Parameter list - Lambdatronic P 3100
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria
Page 69
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com
B0190806
7
Oil boiler
...
←
←
←
←
Oil boiler-Storage
temp diff
10°
←
←
←
←
The minimum temperature difference between the oil
boiler and storage tank which releases the oil boiler
loading pump output.
Oil boiler start
delay
60m
←
←
←
←
Delays start of the burner relay if the boiler fails (the
boiler status is off, fault or shut down and the boiler
temp. is 5°C below the target value). In storage mode
the burner relay, however, only comes on when the
storage tank has cooled down. (Top storage temp.
lower than maximum temp. required.)
Oil boiler min.
runtime
5m
←
←
←
←
Minimum runtime for the oil boiler
Oil boiler min.
temp.
50°
←
←
←
←
Oil boiler minimum temperature for release of oil boiler
loading pump or activation of switch valve.
Solar
...
←
←
←
←
Setup Sol Register:
1
←
←
←
←
System-specific parameter: set as per solar diagrams!
Option for systems
0-9
DHW tank target for
solar l.
65°
←
←
←
←
When the specified temperature is reached in the DHW
tank sensor, the DHW tank loading pump switches off.
When using a switch valve, it switches to the heating
element of the storage tank.
Min rev solar pumps 45%
←
←
←
←
Adjusts the minimum speed to the relevant pump type.
Solar ON diff temp
10°
←
←
←
←
The collector loading pump activates when the collector
temperature exceeds the storage or DHW tank
temperature by this value
Solar OFF diff temp
5°
←
←
←
←
The collector loading pump switches off when the
collector temperature exceeds the storage or DHW tank
temperature by this value
Max temp storage
low
85°
←
←
←
←
Maximum bottom storage tank temperature switches
solar loading pump off (unless the excess temperature
protection for the collector activates (135°)). Only in
conjunction with storage tank.
Solar
...
←
←
←
←
Min rev solar pumps 45%
←
←
←
←
Adjusts the minimum speed to the relevant pump type.
In conjunction with
solar heat
exchanger (systems
12,13,14 and 15)
Coll. ON temp. dif.
10°
←
←
←
←
The collector loading pump activates when the collector
temperature exceeds the lower storage or DHW tank
temperature by this value.
Max temp storage
low
85°
←
←
←
←
Maximum bottom storage tank temperature switches
solar loading pump off (unless the excess temperature
protection for the collector activates (135°)).
ON Delay storage
pump
600s
←
ON and OFF delay for the storage-HE-pump relative to
the collector pump
Storage Solar set
60°
←
Top storage tank target value for solar loading
Solar return storage
lo diff
16°
←
Maximum temperature difference between bottom
storage tank temperature or bottom DHW tank
temperature and collector return feed temperature.