III. START UP

SEQUENCE OF OPERATION

COOLING -

 Any call for cooling from the thermostat completes 

the R-Y circuit which activates the compressor contactor, 

starting both the compressor and outdoor fan motor. The G 

circuit (indoor fan motor) is automatically completed on any call 

for cooling operation. It can also be energized by the manual fan 

switch on the thermostat to provide constant air circulation. 

HEATING (OHS Models) - 

Positioning the thermostat system 

switch for heat activates the 24-Volt solenoid on the reversing 

valve. The solenoid terminal "B" is activated constantly from 

thermostat  contact  "R"  while  the  switch  is  in  the  heating 

position. A thermostat call for 1st stage heat also completes 

R-Y, the circuit activating the compressor contactor starting 

the compressor and blower motor in the same manner that it 

does in cooling.

DEFROST CYCLE 

(OHS MODELS ONLY)

The heat pump control manages temperature and time to control 

the defrost cycle.
Ambient temperatures below 40°F can result in coil temperatures 

below freezing. At these temperatures the coil temperature 

sensor will signal the heat pump control which starts the 

defrost timer.
The heat pump control will place the system in defrost mode 

after it has received coil temperature reports of 30°F or below 

for 30, 60, or 90 minutes. 
In Defrost Mode, the reversing valve switches the unit to normal 

cooling mode, and the hot gasses melt the ice and frost off of the 

outdoor coil. During this process, the outdoor fan motor stops, 

and electric strip heaters are activated indoors to maintain the 

temperature. Once the coil sensor detects 55°F, the heat pump 

sensor returns the unit to the heating cycle.
Occasionally in high winds and extreme cold, temperatures may 

create a situation where the sensor does not detect 55°F. In this 

situation, the heat pump control will restart heat pump operation 

in the heating mode after ten minutes.
The heat pump control provides three timer settings (30, 60, and 

90 minutes). These settings control the time that the outdoor coil 

remains below 32°F before the defrost cycle is started. Units are 

shipped at the 60 minute setting for greatest operating economy. 

If you need to change the setting, remove the wire connected to 

the "60" terminal and reconnect it to the desired terminal.

FINAL INSTALLATION CHECKLIST

1.   Make sure circuit breakers inside unit are ON.

2.   Check to see if all duct work is sealed to unit for an 

airtight fit.

3.   Thermostat is level and properly installed. Heat 

anticipator indicator is set to the correct setting.

4.   Test run in Heating, Cooling, and Emergency Heat 

(OHS only) mode as follows: 

    a.    Set fan control to ON.  If fan runs, return 

control to AUTO setting.  This verifies fan is 

working properly.

    b.    Set system control from OFF to COOL.  Lower 

temperature selector to 50°F or lower.  The 

compressor should energize and cool air 

should flow from room registers. Once cooling 

test is complete, return system control to OFF 

setting.  Wait 5 minutes.

    c.    Set system control to HEAT and raise 

temperature selector to 80°F or higher.  On 

OHS models, compressor should energize, 

and warm air should flow from room registers. 

On OES models, strip heater will turn on.

    d.    Set system control to EM HEAT (Emergency 

Heat). Compressor should turn off and warm 

air should continue to flow from registers.

NOTE:

 

 

On heat pump units in EM HEAT operation, the 

compressor is turned off and  heat is provided by the electric 

heating strips.  Therefore, the temperature of the discharge 

air may be warmer or cooler depending on the capacity of the 

heat strips used during EM Heat operation.

5.   Leave this Installation/Operation Manual with owner or 

user of equipment.

6.   After 72 hours of operation, the unit will achieve full 

rated operating performance.

Make sure that ALL panels are properly installed and ALL screws 

are returned to their original location and fastened securely.

IV. SERVICE / WARRANTY

SERVICE HINTS

Caution the end user to maintain clean air filters at all times, 

and to not needlessly close off supply and return air registers. 

This reduces air flow throughout the system which shortens 

equipment service life and increases operating costs.
Alert the end user that switching to the heating cycle when the 

ambient temperature is 75

°

F or higher may trip the automatic 

reset high pressure switch. The switch will reset automatically 

once the high pressure situation is eliminated. Check all power 

fuses or circuit breakers to ensure they are of the correct rating. 

Periodic cleaning of the outdoor coil is essential to permit full 

and unrestricted air flow circulation.

PRESSURE SERVICE PORTS

High and low pressure service ports are standard on all units 

so the system operating pressures can be measured.
A technical service data label is located on the actual unit.

Содержание OES Series

Страница 1: ...Wall Mount Outdoor Wall mounted Air Conditioners Heat Pumps OES OHS Series 920 138 02 3 04 Installation Operation Manual...

Страница 2: ...Model Information Form 19 Warranty Information 20 21 TABLE OF CONTENTS Please read this manual thoroughly prior to equipment installation or operation It is the installer s responsibility to properly...

Страница 3: ...208 230V 1 PH 60HZ Chassis Color X Alaskan Beige standard Future Revision Digit Figure 2 Unit Dimensions MODEL DIMENSIONS A B C D E F G H I J K L M N O P Q R S T OES OHS18 24 36 9 20 0 6 2 7 9 20 1 2...

Страница 4: ...0B for special installation requirements Recognize safety information This is the safety alert symbol When you see this symbol on the unit or in instructions and manuals be alert to the potential for...

Страница 5: ...external static pressures The supply and return air duct system pressure losses including filter louver grille and registers must not exceed the listed external static pressures for the indoor air sys...

Страница 6: ...filters monthly Replace disposable type filters before they become clogged Use water and mild detergent to clean washable type filters NOTE Most filters are marked with an arrow to indicate the proper...

Страница 7: ...o the rear of the cabinet See Figure 5 Repeat the above steps for each of the eight perforated metal flanges on the rear of the cabinet When completed there will be eight duct flanges that are perpend...

Страница 8: ...in flashing to the back flange of the unit top by using screws in the top panel Top rain flashing is shipped secured to the back of the unit See Figure 9 5 Position the unit in the opening and secure...

Страница 9: ...may be required for some walls Framing Material 2 x 4 s 2 x 6 s and or structural steel See Unit Dimensions Figure 2 for duct dimensions See Unit Dimensions Figure 2 for actual dimensions SUPPLY AIR O...

Страница 10: ...g its entire length Top Front of unit Wall Structure SUPPLY AIR DUCT RETURN AIR DUCT NOTE It is recommended that a bead of silicone be placed behind the side mounting flanges and under the top flashin...

Страница 11: ...d local codes national electric code and NFPA 70 Unit and controls will NOT operate unless properly grounded A ground lug is provided for ground connection Use only approved copper wire and connectors...

Страница 12: ...A 30 N A 10 N A 10 N A 19 9 30 10 10 05 2 230 208 60 1 198 253 19 9 26 0 30 30 10 10 10 10 28 30 10 10 08 2 230 208 60 1 198 253 19 9 39 0 30 40 10 8 10 10 41 50 6 10 10 2 230 208 60 1 198 253 19 9 52...

Страница 13: ...30 8 10 10 10 51 60 6 10 08 2 230 208 60 1 198 253 22 8 39 0 40 40 8 8 10 10 64 70 4 8 10 2 230 208 60 1 198 253 22 8 52 0 40 60 8 6 10 10 77 80 4 8 15 2 230 208 60 1 198 253 22 8 39 0 40 40 8 8 10 10...

Страница 14: ...Fully closed halfway open and fully open Fully open provides 15 of rated airflow of outside air The damper position is fixed Adjustment 1 Remove louvered panel from unit See Figure 11 2 Remove one 1...

Страница 15: ...aneltogainaccesstothedampermotorcontrol Adjust the thumb wheel on the back of the motor to achieve desired set point Figure 13 Commerical Room Ventilator Components Thumbwheel Fresh Air Damper Shaft E...

Страница 16: ...ns closed and energizes the compressor for cooing operation Adjustment 1 1 2 5 Ton Chassis 1 Step 1 2 for 1 1 2 3 ton models only Through the return air opening remove two 2 screws on the access cover...

Страница 17: ...is not required to be mixed with conditioned air Units with vent packages have louvered front panels to allow for air intake Units without ventilation packages have a BOP blank off plate instead of a...

Страница 18: ...cuit breakers inside unit are ON 2 Check to see if all duct work is sealed to unit for an airtight fit 3 Thermostat is level and properly installed Heat anticipator indicator is set to the correct set...

Страница 19: ...L MOUNT MODEL WALL MOUNT SERIAL IF WALL MOUNT WAS PURCHASED INSTALLED IN A MANUFACTURED STRUCTURE DATE OF PURCHASE DEALER NAME DEALER PHONE DEALER FAX DEALER ADDRESS DEALER CITY STATE ZIP MANUFACTURER...

Страница 20: ...da This limited warranty applies only if the unit is installed and operated in accordance with FRIEDRICH instructions and in compliance with applicable local installation and building codes and good t...

Страница 21: ...stributor 4 This limited warranty applies only to units remaining at the site of the original installation except for mobile home installations and only to units installed within the continental Unite...

Страница 22: ...22 920 138 02 3 04...

Страница 23: ...23 920 138 02 3 04...

Страница 24: ...2 3 04 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in...

Отзывы: