10.5.21 Fuel coefficient setting (option)
Description
You can set the fuel coefficient [k], which is for calculation of combustion efficiency, using this func-
tion.
Settable range
:
0.00 to 1.99
Procedu
re
Operation
(example)
Setting the fuel coefficient [k] to 0.73.
Key operation
Description
Displayed message
(LCD)
(1)
Display the screen on the right in accordance with the key op-
eration summary and press the
key.
PARAMETER MENU
FUEL COEFF.
(2)
Use the
key and the
key to input the fuel coefficient.
FUEL COEFF.
0
.73
(3)
Press
the
key
to fix.
FUEL COEFF.
0.73
(4)
Press
the
key to return to the screen on the right.
PARAMETER MENU
FUEL COEFF.
Calculation and display of combustion efficiency
Using the following formula, calculate the combustion efficiency E.
Combustion efficiency E [
%
] =100
– Fuel coefficient [k]
•
Temperature of flue gases [K]
Standard oxygen concentration value [vol%]
-
Measured oxygen concentration value [vol%]
Note 1: Fuel coefficient [k] is according to the fuel used.
Refer to the table below.
Note 2: Temperature of flue gases should be measured separately.
Connect the electromotive force signal of the thermocouple type temperature detector (R-
type) to this unit.
*Type R or type K, depending on the model.
Note 3: The standard oxygen concentration value is to be 20.8 [vol
%
].
Note 4: When the internal calculation result of the combustion efficiency [E]
exceeds 0 [%]
≤
E
≤
100 [%],
% is displayed.
Natural gas
k = 0.66
Oil
k = 0.7
Bituminous coal
k = 0.73
Note 5: Measurement range is between 0°C to 1000°C.
If the temperature exceeds the above range, “
°C” is displayed.
Содержание ZKMA
Страница 1: ......
Страница 13: ...2 INZ TN2ZKMA E 2 OPERATING PARTS AND THEIR FUNCTIONS 2 1 Outline Drawing 1 ZKMA 2 ZKMB...
Страница 22: ...11 INZ TN2ZKMA E 4 2 2 Cable gland and input and output lines 1 ZKMA 2 ZKMB...
Страница 23: ...12 INZ TN2ZKMA E 4 2 3 Allocation of the terminal block...
Страница 24: ...13 INZ TN2ZKMA E 4 3 Wiring and piping diagram 4 3 1 1 Flow guide tube system...
Страница 25: ...14 INZ TN2ZKMA E 4 3 1 2 Flow guide tube system with valve...
Страница 26: ...15 INZ TN2ZKMA E 4 3 1 3 Ejector system...
Страница 27: ...16 INZ TN2ZKMA E 4 3 1 4 Ejector system with valve...
Страница 31: ...20 INZ TN2ZKMA E 5 2 Key operation flow diagram outline...
Страница 32: ...21 INZ TN2ZKMA E...
Страница 33: ...22 INZ TN2ZKMA E...
Страница 34: ...23 INZ TN2ZKMA E...
Страница 113: ...102 INZ TN2ZKMA E 11 SPECIFICATIONS 11 1 Specifications...
Страница 114: ...103 INZ TN2ZKMA E...
Страница 115: ...104 INZ TN2ZKMA E 11 2 Code symbols Converter...
Страница 116: ...105 INZ TN2ZKMA E Detector...
Страница 117: ...106 INZ TN2ZKMA E Ejector Exclusive cable...
Страница 118: ......