4
Insert the strain-relief device into the hole
and secure to the torque specified by the
manufacturer.
5
Guide the mains cable through the strain-
relief device from below.
Remove the OP terminal.
6
Strip the insulation of the single conduct-
ors by 12 mm.
The cable cross section must be between
1.5 mm
2
and 10 mm
2
. Lift to open the ter-
minal's operating lever and insert the
stripped single conductor into the slot
provided, all the way up to the stop. Then
close the operating lever until it engages.
NOTE!
Only one conductor may be connected
to each pin. The conductors can be
connected without ferrules.