7. ELECTRICAL WIRING 

Cable

Cable size (mm

2

)

Type

Remarks

Connection cable

1.5

Type 60245 IEC57

Ground, 1

φ

230V

Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is 
2% or more.

7.1. Wiring system diagram

 WARNING

Before connecting the wires, make sure the power supply is OFF.

Every wire must be connected 

fi

 rmly.

 No wire should be allowed to touch refrigerant tubing, the compressor or any moving 
part.
 Loose wiring may cause the terminal to overheat or result in unit malfunction. A 

fi

 re 

hazard may also exist. Therefore, be sure all wiring is tightly connected.
Connect wires to the matching numbers of terminals.

Grounding line

Type 60245 IEC57 
Cable size 1.5mm

2

(Inter-unit)

OUTDOOR UNIT 
or BRANCH BOX

Please connect it to  
the speci

fi

 ed terminal.

INDOOR UNIT

TERMINAL

Power line

Control line

7.2.  Indoor unit wiring

(1) Remove the wire cover. (Remove the 1 screw.)
(2) Remove the cable clamp. (Remove the 1 screw.)
(3) Bend the end of the connection cable as shown in the 

fi

 gure.

(4) Connect the end of the connection cable fully inserting into the terminal block.
(5) Fasten the connection cable with a cable clamp. (Attach the 1 screw.)

Insert the wire cover tab into the square hole 
of the indoor unit and fasten with a screw.

End of connection cable

30 mm

Cable clamp

Connection 
cable

Screw

Screw

Wire cover

Connection cable

Terminal block

Cable clamp

Connection 
cable

Screw

Screw

Wire cover

50 mm

7.3.  How to connect wiring to the terminals

Caution when wiring cable

When stripping off the insulation of a lead wire, always use a special tool such as a wire 
stripper. If there is no special tool available, carefully strip the insulation with a knife etc.
(1)  Use crimp-type terminals with insulating sleeves as shown in the 

fi

 gure below to con-

nect to the terminal block.

(2)  Securely clamp the crimp-type terminals to the wires using an appropriate tool so that 

the wires do not come loose.

Strip : 10 mm 

Crimp-type 
terminal

Sleeve

(3)  Use the speci

fi

 ed wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-

driver that is too small, otherwise, the screw heads may be damaged and prevent the 
screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

Screw with special washer

Wire

Crimp-type terminal

Terminal blocks

Wire

Screw with special washer

Crimp-type 

terminal

(6)  See the table below for the terminal screw tightening torques.

Tightening torque [N·m (kgf·cm)]

M4 screw

1.2 to 1.8 (12 to 18)

 CAUTION

  Match the terminal block numbers and connection cable colors with those of the 

outdoor unit or branch box.

  Erroneous wiring may cause burning of the electric parts.

  Connect the connection cables 

fi

 rmly to the terminal block. Imperfect installation may 

cause a 

fi

 re.

  Always fasten the outside covering of the connection cable with the cable clamp. (If 

the insulator is chafed, electric discharge may occur.)

Always connect the ground wire.

Do not use the earth screw of the indoor unit for the connection other than a speci

fi

 ed 

outdoor unit or branch box.

9319357003-02_IM_EN.indd   6

9319357003-02_IM_EN.indd   6

7/27/2011   3:42:28 PM

7/27/2011   3:42:28 PM

Содержание 9319357003-02

Страница 1: ...r autorisiertes Personal MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Wall Mounted Type PART NO 9319357003 02...

Страница 2: ... the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional ref...

Страница 3: ...utput port Communication kit UTY TWBXF For the installation of optional parts Optional communication kit is necessary for the installation 3 GENERAL SPECIFICATION This installation manual briefly outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system ...

Страница 4: ...ear a source of heat steam or flammable gas Install the unit where drainage does not cause any trouble Install the indoor unit outdoor unit branch box power supply cable transmission cable and remote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could...

Страница 5: ...serting be sure not to attach any material besides water If any other material is attached it will cause deterioration and water leakage After removing drain hose be sure not to forget mounting drain cap Be sure to fix the drain hose with tape to the bottom of piping Prevent drain water freezing under low temperature environment When installing indoor unit s drain hose outdoors necessary measure f...

Страница 6: ... table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 6 9 2 Bending pipes If pipes are shaped by hand be careful not to collapse them Do not bend the pipes in an angle more than 90 When...

Страница 7: ... when wiring cable When stripping off the insulation of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the insulation with a knife etc 1 Use crimp type terminals with insulating sleeves as shown in the figure below to con nect to the terminal block 2 Securely clamp the crimp type terminals to the wires using an appropriate tool s...

Страница 8: ...pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap For left and left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap For left and left rear piping wrap the area which accommodates the rear piping housing section with cloth tape Fo...

Страница 9: ...ditioner operation 2 Press the MODE button and the FAN button simultaneously for 2 seconds or more to start the test run Test run display 3 Press the start stop button to stop the test run 11 REMOTE CONTROLLER INSTALLATION CAUTION Check that the indoor unit correctly receives the signal from the remote controller then install the remote controller holder Select the remote controller holder selecti...

Страница 10: ...hite Black Black Insulated connection Connector 3 0 m m 3 5 4 5 m m 7 0 8 0 m m Installing the wired remote controller terminal sold separately Connect the wired remote controller terminal to the connector CNC01 on the relay control board Relay wire Connector CNC01 Wired remote controller cord Rib 12 1 Accessories Communication kit The following installation accessories are supplied Use them as re...

Страница 11: ...epending on the installed environment the room temperature sensor may require a cor rection The settings may be selected as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 30 00 Slightly lower control 01 Lower control 02 Warmer control 03 Function number Setting value Installing the external connect kit terminal sold separately Connect the wire o...

Страница 12: ...ensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error Heating Room Temperature Correction Depending on the installed environment the room temperature sensor may require a cor rection The settings may be changed as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 31 00 Lower control 01 Slightly warmer control 02 Warmer control...

Страница 13: ...ion detection error 9 7 Outdoor unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indica...

Отзывы: