9-1
9 Temperature Alarms
There are five temperature alarm functions:
1.
High Temperature Alarm
2.
Low Temperature Alarm
3.
FDA Alarm
4.
Sensor Alarm
5.
Rise Time Alarm
If alarm conditions occur an audible alarm will sound and the displays will alternately display the
product selection and alarm message. Timers cannot be started when a slot is in alarm condition.
9.1 High and Low Temperature Alarm
If the slot temperature is above or below the preset limits for product selection, the controller will
enter the High or Low alarm condition. The audible alarm will sound and the alarm message will
read either
SLOT TEMP HIGH
or
SLOT TEMP LOW
.
To turn off the audible alarm, press any
Timer
key. The displays will alternately display the product
selection and the alarm message until the slot temperature is within the preset limits. The alarm
message will be displayed until the slot temperature is within the preset limits.
Alarm Display Messages
ENTER
PAGE
MENU
TEMP
TEMP
TEMP
TEMP
LOW
LOW
LOW
LOW
SLOT
SLOT
SLOT
SLOT
Press any TIMER key to turn off the audible alarm.
TEMP
TEMP
TEMP
TEMP
ENTER
PAGE
MENU
SLOT
SLOT
SLOT
SLOT
HIGH
HIGH
HIGH
HIGH
Press any TIMER key to turn off the audible alarm.
NOTE:
The low temperature audible alarm is inhibited at power-up. The
SLOT TEMP LOW
message will be displayed until the slot temperature is within the preset limits.