140
Fronius IG
Plus 150
Input data
MPP voltage range
230 - 500 V DC
Max. input voltage
600 V DC
(at 1000 W/m²/ -10 °C (14 °F) in an open circuit)
Max. input current
54.9 A DC
Output data
Nominal output power (P
nom
)
12 kW
Max. output power
12 kW
Nominal mains voltage
3 ~ NPE 400 V, +10 / -15 %
1)
Nominal output current (three phase)
18.2 / 17.4 A AC
Nominal frequency
50 - 60 Hz
1)
Harmonic distortion
< 3.5 %
Power factor cos phi
1
Max. permitted mains impedance Zmax at PCC
2)
none
General data
Maximum efficiency
96 %
Europ. max. efficiency
95.5 %
Power consumption at night
< 1 W
Cooling
Controlled forced ventilation
Protection class
IP 44
Dimensions l x w x h
244 x 434 x 1221 mm (9.6 x 17.1 x 48.1 in)
Weight
49 kg (108 lb).
Permissible ambient temperature
-20 °C - +50 °C (-4 °F - +122 °F)
(with 95% rel. humidity)
EMC emission class
B
Protective equipment
DC insulation measurement
Warning when R
ISO
< 500 kOHM
DC overvoltage protection
integrated
Protection against reversed polarity
integrated
Manifestation of DC overload
Operating point shift
Explanation of
footnotes
1)
The values provided are standard values. Upon request, the Fronius
IG Plus can be customized to the respective country.
*)
PCC = interface to the public grid
Содержание Fronius IG Plus 100
Страница 2: ......
Страница 4: ...ud_fr_st_et_01382 012008...
Страница 14: ...6...
Страница 15: ...7 General Information...
Страница 16: ...8...
Страница 20: ...12...
Страница 21: ...13 Installation and Startup...
Страница 22: ...14...
Страница 71: ...63 Closing Fronius IG Plus Closing Froni us IG Plus 1 1 4 2 7 3 5 6...
Страница 77: ...69 Operation...
Страница 78: ...70...
Страница 118: ...110...
Страница 119: ...111 Troubleshooting and Maintenance...
Страница 120: ...112...
Страница 141: ...133 Appendix...
Страница 142: ...134...
Страница 152: ...144...
Страница 155: ......