![Froling Turbomat TM 400 Скачать руководство пользователя страница 65](http://html1.mh-extra.com/html/froling/turbomat-tm-400/turbomat-tm-400_installation-instructions-manual_2338738065.webp)
▪ Sawdust and carpentry waste should only be used with systems with a rotary
valve.
▪ The store should be fitted with a pressure release device in accordance with re‐
gional regulations.
▪ The same limits apply for the permitted water content of sawdust as for wood
chips.
NOTICE
For fuels with a water content < W30 the boiler's rated heat output can only be
guaranteed if it is used with a flue gas recirculation system (FGR).
Miscanthus
Switchgrass or elephant grass (Latin name: miscanthus) is a C4 plant. Standards and
regulations for burning these plants have not been standardised, so the following ap‐
plies:
NOTICE! The regional regulations for burning miscanthus should be observed. Opera‐
tion may only be possible by special permit.
Changing the fuel
CAUTION
Incorrect fuel parameter settings:
Incorrect parameter settings have a significant adverse effect on the functioning
of the boiler, and as a result this will invalidate the guarantee.
Therefore:
❒ If the fuel is changed (e.g. from wood chips to pellets), the system must be
reset by Froling customer services.
Commissioning
5
Initial startup
Installation Instructions Turbomat TM 400-500 | M0690213_en
65