RUNNING THE MOTOR 

Before giving RUN command, motor parameters have to be set and auto tuning has to be performed. 

 

7.1 

Motor parameters

 

In table 7 motor related parameters are shown, please set motor parameters following same order:

 

 

Function

 

Meaning

 

Recommended setting

 

Remarks

 

P01

 

Number of motor poles

 

Depends on the motor

 

Depends on the motor

 

F03

 

Motor’s maximum frequency (Hz)

 

50 Hz

 

F04

 

Motor’s synchronous frequency (Hz)

 

50 Hz

 

F05

 

Motor’s rated voltage (V)

 

400 V

 

F11

 

Overload detection level (A)

 

Same value than P03

 

Depends on the motor

 

F42

 

Drive control selection

 

1

 

Dynamic torque vector 

control

 

P02

 

Motor’s rated power (kW)

 

Depends on the motor

 

Depends on the motor

 

P03

 

Motor’s rated current (A)

 

P04

 

Auto tuning mode

 

P04=1: static auto tuning (P07 and P08 are measured)

 

1

 

P06

 

Motor’s no

-

load current (A)

 

40 % of P03

 

P07

 

Motor’s stator resistance (R1) in %

 

Measured by auto tuning (P04=1)

 

-

 

P08

 

Motor’s stator reactance (X1) in %

 

P12

 

Motor’s slip frequency (Hz)

 

Depends on the motor

 

Check NOTE 

 

Table 7: Motor related parameters

 

NOTE:

 

 

If motor’s speed is 3000 rpm, means that motor has 2 poles, in consequence P01=2.

 

 

If motor’s speed is 1500 rpm, means that motor has 4 poles, in consequence P01=4.

 

 

Motor’s slip frequency formula:

 

(rpm)

 

speed

 

s

Synchronou

(Hz)

Frequency 

*

(rpm))

 

speed

 

Rated

(rpm))

 

speed

 

us

(Synchrono

P12

=

 

 

Example: Motor’s rated speed= 2740 rpm

 

 

Hz

33

.

4

rpm

 

3000

Hz

 

50

*

rpm)

2740

rpm

 

(3000

P12

=

=

 

 

7.2 

Step by step auto tuning procedure

 

After setting correctly motor parameters, next step is to perform an auto tuning:

 

 

1. 

Set P04= 1 (After auto tuning is finished, it will be se automatically to 0).

 

2. 

After selecting MAINTENANCE operation give RUN command (UP or DOWN). Keep RUN command 
until inverter’s keypad shows that auto tuning is finished.

 

 

Auto tuning mode 1 (P04=1) is static, it means that motor will not turn.

 

 

 

Auto tuning process will automatically finish. When it is finished 

p06

 parameter is shown.

 

 

If inverter trips 

er7

 

during auto tuning, please check chapter 11.

 

 

 

Содержание FUJI-Hydraulic FRN AR Series

Страница 1: ...STARTING GUIDE HYDRAULIC SOLUTION Frequency inverter for hydraulic elevator SG_FUJI_Hydaulic_EN_1 0 9...

Страница 2: ...and 55 kW added 18 02 13 S Ure a 1 0 4 Chapter 4 and 5 are added Contents updated 20 02 13 M A G mez S Ure a S Ure a 1 0 5 Wiring and Operation information is modified 25 03 13 M A G mez S Ure a S Ur...

Страница 3: ...WIRING EXAMPLE 12 6 1 Power Controller 12 6 2 Valves control 13 6 3 Basic wiring diagram 13 7 RUNNING THE MOTOR 14 7 1 Motor parameters 14 7 2 Step by step auto tuning procedure 14 8 SPEEDS SETTING 1...

Страница 4: ...connections wiring operation or maintenance and inspection Ensure you have sound knowledge of the device and familiarize yourself with all safety information and precautions before proceeding to opera...

Страница 5: ...a recommended molded case circuit breaker MCCB or residual current operated protective device RCD earth leakage circuit breaker ELCB with overcurrent protection in the path of each pair of power lines...

Страница 6: ...anual the motor may rotate with a torque or at a speed not permitted for the machine An accident or injuries could occur Even if the inverter has interrupted power to the motor if the voltage is appli...

Страница 7: ...humidity 5 to 95 No condensation Atmosphere The inverter must not be exposed to dust direct sunlight corrosive gases flammable gases oil mist vapor or water drops Pollution degree 2 IEC EN 60664 1 7...

Страница 8: ...pply side primary side according to the following tables Breaking capacity Min 10 kA Rated voltage Min 500 V Power supply voltage Nominal applied motor kW Inverter type Fuse rating A Figure 1 Input po...

Страница 9: ...inverter type is FRN4 0AR1 4E Note A box replaces an alphabetic letter depending on the enclosure A box replaces an alphabetic letter depending on the shipping destination Enclosure M IP21 or L IP55...

Страница 10: ...mming mode This key discards the settings being configured and cancels the screen transition In Alarm mode This key resets the alarm states and switches to Programming mode UP DOWN key which works as...

Страница 11: ...gure press to confirm PRG 2 1 Data Set 2 Data Check 3 Changed Data 4 Data Copy 5 Timer Setup 6 Initialize 3 Use to select 1 Data Set as it is shown on the figure press to confirm PRG 2 1 F Fundamental...

Страница 12: ...saved next parameter is automatically shown in LCD 6 WIRING EXAMPLE 6 1 Power Controller On the following diagram guidance only 1 an example of motor s wiring with and without inverter is shown single...

Страница 13: ...oller side Same philosophy than a classic hydraulic lift can be used Inverter is not working during DOWN direction travel MAINTENANCE travel Same philosophy than UP DOWN travel Speed is controlled by...

Страница 14: ...Measured by auto tuning P04 1 P08 Motor s stator reactance X1 in P12 Motor s slip frequency Hz Depends on the motor Check NOTE Table 7 Motor related parameters NOTE If motor s speed is 3000 rpm means...

Страница 15: ...8 1 Soft start speed Soft start speed is dependent on HIGH speed as it is shown on below example Example If HIGH speed is C08 Soft start speed C16 HIGH speed Soft start speed C08 C16 C09 C17 C10 C18 C...

Страница 16: ...utput function changes the state from ON to OFF when inverter has switched off IGBT s gate circuit It ensures that magnetic contactors will open after current flow is finished In order to have AX func...

Страница 17: ...stop In order to improve the comfort at stopping soft stop parameters can be adjusted as shown in table 13 Function Recommended setting Description F20 0 2 Hz Starting frequency F21 60 DC braking lev...

Страница 18: ...epend on the load so higher load means lower speed and vice versa Speed ON FWD X1 SS1 ON ON Time ON EN1 EN2 ON E31 F07 F08 E11 E10 ON When U29 Power is reached and speed is higher than E31 speed is li...

Страница 19: ...can make a longer creep speed In order to avoid excessive waiting time two different deceleration holding time parameters can be adjusted U49 U59 There are two limit zones Limit 1 and Limit 2 Dependin...

Страница 20: ...High speed U44 U49 ON ALP Figure 10 Deceleration holding time when Limit 1 zone is reached Output frequency Deceleration holding time default setting Upper Limit 1 U44 90 45 Hz U49 0 25 s Lower Limit...

Страница 21: ...on E03 25 E05 17 E06 18 E31 30 Hz U00 1 U06 3001 U07 8006 U11 20 U12 4003 U13 2 U16 2056 U17 8020 U19 20 0 U21 20 U22 2003 U23 2004 U26 2055 U27 2002 U29 Power limit U30 0 10 U31 20 U32 2006 U33 2003...

Страница 22: ...rrectly set APL function may not work as expected Inverter capacity U94 11 kW 0 22 15 kW 0 30 18 5 kW 0 37 22 kW 0 44 30 kW 0 60 37 kW 0 74 45 kW 0 90 55 kW 1 1 Table 16 U94 setting Function Recommend...

Страница 23: ...z See chapter 9 4 1 C08 HIGH LOW MAINTENANCE speed It depends on installation See chapter 8 for additional details C09 HIGH LOW MAINTENANCE speed C10 HIGH LOW MAINTENANCE speed C11 HIGH LOW MAINTENANC...

Страница 24: ...tion 2 60 U56 Step 12 Control Function 23 U57 Step 12 Input 1 2008 U58 Step 12 Input 2 2011 U59 Step 6 Function 1 0 50 s U61 Step 13 Control Function 30 Soft start Configuration See chapter Error No s...

Страница 25: ...of the motor has risen abnormally 0l1 Overload of motor 1 The electronic thermal protection for motor overload detection was activated 0lu Inverter overload The temperature inside the inverter has ris...

Страница 26: ...c europe com www fujielectric europe com Spain Fuji Electric Europe GmbH Sucursal en Espa a Ronda Can Fatj 5 Edifici D Local B Parc Tecnol gic del Vall s 08290 Cerdanyola Barcelona Tel 34 0 935 824 33...

Отзывы: