9.  FRONT PANEL REMOVAL AND INSTALLATION

9.1. Intake grille removal

 (1)  Open the intake grille.
 (2)  While holding the intake grille, lift up the grille stay and secure the intake grille. 
 (3)  Remove the screws from the arm-cover on the top part of the front panel 

(in 2 places, one on the left and one on the right).

 (4)  Push down the arm-cover grips to release the lock.
 (5)  Open the intake grille until it is horizontal, and pull it towards you to remove it.

(1)

(2)

(3)

(4)

Intake grille

Arm-cover knob

Grille stay

Intake grille

Grille stay

9.2. Intake grille installation

 (1)  Make the intake grille horizontal and push the attachment shafts into the holes for 

them in the top of the front panel (in 2 places, one on the left and one on the right).

 (2)  While holding the intake grille, lift up the grille stay and secure the intake grille.  
 (3)  Push the arm-cover grips up, and lock the intake grille attachment shaft.
 (4)  Fix the arm-cover on the top part of the front panel using screws (in 2 places, one on 

the left and one on the right).

 (5)  Lift up the intake grille a little, and return the grille stay to its original position.
 (6)  Close the intake grille.

Attachment shaft

Hole

9.3. Front panel removal

 (1)  Remove intake grille. (Reference the intake grille removal.)
 (2)  Remove wire cover. (Remove the 1 screw.)
 (3)  Remove 4 screws.

Screws (4 position)

Wire cover Screw (Wire cover)

 (4)  The front panel is pulled to the front, raising the upper surface, and a front panel is 

removed.

Front panel

8. FINISHING 

 (1)  Insulate between pipes.

•  Insulate suction and discharge pipes separately.
•  For rear, right, and bottom piping, overlap the connection pipe heat insulation and 

indoor unit pipe heat insulation and bind them with vinyl tape so that there is no 
gap.

•  For left and left rear piping, butt the connection pipe heat insulation and indoor unit 

pipe heat insulation together and bind them with and vinyl tape so that there is no 
gap.

•  For left and left rear piping, wrap the area which accommodates the rear piping 

housing section with cloth tape.

•  For left and left rear piping, bind the connection cable to the top of the pipe with 

vinyl tape.

•  For left and left rear piping, bundle the piping and drain hose together by wrapping 

them with cloth tape over the range within which they 

fi

 t into the rear piping 

housing section.

 (2)  Temporarily fasten the connection cable along the connection pipe with vinyl tape. 

(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water 
does not enter.)

 (3)  Fasten the connection pipe to the outside wall with a saddle, etc.
 (4)  Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain 

water and wind cannot blow in.

 (5)  Fasten the drain hose to the outside wall, etc.

Pipe

Saddle*

Outside wall cap*

Sealer putty*

(Outdoors)

*Field supplied

Wall

Seal A is used when the diameter 

of gas pipe is Ø12.70 or more.

Butt connection pipe (heat 

insulation) against the indoor 

unit pipe (heat insulation) and 

wrap with seal A so that there 

is no gap.

Overlap the insulation

Vinyl tape

Wrap with cloth tape 

Cloth tape

Drain hose

Connection cable

Pipe

Drain hose

Check the following:

GOOD

Drain hose

Saddle

Lifted up

Wave

End in water

Drain hose

Connection pipe

Wall pipe

Connection cable

Left piping

For connection from the left rear

NO GOOD NO GOOD NO GOOD

Pipe

Connection pipe 
(heat insulation)

Bind the pipes together 
so that there is no gap.

Indoor unit pipe 
(heat insulation)

9319357003-02_IM_EN.indd   7

9319357003-02_IM_EN.indd   7

7/27/2011   3:42:29 PM

7/27/2011   3:42:29 PM

Содержание 9319357003-02

Страница 1: ...r autorisiertes Personal MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Wall Mounted Type PART NO 9319357003 02...

Страница 2: ... the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional ref...

Страница 3: ...utput port Communication kit UTY TWBXF For the installation of optional parts Optional communication kit is necessary for the installation 3 GENERAL SPECIFICATION This installation manual briefly outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system ...

Страница 4: ...ear a source of heat steam or flammable gas Install the unit where drainage does not cause any trouble Install the indoor unit outdoor unit branch box power supply cable transmission cable and remote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could...

Страница 5: ...serting be sure not to attach any material besides water If any other material is attached it will cause deterioration and water leakage After removing drain hose be sure not to forget mounting drain cap Be sure to fix the drain hose with tape to the bottom of piping Prevent drain water freezing under low temperature environment When installing indoor unit s drain hose outdoors necessary measure f...

Страница 6: ... table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 6 9 2 Bending pipes If pipes are shaped by hand be careful not to collapse them Do not bend the pipes in an angle more than 90 When...

Страница 7: ... when wiring cable When stripping off the insulation of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the insulation with a knife etc 1 Use crimp type terminals with insulating sleeves as shown in the figure below to con nect to the terminal block 2 Securely clamp the crimp type terminals to the wires using an appropriate tool s...

Страница 8: ...pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap For left and left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap For left and left rear piping wrap the area which accommodates the rear piping housing section with cloth tape Fo...

Страница 9: ...ditioner operation 2 Press the MODE button and the FAN button simultaneously for 2 seconds or more to start the test run Test run display 3 Press the start stop button to stop the test run 11 REMOTE CONTROLLER INSTALLATION CAUTION Check that the indoor unit correctly receives the signal from the remote controller then install the remote controller holder Select the remote controller holder selecti...

Страница 10: ...hite Black Black Insulated connection Connector 3 0 m m 3 5 4 5 m m 7 0 8 0 m m Installing the wired remote controller terminal sold separately Connect the wired remote controller terminal to the connector CNC01 on the relay control board Relay wire Connector CNC01 Wired remote controller cord Rib 12 1 Accessories Communication kit The following installation accessories are supplied Use them as re...

Страница 11: ...epending on the installed environment the room temperature sensor may require a cor rection The settings may be selected as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 30 00 Slightly lower control 01 Lower control 02 Warmer control 03 Function number Setting value Installing the external connect kit terminal sold separately Connect the wire o...

Страница 12: ...ensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error Heating Room Temperature Correction Depending on the installed environment the room temperature sensor may require a cor rection The settings may be changed as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 31 00 Lower control 01 Slightly warmer control 02 Warmer control...

Страница 13: ...ion detection error 9 7 Outdoor unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indica...

Отзывы: