Connecting the
battery commu-
nication cables
1
Strip 10 mm from the single conductors
and mount the ferrules if necessary.
2
Insert the cable into the respective slot
and check the cable is securely retained.
IMPORTANT!
Use only twisted pairs for connecting
"Data +/-" and "/-", see section
Permitted cables for the data commu-
nication area
.
Twist the cable shield and insert into the
"SHIELD" slot.
IMPORTANT!
Improperly fitted shielding can cause data
communication problems.
Wiring proposal recommended by Fronius, see page .
Terminating res-
istors
It may be possible for the system to function without terminating resistors. However,
owing to interference, the use of terminating resistors according to the following overview
is recommended for trouble-free functioning.
For permissible cable and max. distances see chapter
on page
.
IMPORTANT!
Terminating resistors that are not positioned as illustrated can result in interference in the
data communication. If the terminating resistor on the battery cannot be deactivated, the
battery is to be set up at the bus end (see option 2, 3).
75
EN
Содержание Symo GEN24 10.0
Страница 2: ......
Страница 10: ...10 ...
Страница 11: ...General information 11 ...
Страница 12: ...12 ...
Страница 28: ...28 ...
Страница 29: ...Backup power variant PV Point OP 29 ...
Страница 30: ...30 ...
Страница 32: ...32 ...
Страница 33: ...Backup power variant Full Backup 33 ...
Страница 34: ...34 ...
Страница 41: ...Installation 41 ...
Страница 42: ...42 ...
Страница 82: ...82 ...
Страница 83: ...Settings web interface of the inverter 83 ...
Страница 84: ...84 ...
Страница 104: ...104 ...
Страница 105: ...Appendix 105 ...
Страница 106: ...106 ...
Страница 116: ...116 ...
Страница 117: ...Circuit diagrams 117 ...