1. SAFETY PRECAUTIONS

Be sure to read this manual thoroughly before installation.

• 

The warnings and precautions indicated in this manual contain important information 

• 

pertaining to your safety. Be sure to observe them.
Hand this manual, together with the operating manual, to the customer. Request the 

• 

customer to keep them on hand for future use, such as for relocating or repairing the 
unit.

 WARNING

This mark indicates procedures which, if improperly per-
formed, might lead to the death or serious injury of the user.

Request your dealer or a professional installer to install the indoor unit in accordance 
with this installation manual. An improperly installed unit can cause serious accidents 
such as water leakage, electric shock, or 

fi

 re. If the indoor unit is installed in disregard 

of the instructions in the installation manual, it will void the manufacturer’s warranty.

Do not turn ON the power until all work has been completed. Turning ON the power be-
fore the work is completed can cause serious accidents such as electric shock or 

fi

 re.

If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant 
comes in contact with a 

fl

 ame, it produces a toxic gas.

Installation work must be performed in accordance with national wiring standards by 
authorized personnel only.

 CAUTION

This mark indicates procedures which, if improperly 
performed, might possibly result in personal harm to the user, 
or damage to property.

Read carefully all security information before use or install the air conditioner.

Do not attempt to install the air conditioner or a part of the air conditioner by yourself.

This unit must be installed by quali

fi

 ed personnel with a capacity certi

fi

 cate for handling 

refrigerant 

fl

 uids. Refer to regulation and laws in use on installation place.

The installation must be carried out in compliance with regulations in force in the place 
of installation and the installation instructions of the manufacturer.

This unit is part of a set constituting an air conditioner. It must not be installed alone or 
with non-authorized by the manufacturer.

Always use a separate power supply line protected by a circuit breaker operating on all 
wires with a distance between contact of 3 mm for this unit.

Contents

1. SAFETY 

PRECAUTIONS 

............................................................................................1

2. ABOUT 

THE 

UNIT 

.......................................................................................................1

3. GENERAL 

SPECIFICATION 

.......................................................................................2

4. ELECTRICAL 

REQUIREMENT 

...................................................................................2

5.  SELECTING THE MOUNTING POSITION .................................................................3

6. INSTALLATION 

WORK 

...............................................................................................3

7. ELECTRICAL 

WIRING 

 

...............................................................................................6

8. FINISHING 

..................................................................................................................7

9.  FRONT PANEL REMOVAL AND INSTALLATION .......................................................7

10. TEST RUN 

...................................................................................................................8

11.  

REMOTE CONTROLLER INSTALLATION ..................................................................8

12.  OPTIONAL KIT INSTALLATION (UTY-TWBXF) ..........................................................8

13.  SELECTING THE REMOTE CONTROLLER SIGNAL CODE ................................... 10

14. FUNCTION SETTING................................................................................................ 10

15. CUSTOMER GUIDANCE 

.......................................................................................... 11

16. ERROR CODES 

........................................................................................................ 11

The unit must be correctly grounded and the supply line must be equipped with a dif-
ferential breaker in order to protect the persons.

The units are not explosion proof and therefore should not be installed in explosive 
atmosphere.

Never touch electrical components immediately after the power supply has been 
turned off. Electric shock may occur. After turning off the power, always wait 5 minutes 
before touching electrical components.

This unit contains no user-serviceable parts. Always consult authorized service person-
nel to repairs.

When moving, consult authorized service personnel for disconnection and installation 
of the unit.

2.  ABOUT THE UNIT

2.1. Precautions for using R410A refrigerant

The basic installation work procedures are the same as conventional refrigerant (R22) 
models.
However, pay careful attention to the following points:

Since the working pressure is 1.6 times higher than that of conventional refrigerant 
(R22) models, some of the piping and installation and service tools are special. (See 
the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant 
R410A model, always replace the conventional piping and 

fl

 are nuts with the R410A piping 

and 

fl

 are nuts.

Models that use refrigerant R410A have a different charging port thread diameter to pre-
vent erroneous charging with conventional refrigerant (R22) and for safety. Therefore, 
check beforehand. [The charging port thread diameter for R410A is 1/2 inch.]

Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with 
refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by 
pinching, taping, etc.

When charging the refrigerant, take into account the slight change in the composition of 
the gas and liquid phases. And always charge from the liquid phase where refrigerant 
composition is stable.

2.2. Special tools for R410A

Tool name

Contents of change

Gauge manifold

Pressure is high and cannot be measured with a conven-
tional (R22) gauge. To prevent erroneous mixing of other 
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals -0.1 to 5.3 MPa 
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

Charge hose

To increase pressure resistance, the hose material and base 
size were changed.

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter.

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 
discolored portion (especially on the interior surface). Otherwise, the expansion value or 
capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is neces-
sary to choose adequate materials. 

 WARNING

Do not use the existing (for R22) piping and 

fl

 are nuts.

If the existing materials are used, the pressure inside the refrigerant cycle will rise and 
cause failure, injury, etc. (Use the special R410A materials.)

When installing and relocating the air conditioner, do not mix gases other than the 
speci

fi

 ed refrigerant (R410A) to enter the refrigerant cycle.

If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to 
an abnormally high value and cause failure, injury, etc.

AIR CONDITIONER 

INSTALLATION MANUAL

Compact Wall Mounted Type

PART NO. 9319357003-02

Branch box which is speci

fi

 ed in this manual is the equipment to support the indoor unit 

• 

of multi-connection type.

9319357003-02_IM_EN.indd   1

9319357003-02_IM_EN.indd   1

7/27/2011   3:40:46 PM

7/27/2011   3:40:46 PM

Содержание 9319357003-02

Страница 1: ...r autorisiertes Personal MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Wall Mounted Type PART NO 9319357003 02...

Страница 2: ... the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional ref...

Страница 3: ...utput port Communication kit UTY TWBXF For the installation of optional parts Optional communication kit is necessary for the installation 3 GENERAL SPECIFICATION This installation manual briefly outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system ...

Страница 4: ...ear a source of heat steam or flammable gas Install the unit where drainage does not cause any trouble Install the indoor unit outdoor unit branch box power supply cable transmission cable and remote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could...

Страница 5: ...serting be sure not to attach any material besides water If any other material is attached it will cause deterioration and water leakage After removing drain hose be sure not to forget mounting drain cap Be sure to fix the drain hose with tape to the bottom of piping Prevent drain water freezing under low temperature environment When installing indoor unit s drain hose outdoors necessary measure f...

Страница 6: ... table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 6 9 2 Bending pipes If pipes are shaped by hand be careful not to collapse them Do not bend the pipes in an angle more than 90 When...

Страница 7: ... when wiring cable When stripping off the insulation of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the insulation with a knife etc 1 Use crimp type terminals with insulating sleeves as shown in the figure below to con nect to the terminal block 2 Securely clamp the crimp type terminals to the wires using an appropriate tool s...

Страница 8: ...pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap For left and left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap For left and left rear piping wrap the area which accommodates the rear piping housing section with cloth tape Fo...

Страница 9: ...ditioner operation 2 Press the MODE button and the FAN button simultaneously for 2 seconds or more to start the test run Test run display 3 Press the start stop button to stop the test run 11 REMOTE CONTROLLER INSTALLATION CAUTION Check that the indoor unit correctly receives the signal from the remote controller then install the remote controller holder Select the remote controller holder selecti...

Страница 10: ...hite Black Black Insulated connection Connector 3 0 m m 3 5 4 5 m m 7 0 8 0 m m Installing the wired remote controller terminal sold separately Connect the wired remote controller terminal to the connector CNC01 on the relay control board Relay wire Connector CNC01 Wired remote controller cord Rib 12 1 Accessories Communication kit The following installation accessories are supplied Use them as re...

Страница 11: ...epending on the installed environment the room temperature sensor may require a cor rection The settings may be selected as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 30 00 Slightly lower control 01 Lower control 02 Warmer control 03 Function number Setting value Installing the external connect kit terminal sold separately Connect the wire o...

Страница 12: ...ensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error Heating Room Temperature Correction Depending on the installed environment the room temperature sensor may require a cor rection The settings may be changed as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 31 00 Lower control 01 Slightly warmer control 02 Warmer control...

Страница 13: ...ion detection error 9 7 Outdoor unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indica...

Отзывы: