Time

DRY Function

Room

temperature

Set temperature

Cool

Cool

Cool

Fan only

Fan only

DRY operation

The dry mode will automatically select 
the drying operation based on the 
difference between the set 
temperature and the actual room 
temperature.
The temperature is regulated while 
dehumidifying by repeating turning on 
and off of the cooling operation or fan 
only. The fan speed is LOW.
1.  Push the MODE button to select 

DRY.

2.  Push the TEMP button to set the 

desired temperature from 21ºC to 
28ºC.

3.  Push the ON/OFF button, the 

operation lamp lights and the air 
conditioner start to operate in the 
DRY mode. FAN SPEED is Low. 
Push the ON/OFF button again to 
stop this unit operation.

Due to the difference of the set 
temperature of the unit and the 
actual indoor temperature, the Air 
Conditioner when in DRY mode will 
automatically operate many times 
without running the COOL and FAN 
mode.

Air flow direction adjustment

Use SWING to adjust the airflow direction up and down.
1.  When swing is pressed the horizontal louver moves up and down 

automatically.  Press again to stop operation

If the louver oscillates or moves in a position that could affect the cooling or 
heating of the air conditioner the direction of the oscillation/movement would 
alter automatically.

39

40

Attention

Attention

How the air conditioner works

Automatic operation

When the Air Conditioner is ready for use, switch on the power and the 
OPERATION indicator lamp on the display panel of the indoor unit starts 
flashing.
1. Use the MODE .select button to select AUTO.
2. Push the TEMP button to set the desired room temperature. The most 

comfortable temperature setting are between 21ºC o to 28ºC.

3. Push the ON/OFF button to start the air conditioner. The OPERATION lamp 

on the display panel of the indoor unit lights. The

operating mode is AUTO FAN SPEED is automatically set and there are no 

indicators shown on the display panel of the remote controller.

4. Push the ON/OFF button again to stop the unit operation.

COOL / HEAT and FAN ONLY operation

1. If the AUTO mode is not comfortable, you may manually override the settings 

by using COOL, HEAT* or FAN** ONLY modes.

2. Push the TEMP button to set the desired room temperature. When in COOL 

mode, the most comfortable settings are 21ºC or above. When in HEAT 
mode, the most comfortable settings are 28 C or b elow.

3. Push the FAN SPEED to select the FAN mode of AUTO, HIGH, MED or LOW.
4. Push the ON/OFF button, the operation lamp lights and the air conditioner 

start to operate as your settings. Push the ON/OFF button again to stop this 
unit operation.

  * Nota: Only for heating and cooling models
  **Note: The FAN ONLY mode can not be used to control the temperature. 

While in this mode, only steps 1,3 and 4 may be performed.

1.  When you set the air conditioner in AUTO mode, it will automatically select cooling, 

heating(cooling/heating models only), or fan only operation depending on what 
temperature you have selected and the room temperature.

2.  The air conditioner will control room temperature automatically round the 

temperature point set by you.

3.  If the AUTO mode is uncomfortable, you can select desired conditions manually.

Attention

Содержание FRS095YC1

Страница 1: ...347 350 512 515 FM_English_120907A 1 ATTENTION Please read this manual completely before operating your room air conditioner FRS095YC1 FRS095YW1 FRS125YC1 FRS125YW1 FRS185YC2 FRS185W2 FRS225YC2 FRS225YW2 FAS C E 09C6APLW FAS C E 12C6APLW FAS C E 18C6APLW FAS C E 24C6APLW ...

Страница 2: ...ase take the appliance to the nearest WEEE collection point where available Environmental advices Welcome to the world of simple handling and no worries Contents 01 02 01 Welcome 01 02 Environmental advices 01 03 Contents 02 04 Safety precautions 04 05 Installation 5 1 Choosing the installation site 08 5 2 Parts list 10 5 3 Indoor unit installation 12 5 4 Outdoor unit installation 17 5 5 Refrigera...

Страница 3: ...t may cause electric shock 8 Do not allow water to run into electric parts It may cause failure of machine or electric shock 9 Do not drink water drained from air 03 04 The air conditioner that you have bought may be slightly different from the one illustrated in this manual Please refer to the information related to the model you have This air conditioner is for domestic use only It is not reccom...

Страница 4: ...nd degrade the insulation It may cause an electric shock 20 Ventilate the room well when used together with a stove etc An oxygen shortage may occur 21 When the unit is to be cleaned switch off and turn off the circuit breaker Do not clean unit when power is on as it may cause fire and electric shock it may cause an injury 22 Do not put a children pet or house plant where it will be exposed to dir...

Страница 5: ...as coastal areas 3 Sites with sulfuric gas such as hot water springs 4 Sites with high frequency equipment such as wireless equipment welding machines and medical installations 5 Sites with flammable gases or volatile material 6 Sites with special environmental conditions 7 Laundry rooms Indoor Unit 1 The unit must be installed at a site that does not obstruct the flow of air 2 The site must suppo...

Страница 6: ...f no less than 5 meters 16 feet and for pipes measuring at least 10 meters 33 feet in length 7 The site must provide enough space around the unit as shown in the diagram 8 Children must not be able to access the installation site More than 60cm More than 30cm More than 200cm More than 30cm More than 60cm Parts list NUMBERING PART NAME Installation plate Clip anchor Self tapping screw A ST3 9x25 Se...

Страница 7: ...20mm from the wall Refrigerant pipe hole left Ø 65 Refrigerant pipe hole right Ø 65 45 45 293 90 45 920 A Models 12000 Btu s 1 This illustration is for explanation purposes only 2 Copper lines must be insulated independently 7 8 5 4 2 3 1 Indoor unit Outdoor Unit 6 6 More than 12cm More than 12cm Air filter More than 200cm More than 60cm More than 30cm More than 60cm More than 15cm A B C 9 B above...

Страница 8: ...ole left Ø 95 50 50 Indoor unit outline Models 24000 Btu s Models 30000 Btu s 325 55 55 1250 815 257 178 55 58 above 150mm from ceiling above 120mm from wall above 120mm from wall Refrigerant pipe hole right Ø 95 Indoor unit outline Models 30000 Btu s Models 36000 Btu s Do not put the end of drain hose into water Do not block water flow by a rise Do not block water flow by a rise Connective pipe a...

Страница 9: ...e bundle Locating at the upper side can cause drain pan to overflow inside the unit 7 Never intercross nor intertwist the power wire with any other wiring 8 Run the drain hose sloped downward to drain out the condensed water smoothly Cushioning material 15 16 Attention 1 Pass the piping through the hole in the wall 2 Put the upper claw at the back of the indoor unit on the upper hook of the instal...

Страница 10: ...7 18 1 Install the outdoor part of the unit on a rigid surface to avoid excess noise and vibration 2 Direct the air vent toward an area without obstacles 3 Install the unit so that it is exposed to as little wind as possible especially in areas where it is frequently windy 4 If the installation site is exposed to heavy winds such as in coastal areas place the unit along the widest part of the wall...

Страница 11: ...ion conditions 19 20 Flaring work Main cause for refrigerant leakage is due to defect in the flaring work Carry out correct flaring work using the following procedure 1 Cut the pipes and the cable A Use the piping kit accessory or pipes purchased locally B Measure the distance between the indoor and the outdoor unit C Cut the pipes a little longer than the measured distance D Cut the cable 1 5m lo...

Страница 12: ... 220 230V 60Hz 220 240V 50Hz 220 230V 60Hz MODEL INPUT RATED AMP Switch Fuse POWER SUPPLY CABLE SIZE 10A 10A 16A 16A 25 32A 25 32A 1 0 mm 1 5 mm 2 5 mm 2 5 mm 2 5 mm 2 5 mm Note The supply voltage must be consistent with the rate voltage of the air conditioner Electrical work 1 If there is serious safety problem about the power supply the technicians should refuse to install the air conditioner an...

Страница 13: ...ouch any electrical or metal parts Connect the cable to the outdoor unit Screw Cover 40mm 40mm 10mm 10mm 18000 btu s CABLE Cooling model 18000 btu s btu s CABLE Heating and cooling model Cable code 18000 btu s CABLE Heating and cooling model 40mm 10mm 40mm 10mm Cable D Cable F Cable E or Cable code Cable code Cable code 23 24 9000 and 18000 Btu s COOLING MODEL 24000 Btu s HEATING AND COOLING MODE ...

Страница 14: ...d have an air gap contact separation of at least 3mm in each active phase conductors Caution After the confirmation of the above conditions prepare the wiring as follows Air purging Air and moisture in the refrigerant system have undesirable effects as indicated below 1 Pressure in the system rises 2 Operating current rises 3 Cooling or heating efficiency drops 4 Moisture in the refrigerant circui...

Страница 15: ...he Low pressure charge hose 8 Fully open the packed valve stems B and A Vacuum pump Charge hose Manifold valve 76cm Hg Charge hose Handle Lo Handle Hi Outdoor unit Indoor unit 9 Securely tighten the cap of the packed valve 27 28 Air purging with vacuum pump 1 Check that each tube both liquid and gas side tubes between the indoor and outdoor units have been properly connected and all wiring for the...

Страница 16: ...r a liquid neutral detergent on the indoor unit connection or outdoor unit connections by a soft brush to check for leakage of the connecting points of th piping If bubbles come out the pipes have leakage Leak detector Use the leak detector to check for leakage Caution A Lo packed valve B Hi packed valve C and D are ends of indoor unit connection Cover indoor unit check point 1 Insulated resistanc...

Страница 17: ...ectly 4 If the unit has been out of use for a long period of time it is recommended that the air filter be cleaned before use During continuous use clean the air filter every two weeks 5 This air conditioner was designed for use under the following conditions If air conditioner is used outside of the above conditions certain safety protection features may come into operation and cause the unit to ...

Страница 18: ...n Attention 88 17 13 18 14 15 16 Remote control ESPECIFICACIONES DEL CONTROL REMOTO Rated voltage Lowest of voltage of CPU emiting signal Transmission distance Environment 3 V 2 4 V 8 m 5ºC 60ºC With 3 V reaches 11m Remote control battery To use the remote control it is necessary to install two R03 Ir03x2 alkaline AAA batteries 1 The air conditioner will not operate when curtains doors our other m...

Страница 19: ...s Otherwise battery leakage may damage the remote controller 3 The average battery life under normal use is about 6 months 4 Replace the batteries when there is no answering beep from the indoor unit or if the Transmission Indicator light fails to light 3 When selecting the function of timer the remote control sends automatically a signal to the indoor unit at the specific moment If the control re...

Страница 20: ...swing up and down automatically Push again to stop it LED screen Press this button to erase the digits that are shown in the screen of the air conditioner Press again to activate 8 9 10 11 12 LCD display indicators NOTE All signs shown in the display is for the purpose of clear presentation But during the actual operation only the relative functional signs are shown on the display panel 15 16 17 1...

Страница 21: ...he indoor unit starts flashing 1 Use the MODE select button to select AUTO 2 Push the TEMP button to set the desired room temperature The most comfortable temperature setting are between 21ºC o to 28ºC 3 Push the ON OFF button to start the air conditioner The OPERATION lamp on the display panel of the indoor unit lights The operating mode is AUTO FAN SPEED is automatically set and there are no ind...

Страница 22: ...zontal louvre in closed position Exemples 6h Temp On OFF ON 6h Temp Off ON OFF 12h Temp Off ON OFF ON 14h Temp On 20h Temp On ONN OFF 23h Temp Off OFF 41 42 SLEEP mode Press the sleep button to activate the sleep mode To deactivate press the button again Cool only mode The indoor unit fan operates at a low velocity After and hour of operation the adjusted temperature will increase 1º C After the u...

Страница 23: ...ouver may generate a sound for 10 seconds this is a normal operation 43 44 How to use the indoor unit Adjusting air flow direction Adjust the air flow direction properly otherwise it might cause discomfort or cause uneven room temperatures Adjust the horizontal louver using the remote controller Adjust the vertical louver manually Adjusting the vertical air flow direction up down The air condition...

Страница 24: ...out from the filter holder then pull it downwards 3 Remove the air filter Fresh air filter support of the unit 4 Remove fresh air filter from frame support 5 Clean the fresh air filter at least once a month and replace every 4 to 5 months Use a vacuum cleaner then dry 6 Clean the support frame using a Air filter Air filter 45 46 Manual operation without remote control Manual operation can be used ...

Страница 25: ...ompressor is running or has just stopped running This sound is the sound of the refrigerant flowing or coming to a stop You can also hear a low squeak sound when the compressor is running or has just stopped running This is caused by heat expansion and cold contraction of the plastic parts in the unit when the temperature is changing A noise may be heard due to louver restoring to its original pos...

Страница 26: ...The air conditioner turns to FAN only mode from COOL or HEAT For cooling and heating models only mode When indoor temperature reaches the temperature setting on air conditioner the compressor will stop automatically and the air conditioner turns to FAN only mode The compressor will start again when the indoor temperature rises on COOL mode or falls on HEAT mode For cooling and heating models o ly ...

Страница 27: ... 240 15 5 845 700 320 44 5 OUTDOOR UNIT INDOOR UNIT Cycle Cooling power Btu h Heating power Btu h Rated voltage V Frequency Hz Indoor unit width mm Indoor unit high mm Indoor unit depth mm Indoor unit net weight kg Outdoor unit width mm Outdoor unit high mm Outdoor unit depth mm Outdoor unit net weight kg FRS095YC1 FRS095YW1 FRS125YC1 FRS125YW1 HEATING COOLING MODELS FRS185YC2 FRS185W2 Heat Cool 9...

Страница 28: ...54 53 Notes Notes ...

Отзывы: