Table 5 - Unit Sizes and Available Electric Heat
*20 KW electric heat available on cooling-only model only; not available on heat pump.
Table 6 - Electric Heat Tables
240V-1
208V-1
KW
Amps
BTU/h
Amps
BTU/h
5.0
20.8
17,065
18.1
12,800
8.0
31.2
27,320
28.1
24,588
240V-1
208V-1
KW
Amps
BTU/h
Amps
BTU/h
10.0
41.6
34,130
36.2
25,600
15.0
62.4
51,200
54.1
38,400
20.0
83.4
68,200
72.4
51,200
Unit Size
Cooling
BTUh
Heating
BTU/h at 47°F
(Heat Pump Mode)
Available
KW
18
17,000
17,000
5,8,10
24
24,600
23,600
5,8,10
30
30,000
25,000
5,8,10,15
36
36,000
34,600
5,8,10,15
42
42,000
42,000
10,15
48
48,000
48,000
10,15
60
60,000
54,000
15,20*
Multiple Circuits
Single Circuit
Factory
Circuit
Breakers
Voltage / Hz
/ Ph
Voltage
Range
MCA
HACR / Max
Breaker Size
Wire Size
(field)
Groung Wire
Size (field)
MCA
HACR
/ Max
Breaker
Size
Wire
Size
(field)
Groung
Wire
Size
(field)
Ckt 1
Ckt 2
Ckt 1
Ckt 2
Ckt 1
Ckt 2
Ckt 1
Ckt 2
Ckt 1
Ckt 1
Ckt 1
Ckt 1
OHS18KA 00
1
230/208-60-1
198-253
15.0
N/A
20
N/A
12
N/A
12
N/A
15
20
10
12
05
2
230/208-60-1
198-253
15.0
26.0
20
30
12
10
12
10
39
40
8
10
08
2
230/208-60-1
198-253
15.0
39.0
20
40
12
8
12
10
52
60
6
10
10
2
230/208-60-1
198-253
15.0
52.0
20
60
12
6
12
10
65
70
4
8
OHS24KA 00
1
230/208-60-1
198-253
19.9
N/A
30
N/A
10
N/A
10
N/A
19.9
30
10
10
05
2
230/208-60-1
198-253
19.9
26.0
30
30
10
10
10
10
41
40
8
10
08
2
230/208-60-1
198-253
19.9
39.0
30
40
10
8
10
10
54
60
6
10
10
2
230/208-60-1
198-253
19.9
52.0
30
60
10
6
10
10
67
70
4
8
OHS30KA 00
1
230/208-60-1
198-253
22.8
N/A
40
N/A
8
N/A
10
N/A
22.8
40
8
10
05
2
230/208-60-1
198-253
22.8
26.0
40
30
8
10
10
10
51
60
6
10
08
2
230/208-60-1
198-253
22.8
39.0
40
40
8
8
10
10
64
70
4
8
10
2
230/208-60-1
198-253
22.8
52.0
40
60
8
6
10
10
77
80
4
8
15
2
230/208-60-1
198-253
22.8
39.0
40
40
8
8
10
10
81
90
4
8
OHS36KA 00
1
230/208-60-1
198-253
27.9
N/A
40
N/A
8
N/A
10
N/A
27.9
40
8
10
05
2
230/208-60-1
198-253
27.9
26.0
40
30
8
10
10
10
54
60
6
10
08
2
230/208-60-1
198-253
27.9
39.0
40
40
8
8
10
10
67
70
4
8
10
2
230/208-60-1
198-253
27.9
52.0
40
60
8
6
10
10
80
80
4
8
15
2
230/208-60-1
198-253
27.9
39.0
40
40
8
8
10
10
81
90
4
8
OHS42KA 00
1
230/208-60-1
198-253
31.8
N/A
50
N/A
6
N/A
10
N/A
31.8
50
6
10
10
2
230/208-60-1
198-253
31.8
52.0
50
60
6
6
10
10
84
90
4
8
15
2
230/208-60-1
198-253
31.8
39.0
50
40
6
8
10
10
81
90
4
8
OHS48KA 00
1
230/208-60-1
198-253
41.0
N/A
60
N/A
6
N/A
10
N/A
41
60
6
10
10
2
230/208-60-1
198-253
41.0
52.0
60
60
6
6
10
10
88
90
4
8
15
2
230/208-60-1
198-253
41.0
39.0
60
40
6
8
10
10
81
90
4
8
OHS60KA 00
1
230/208-60-1
198-253
48.0
N/A
60
N/A
6
N/A
10
N/A
48
60
6
10
15
2
230/208-60-1
198-253
48.0
39.0
60
40
6
8
10
10
88
110
2
6
1
If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX,
shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-30. If other than uncoated (non-plated), 60°C or 75°C (140°F or 167°F) insulation, copper wire
(solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
2
Length shown is as measured 1 way along the wire path between the unit and the service panel for voltage drop not to exceed 10V, consult the factory for longer wire lengths if
needed.
3
Time-delay fuse, or HACR type breaker.
Heat Pumps
Table 4 - Electrical Data