137
Fronius IG
Plus 70
Input data
MPP voltage range
230 - 500 V DC
Max. input voltage
600 V DC
(at 1000 W/m²/ -10 °C (14 °F) in an open circuit)
Max. input current
29.7 A DC
Output data
Nominal output power (P
nom
)
6.5 kW
Max. output power
6.5 kW
Nominal mains voltage
1 ~ NPE 220 / 230 V, +10 / -15 %
1)
2 ~ NPE 220 / 230 V, +10 / -15 %
1)
Nominal output current
single phase
29.5 / 28.3 A AC
two phase
14.8 / 14.1 A AC
Nominal frequency
50 - 60 Hz
1)
Harmonic distortion
< 3.5 %
Power factor cos phi
1
Max. permitted mains impedance Zmax at PCC
2)
1-phase
161 mOhm
2-phase
none
General data
Maximum efficiency
96 %
Europ. max. efficiency
95.4 %
Power consumption at night
< 1 W
Cooling
Controlled forced ventilation
Protection class
IP 44
Dimensions l x w x h
244 x 434 x 962 mm (9.6 x 17.1 x 37.8 in)
Weight
38 kg (83.7 lb)
Permissible ambient temperature
-20 °C - +50 °C (-4 °F - +122 °F)
(with 95% rel. humidity)
EMC emission class
B
Protective equipment
DC insulation measurement
Warning when R
ISO
< 500 kOHM
DC overvoltage protection
integrated
Protection against reversed polarity
integrated
Manifestation of DC overload
Operating point shift
Содержание Fronius IG Plus 100
Страница 2: ......
Страница 4: ...ud_fr_st_et_01382 012008...
Страница 14: ...6...
Страница 15: ...7 General Information...
Страница 16: ...8...
Страница 20: ...12...
Страница 21: ...13 Installation and Startup...
Страница 22: ...14...
Страница 71: ...63 Closing Fronius IG Plus Closing Froni us IG Plus 1 1 4 2 7 3 5 6...
Страница 77: ...69 Operation...
Страница 78: ...70...
Страница 118: ...110...
Страница 119: ...111 Troubleshooting and Maintenance...
Страница 120: ...112...
Страница 141: ...133 Appendix...
Страница 142: ...134...
Страница 152: ...144...
Страница 155: ......