Installers and service technicians
Electrical Connection
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen, Austria
Page 57
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected] www.froeling.com
B0190806
7
7.3.4
Connection instructions for Komfort pellet box
With the automatic universal suction system the Komfort pellet box is
linked to the control board with a flexible cable (5x 0.75mm², flexible,
e.g. YMM as per ÖVE-K41-5 or H05VV-F as per DIN VDE 0281-5).
This is a 24V control line.
Komfort pellet box
P
ri
m
a
ry
a
ir
S
e
c
o
n
d
a
ry
a
ir
Lambdatronic P3100
The figure above shows the plugged-in 5-pin connecting plug of the
Komfort pellet box and the accompanying connection layout of the
Lambdatronic P3100 control system.
To check the plug arrangement:
Detach the protective plate (1)
from the board
Perform check using the
board’s labels
The servomotors (2) of the
pellet box must be switched
to the “R” position!
The servomotors are ready to plug in and are connected to the board.
All necessary plug clips are included in delivery!
1
2