background image

En-11

15. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1)  Starting and stopping method, operation switching, temperature adjustment, timer, air 

fl

 ow switching, and other remote control unit operations.

(2)  Air 

fi

 lter removal and cleaning, and how to use the air louvers.

(3) Give the operating manual to the customer.

16. ERROR CODES

If you use a wireless remote controller, the lamp on the photo detector unit will output er-
ror codes by way of blinking patterns. If you use a wired remote controller, error codes will 
appear on the remote controller display. See the lamp blinking patterns and error codes in 
the table. An error display is displayed only during operation.

Error display

Wired

remote

controller

Error code

Description

OPERATION

lamp

(green)

TIMER

lamp

(orange)

ECONOMY

lamp

(green)

(1)

(1)

Serial communication error

(1)

(2)

Wired remote controller 
communication  error

(1)

(5)

Check run unfinished

(2)

(1)

Unit number or Refrigerant 
circuit address setting error 
[Simultaneous Multi]

(2)

(2)

Indoor unit capacity error

(2)

(3)

Combination error

(2)

(4)

•  Connection unit number 

error (indoor slave unit) 
[Simultaneous Multi]

•  Connection unit number error 

(indoor unit or branch unit) 
[Flexible Multi]

(2)

(7)

Master unit, slave unit set-up 
error [Simultaneous Multi]

(3)

(2)

Indoor unit PCB model 
information error

(3)

(5)

Manual auto switch error

(4)

(1)

Room temp. sensor error 

(4)

(2)

Indoor unit Heat Ex. Middle temp. 
sensor error

(5)

(1)

Indoor unit fan motor error

(5)

(3)

Drain pump error

(5)

(7)

Damper error

(5)

(8)

Intake grille error

(5)

(15)

Indoor unit error

(6)

(2)

Outdoor unit main PCB model 
information error or 
communication error

(6)

(3)

Inverter  error 

(6)

(4)

Active filter error, PFC circuit 
error 

(6)

(5)

Trip terminal L error

(6)

(10)

Display PCB microcomputers 
communication error  

(7)

(1)

Discharge temp. sensor error

(7)

(2)

Compressor temp. sensor error

(7)

(3)

Outdoor unit Heat Ex. liquid 
temp. sensor error

(7)

(4)

Outdoor temp. sensor error

(7)

(5)

Suction Gas temp. sensor error

Heating Room Temperature Correction

 Depending on the installed environment, the room temperature sensor may require a cor-
rection. 
  The settings may be changed as shown in the table below.

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

Standard

31

00

Lower control

01

Slightly warmer control

02

Warmer control

03

Auto Restart

 Enable or disable automatic system restart after a power outage. 

(

...  Factory setting)

Setting Description

Function 

Number

Setting Value

   Yes

40

00

No

01

*  Auto restart is an emergency function such as for power failure etc. Do not start and stop 

the indoor unit by this function in normal operation. Be sure to operate by the control unit, 
or external input device.

Indoor room temperature sensor switching function

(Only for wired remote controller)
The following settings are needed when using the wired remote controller temperature 
sensor.

(

...  Factory setting)

Setting Description

Function 

Number

Setting Value

   No

42

00

Yes

01

* If setting value is “00” : 

 Room temperature is controlled by the indoor unit temperature sensor.

* If setting value is “01” : 

 Room temperature is controlled by either indoor unit temperature sensor or remote con-
troller unit sensor.

Remote controller signal code

 Change the indoor unit Signal Code, depending on the remote controllers.

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

   A

44

00

B

01

C

02

D

03

External input control

 “Operation/Stop” mode or “Forced stop” mode can be elected.

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

Operation/Stop mode

46

00

(Setting forbidden)

01

Forced stop mode

02

Setting record

Record any changes to the settings in the following table.

Setting Description

Setting Value

Filter sign

Cooler room temperature correction

Heater room temperature correction

Auto restart

Indoor room temperature sensor switching function 

Remote controller signal code

External input control

After completing the FUNCTION SETTING, be sure to turn off the power and turn it on 
again.

9319357003-02_IM_EN.indd   11

9319357003-02_IM_EN.indd   11

7/27/2011   3:43:40 PM

7/27/2011   3:43:40 PM

Содержание 9319357003-02

Страница 1: ...r autorisiertes Personal MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Compact Wall Mounted Type PART NO 9319357003 02...

Страница 2: ... the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional ref...

Страница 3: ...utput port Communication kit UTY TWBXF For the installation of optional parts Optional communication kit is necessary for the installation 3 GENERAL SPECIFICATION This installation manual briefly outlines where and how to install the air conditioning system Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system ...

Страница 4: ...ear a source of heat steam or flammable gas Install the unit where drainage does not cause any trouble Install the indoor unit outdoor unit branch box power supply cable transmission cable and remote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could...

Страница 5: ...serting be sure not to attach any material besides water If any other material is attached it will cause deterioration and water leakage After removing drain hose be sure not to forget mounting drain cap Be sure to fix the drain hose with tape to the bottom of piping Prevent drain water freezing under low temperature environment When installing indoor unit s drain hose outdoors necessary measure f...

Страница 6: ... table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure the dimension A Width across flats Pipe outside diameter mm in Width across flats of Flare nut mm 6 35 1 4 17 9 52 3 8 22 12 70 1 2 26 15 88 5 8 29 19 05 3 4 36 6 9 2 Bending pipes If pipes are shaped by hand be careful not to collapse them Do not bend the pipes in an angle more than 90 When...

Страница 7: ... when wiring cable When stripping off the insulation of a lead wire always use a special tool such as a wire stripper If there is no special tool available carefully strip the insulation with a knife etc 1 Use crimp type terminals with insulating sleeves as shown in the figure below to con nect to the terminal block 2 Securely clamp the crimp type terminals to the wires using an appropriate tool s...

Страница 8: ...pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap For left and left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap For left and left rear piping wrap the area which accommodates the rear piping housing section with cloth tape Fo...

Страница 9: ...ditioner operation 2 Press the MODE button and the FAN button simultaneously for 2 seconds or more to start the test run Test run display 3 Press the start stop button to stop the test run 11 REMOTE CONTROLLER INSTALLATION CAUTION Check that the indoor unit correctly receives the signal from the remote controller then install the remote controller holder Select the remote controller holder selecti...

Страница 10: ...hite Black Black Insulated connection Connector 3 0 m m 3 5 4 5 m m 7 0 8 0 m m Installing the wired remote controller terminal sold separately Connect the wired remote controller terminal to the connector CNC01 on the relay control board Relay wire Connector CNC01 Wired remote controller cord Rib 12 1 Accessories Communication kit The following installation accessories are supplied Use them as re...

Страница 11: ...epending on the installed environment the room temperature sensor may require a cor rection The settings may be selected as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 30 00 Slightly lower control 01 Lower control 02 Warmer control 03 Function number Setting value Installing the external connect kit terminal sold separately Connect the wire o...

Страница 12: ...ensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error Heating Room Temperature Correction Depending on the installed environment the room temperature sensor may require a cor rection The settings may be changed as shown in the table below Factory setting Setting Description Function Number Setting Value Standard 31 00 Lower control 01 Slightly warmer control 02 Warmer control...

Страница 13: ...ion detection error 9 7 Outdoor unit fan motor error 9 9 4 way valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator lamp green TIMER indicator lamp orange ECONOMY indica...

Отзывы: