signals may be attenuated or amplified by the inverter. The settings below can be
used to counteract this if necessary.
Parameter
Range of val-
ues
Description
"Reduction of
Influence"
Off
The function is deactivated.
On
The function is activated.
"Frequency of
Ripple Control
Signal"
100
‑
3000 Hz
The frequency specified by the energy
company must be entered here.
"Grid Induct-
ance"
0.00001
‑
0.00
5 H
The value measured at the feed-in point
must be entered here.
"Measure against RCD false triggers"
(when using a 30 mA residual current circuit breaker)
NOTE!
National regulations, the grid operator's specifications or other factors may re-
quire a residual current circuit breaker in the AC connection lead.
For this situation, a type A residual-current circuit breaker is generally adequate.
Nevertheless, false alarms can be triggered for the type A residual current circuit
breaker in individual cases and depending on local conditions. For this reason, in
accordance with national legislation, Fronius recommends that a residual current
circuit breaker with a tripping current of at least 100 mA suitable for frequency
converters be used.
Parameter
Range of val-
ues
Description
"Switch-Off be-
fore 30mA RCD
Trip" (only for
Primo GEN24)
0
No measures to prevent false tripping.
1
The inverter switches off at 15 mA before
the residual current circuit breaker trips.
"Leakage Cur-
rent Factor"
(only for Symo
GEN24)
0
‑
0.25
(default: 0.16)
Reducing the setting value reduces the
leakage current and raises the intermedi-
ate circuit voltage, which slightly reduces
the efficiency. Setting value 0.16 enables
optimum efficiency.
"Iso Warning"
Parameter
Range of val-
ues
Description
"Iso Warning"
Off
The isolation warning is deactivated.
On
The isolation warning is activated.
A warning is issued in the event of an isola-
tion fault.
107
EN
Содержание Primo GEN24 3.0
Страница 2: ......
Страница 7: ...Dimensions of the inverter 187 Fronius Primo GEN24 3 6 kW 189 Fronius Primo GEN24 3 6 kW 189 7 EN...
Страница 12: ...12...
Страница 13: ...General information 13...
Страница 14: ...14...
Страница 18: ...Fronius recommends testing the Internet connection on site according to the minimum requirements 18...
Страница 34: ...34...
Страница 35: ...Backup power variant PV Point OP 35...
Страница 36: ...36...
Страница 38: ...38...
Страница 39: ...Backup power variant Full Backup 39...
Страница 40: ...40...
Страница 48: ...48...
Страница 49: ...Installation 49...
Страница 50: ...50...
Страница 57: ...Do not install the inverter on the ceiling 57 EN...
Страница 101: ...Settings user interface of the in verter 101...
Страница 102: ...102...
Страница 132: ...132...
Страница 133: ...Options 133...
Страница 134: ...134...
Страница 143: ...2 Set the DC disconnector to the On switch position Switch on the auto matic circuit breaker 143 EN...
Страница 144: ...144...
Страница 145: ...Appendix 145...
Страница 146: ...146...
Страница 172: ...172...
Страница 173: ...Circuit diagrams 173...
Страница 174: ...174...
Страница 175: ...Circuit Diagram PV Point OP Circuit Diagram 175 EN...
Страница 176: ...Fronius Primo GEN24 and BYD Battery Box Premium HV Circuit Diagram 176...
Страница 177: ...Fronius Primo GEN24 with two BYD Battery Box Premium HV connected in parallel Circuit Diagram 177 EN...
Страница 178: ...Fronius Primo GEN24 with three BYD Battery Box Premium HV connected in parallel Circuit Diagram 178...
Страница 179: ...Automatic switch to backup power 1 pin double separation e g Austria Circuit Diagram 179 EN...
Страница 180: ...Automatic switch to backup power 1 pin single separation e g Australia Circuit Diagram 180...
Страница 181: ...Automatic switch to backup power 2 pin double separation e g Germany Circuit Diagram 181 EN...
Страница 182: ...Automatic switch to backup power 2 pin single separation e g France Spain Circuit Diagram 182...
Страница 183: ...Automatic switch to backup power 2 pin double separation e g UK Circuit Diagram 183 EN...
Страница 185: ...Fronius Primo GEN24 with Enwitec Box Circuit Diagram 185 EN...
Страница 186: ...Wiring diagram surge protective device SPD Circuit Diagram 186...
Страница 187: ...Dimensions of the inverter 187...
Страница 188: ...188...
Страница 189: ...Fronius Primo GEN24 3 6 kW Fronius Primo GEN24 3 6 kW 189 EN...
Страница 190: ...190...
Страница 191: ...191 EN...
Страница 192: ......