6
CAUTION!
Danger due to polarity reversal at the
terminals.
Serious substantive damage to the PV
system may result.
▶
Use a suitable measuring instrument
to check the polarity of the DC cabling
when the battery is switched on.
▶
The maximum voltage for the battery
input must not be exceeded (see
on page
7
Insert the DC terminals into the respective
slot until they engage.
8
Fasten the screws of the cable guides to
the housing using a screwdriver (TX20)
and a torque of 1.3-1.5 Nm.
NOTE!
Do not use a drill driver as this could
cause overturning.
A possible consequence of overturning is,
for example, damaging the strain-relief
device.
IMPORTANT!
Information for connection on the battery side can be found in the installation instructions
from the relevant manufacturer.
65
EN