 CAUTION:  

If return air ducting is not used, an adequately 

sized metal return air grille is required. Velocity should not 

exceed 500 FPM for return air grilles, and 400 FPM for filter 

grilles. It is recommended that the proper Friedrich return air 

grille kit be installed in applications where no return duct is 

used.

FILTERS

Two replaceable air filters are supplied from the factory. The 

filters are accessible through the access panels on the sides of 

the unit (See Figure 2) or from the inside of the building through 

the return air grille.
The combined pressure losses of the return and supply air 

paths must not exceed the external static capabilities of the 

system at the design airflow (See Table 1). 
The factory-installed filter rails are designed to hold 1" or 2" 

filters. When using 2" filters the filter rail divider tabs must be 

folded flat (See Figure 3).

NOTE:  

Dirty filters are the most common cause of inadequate 

heating and cooling performance.

•   

Inspect filters monthly

•  

Replace disposable type filters before they become 

clogged

•  

Use water and mild detergent to clean washable type 

filters

NOTE:

  Most filters are marked with an arrow to indicate the 

proper direction of air flow through the filter.  The arrow MUST 

point in the direction of air flow.

OUTDOOR AIR SYSTEM

As a completely self-contained system,  OES/OHS series units 

require an adequate supply of outdoor air to exchange heat 

from the outdoor air coil.  The outdoor air intake and discharge 

openings are located on the front and sides of the unit.  

!

 CAUTION:

  To ensure proper operation, the outdoor air 

intake and discharge air paths must be free and unobstructed 

for the first 20 inches.  The two air paths must be unrestricted 

to ensure that the intake and discharge air do not recirculate 

(also called short-circuit).

   

CONDENSATE DRAINAGE

A plastic drain hose extends from the drain pan to the vent at 

the bottom of the unit. This line can be attached to a suitable 

drainage system.  If this is done, the system must be vented 

or open type to ensure proper drainage.  Condensate water 

can freeze in cold weather which could create hazardous 

situations.

Figure 3 - Filter Rail Adjustment

Содержание OES Series

Страница 1: ...Wall Mount Outdoor Wall mounted Air Conditioners Heat Pumps OES OHS Series 920 138 02 3 04 Installation Operation Manual...

Страница 2: ...Model Information Form 19 Warranty Information 20 21 TABLE OF CONTENTS Please read this manual thoroughly prior to equipment installation or operation It is the installer s responsibility to properly...

Страница 3: ...208 230V 1 PH 60HZ Chassis Color X Alaskan Beige standard Future Revision Digit Figure 2 Unit Dimensions MODEL DIMENSIONS A B C D E F G H I J K L M N O P Q R S T OES OHS18 24 36 9 20 0 6 2 7 9 20 1 2...

Страница 4: ...0B for special installation requirements Recognize safety information This is the safety alert symbol When you see this symbol on the unit or in instructions and manuals be alert to the potential for...

Страница 5: ...external static pressures The supply and return air duct system pressure losses including filter louver grille and registers must not exceed the listed external static pressures for the indoor air sys...

Страница 6: ...filters monthly Replace disposable type filters before they become clogged Use water and mild detergent to clean washable type filters NOTE Most filters are marked with an arrow to indicate the proper...

Страница 7: ...o the rear of the cabinet See Figure 5 Repeat the above steps for each of the eight perforated metal flanges on the rear of the cabinet When completed there will be eight duct flanges that are perpend...

Страница 8: ...in flashing to the back flange of the unit top by using screws in the top panel Top rain flashing is shipped secured to the back of the unit See Figure 9 5 Position the unit in the opening and secure...

Страница 9: ...may be required for some walls Framing Material 2 x 4 s 2 x 6 s and or structural steel See Unit Dimensions Figure 2 for duct dimensions See Unit Dimensions Figure 2 for actual dimensions SUPPLY AIR O...

Страница 10: ...g its entire length Top Front of unit Wall Structure SUPPLY AIR DUCT RETURN AIR DUCT NOTE It is recommended that a bead of silicone be placed behind the side mounting flanges and under the top flashin...

Страница 11: ...d local codes national electric code and NFPA 70 Unit and controls will NOT operate unless properly grounded A ground lug is provided for ground connection Use only approved copper wire and connectors...

Страница 12: ...A 30 N A 10 N A 10 N A 19 9 30 10 10 05 2 230 208 60 1 198 253 19 9 26 0 30 30 10 10 10 10 28 30 10 10 08 2 230 208 60 1 198 253 19 9 39 0 30 40 10 8 10 10 41 50 6 10 10 2 230 208 60 1 198 253 19 9 52...

Страница 13: ...30 8 10 10 10 51 60 6 10 08 2 230 208 60 1 198 253 22 8 39 0 40 40 8 8 10 10 64 70 4 8 10 2 230 208 60 1 198 253 22 8 52 0 40 60 8 6 10 10 77 80 4 8 15 2 230 208 60 1 198 253 22 8 39 0 40 40 8 8 10 10...

Страница 14: ...Fully closed halfway open and fully open Fully open provides 15 of rated airflow of outside air The damper position is fixed Adjustment 1 Remove louvered panel from unit See Figure 11 2 Remove one 1...

Страница 15: ...aneltogainaccesstothedampermotorcontrol Adjust the thumb wheel on the back of the motor to achieve desired set point Figure 13 Commerical Room Ventilator Components Thumbwheel Fresh Air Damper Shaft E...

Страница 16: ...ns closed and energizes the compressor for cooing operation Adjustment 1 1 2 5 Ton Chassis 1 Step 1 2 for 1 1 2 3 ton models only Through the return air opening remove two 2 screws on the access cover...

Страница 17: ...is not required to be mixed with conditioned air Units with vent packages have louvered front panels to allow for air intake Units without ventilation packages have a BOP blank off plate instead of a...

Страница 18: ...cuit breakers inside unit are ON 2 Check to see if all duct work is sealed to unit for an airtight fit 3 Thermostat is level and properly installed Heat anticipator indicator is set to the correct set...

Страница 19: ...L MOUNT MODEL WALL MOUNT SERIAL IF WALL MOUNT WAS PURCHASED INSTALLED IN A MANUFACTURED STRUCTURE DATE OF PURCHASE DEALER NAME DEALER PHONE DEALER FAX DEALER ADDRESS DEALER CITY STATE ZIP MANUFACTURER...

Страница 20: ...da This limited warranty applies only if the unit is installed and operated in accordance with FRIEDRICH instructions and in compliance with applicable local installation and building codes and good t...

Страница 21: ...stributor 4 This limited warranty applies only to units remaining at the site of the original installation except for mobile home installations and only to units installed within the continental Unite...

Страница 22: ...22 920 138 02 3 04...

Страница 23: ...23 920 138 02 3 04...

Страница 24: ...2 3 04 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in...

Отзывы: