700-SDI-RADAR-LX-80-Man Rev 1 08 Oct 2021
9
/49
loggers, or data concentrators. The signal range and function for 4 – 20 mA analog output can be
configured in the setup application so the sensor will be able to signal the best suitable value range
with the available current range.
The sensor’s current step has a limiting resolution of 0.3 μA. Ensure the minimal and maximal
values representing 4 mA and 20 mA have sufficient resolution for system requirements.
Figure 3-2: Analog 4-20 mA internal architecture
Measurement of the current by the client device (logger, PLC, modem etc.) must be implemented as
the high side current measurement as shown in figure 3-3. If a sensing resistor is used, resistance
should be selected from the range 10Ω to 500Ω, with
a
recommended value 100Ω for the sensing
resistor.
Figure 3-3: High side current measurement for the 4-20 mA analog output
Содержание 21216
Страница 5: ...iii 10 1 SPECIFICATIONS 47 10 2 MECHANICAL ASSEMBLY 48...
Страница 39: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 34 49...
Страница 41: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 36 49...
Страница 42: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 37 49...
Страница 46: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 41 49 TROUBLESHOOTING...
Страница 47: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 42 49 continued...
Страница 48: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 43 49 continued...
Страница 49: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 44 49...
Страница 50: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 45 49...
Страница 51: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 46 49...
Страница 53: ...700 SDI RADAR LX 80 Man Rev 1 08 Oct 2021 48 49 10 2 MECHANICAL ASSEMBLY All measurements in mm...