KRTA
A zone
58 rps
B zone
52 rps
C zone
43 rps
D zone
38 rps
E zone
28 rps
F zone
23 rps
G zone
20 rps
H zone
17 rps
I zone
17 rps
AOYG45KRTA
A zone
46 rps
B zone
42 rps
C zone
35 rps
D zone
32 rps
E zone
23 rps
F zone
20 rps
G zone
17 rps
H zone
13 rps
I zone
16 rps
1-5. Compressor frequency limitation by outdoor temperature
- (04-6) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABYG36KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Страница 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Страница 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Страница 40: ......
Страница 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Страница 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Страница 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Страница 106: ......
Страница 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...