background image

4

5

920-138-02 (3-04)

920-138-02 (3-04)

II. INSTALLATION

Introduction

NOTE:

 Read the entire instruction manual before starting 

the installation.
The OES/OHS series air conditioners and heat pumps are 

ETL and c-ETL listed and are available in the cooling/electric 

heating sizes shown in Table 5 on page 13.  This series of 

units is designed for outside installation only. 
The OES/OHS series air conditioners and heat pumps are 

self-contained units. All components, including outdoor coil, 

compressor, and refrigerant tubing, are located in a single 

package. The units are already piped, charged, and wired. 

Refer to Figure 2 on page 3 for basic unit dimensions.

The OES/OHS series air conditioners and heat pumps are 

designed for installation in various light commercial applications. 

These instructions detail a typical method of installation. These 

units  can  be  installed  with  or  without  ductwork.  Installed 

flanges can be used for attaching ductwork or covered with a 

decorative grille. OES/OHS series units come from the factory 

with two 1" air filters installed. Simply bend tabs on filter rack 

to accommodate 2" filters. Return filter grills are offered as 

an accessory option. If a different or additional air filters are 

required, they will need to be field-installed in the duct system. 

These units have 2" long duct flanges for connecting to the 

field ducts.

Safety Considerations

Improper  installation,  adjustment,  alteration,  service, 

maintenance,  or  use  can  cause  explosion,  fire,  electrical 

shock, or other conditions which may cause personal injury or 

property damage. Consult a qualified installer, service agency, 

or your distributor or dealer for information and assistance. 

The qualified installer or agency must use factory-authorized 

parts or accessories when modifying this product. Refer to the 

individual instructions packaged with the parts or accessories 

when installing.
Follow all safety codes. Wear the proper attire, including 

safety  glasses  and  work  gloves.  Read  these  instructions 

thoroughly and follow all warnings or cautions attached to the 

unit. Consult local building codes, the National Electric Code 

(NEC), and the Installation Standards, Warm Air Heating 

and Air Conditioning Systems ANSI/NFPA 90B for special 

installation requirements.
Recognize safety information. This is the safety-alert symbol:

  When you see this symbol on the unit or in instructions 

and manuals, be alert to the potential for personal injury.

DANGER:

 Before installing or servicing system, always turn off main power to system. There may be more than one 

(1) disconnect switch. Turn off auxiliary heater power if applicable. Electrical shock can cause personal injury or death.

Understand  the  signal  words 

DANGER

WARNING

,  and 

CAUTION

. These words are used with the safety-alert symbol. 

DANGER

 identifies the most serious hazards which will result 

in severe personal injury or death. 

WARNING

 signifies hazards 

which could result in personal injury or death. 

CAUTION

 is 

used to identify unsafe practices which would result in minor 

personal injury or product and property damage. 

NOTE

 is used 

to convey special or supplemental information or to repeat and 

emphasize information previously provided.

General Recommendations 

(Do's and Do Not's)

The installation of this unit must comply with all local and 

national  electrical  and  installation  codes.    Where  local 

regulations differ with these instructions, local codes must 

apply.

  Do read the instructions completely before installation.

  Do take time to perform a quality installation.

  Supply and return air ductwork must be properly sized 

for this equipment. All ductwork should be insulated to 

prevent condensation and water damage.

  Do tape and seal all duct joints.

  Do check the indoor conditioned air duct system static 

pressure losses. It should not exceed those listed for 

these units. Consult your dealer or distributor for more 

information.

  When designing indoor supply systems, do not reduce 

air intake or discharge sizes.

• 

 Do insulate all conditioned air duct system 

components.

  Do locate thermostat on an interior wall.

  Do check that condensate drain line drains freely.

  Do provide minimum installation and service 

clearances.

  Do follow all guidelines for indoor and outdoor air 

system.

  

Do not

 drill into unit (except for 2 in. flanges for ducted 

return units).  This could cause a refrigerant leak.

  

Do not

 substitute any components without checking 

with your dealer or distributor.  If you do substitute, get 

approval in writing. Substitutions without approval void 

unit warranty.

  

Do not

 guess. Consult your dealer or distributor if any 

portion of the installation procedure is unclear.

Содержание OES Series

Страница 1: ...Wall Mount Outdoor Wall mounted Air Conditioners Heat Pumps OES OHS Series 920 138 02 3 04 Installation Operation Manual...

Страница 2: ...Model Information Form 19 Warranty Information 20 21 TABLE OF CONTENTS Please read this manual thoroughly prior to equipment installation or operation It is the installer s responsibility to properly...

Страница 3: ...208 230V 1 PH 60HZ Chassis Color X Alaskan Beige standard Future Revision Digit Figure 2 Unit Dimensions MODEL DIMENSIONS A B C D E F G H I J K L M N O P Q R S T OES OHS18 24 36 9 20 0 6 2 7 9 20 1 2...

Страница 4: ...0B for special installation requirements Recognize safety information This is the safety alert symbol When you see this symbol on the unit or in instructions and manuals be alert to the potential for...

Страница 5: ...external static pressures The supply and return air duct system pressure losses including filter louver grille and registers must not exceed the listed external static pressures for the indoor air sys...

Страница 6: ...filters monthly Replace disposable type filters before they become clogged Use water and mild detergent to clean washable type filters NOTE Most filters are marked with an arrow to indicate the proper...

Страница 7: ...o the rear of the cabinet See Figure 5 Repeat the above steps for each of the eight perforated metal flanges on the rear of the cabinet When completed there will be eight duct flanges that are perpend...

Страница 8: ...in flashing to the back flange of the unit top by using screws in the top panel Top rain flashing is shipped secured to the back of the unit See Figure 9 5 Position the unit in the opening and secure...

Страница 9: ...may be required for some walls Framing Material 2 x 4 s 2 x 6 s and or structural steel See Unit Dimensions Figure 2 for duct dimensions See Unit Dimensions Figure 2 for actual dimensions SUPPLY AIR O...

Страница 10: ...g its entire length Top Front of unit Wall Structure SUPPLY AIR DUCT RETURN AIR DUCT NOTE It is recommended that a bead of silicone be placed behind the side mounting flanges and under the top flashin...

Страница 11: ...d local codes national electric code and NFPA 70 Unit and controls will NOT operate unless properly grounded A ground lug is provided for ground connection Use only approved copper wire and connectors...

Страница 12: ...A 30 N A 10 N A 10 N A 19 9 30 10 10 05 2 230 208 60 1 198 253 19 9 26 0 30 30 10 10 10 10 28 30 10 10 08 2 230 208 60 1 198 253 19 9 39 0 30 40 10 8 10 10 41 50 6 10 10 2 230 208 60 1 198 253 19 9 52...

Страница 13: ...30 8 10 10 10 51 60 6 10 08 2 230 208 60 1 198 253 22 8 39 0 40 40 8 8 10 10 64 70 4 8 10 2 230 208 60 1 198 253 22 8 52 0 40 60 8 6 10 10 77 80 4 8 15 2 230 208 60 1 198 253 22 8 39 0 40 40 8 8 10 10...

Страница 14: ...Fully closed halfway open and fully open Fully open provides 15 of rated airflow of outside air The damper position is fixed Adjustment 1 Remove louvered panel from unit See Figure 11 2 Remove one 1...

Страница 15: ...aneltogainaccesstothedampermotorcontrol Adjust the thumb wheel on the back of the motor to achieve desired set point Figure 13 Commerical Room Ventilator Components Thumbwheel Fresh Air Damper Shaft E...

Страница 16: ...ns closed and energizes the compressor for cooing operation Adjustment 1 1 2 5 Ton Chassis 1 Step 1 2 for 1 1 2 3 ton models only Through the return air opening remove two 2 screws on the access cover...

Страница 17: ...is not required to be mixed with conditioned air Units with vent packages have louvered front panels to allow for air intake Units without ventilation packages have a BOP blank off plate instead of a...

Страница 18: ...cuit breakers inside unit are ON 2 Check to see if all duct work is sealed to unit for an airtight fit 3 Thermostat is level and properly installed Heat anticipator indicator is set to the correct set...

Страница 19: ...L MOUNT MODEL WALL MOUNT SERIAL IF WALL MOUNT WAS PURCHASED INSTALLED IN A MANUFACTURED STRUCTURE DATE OF PURCHASE DEALER NAME DEALER PHONE DEALER FAX DEALER ADDRESS DEALER CITY STATE ZIP MANUFACTURER...

Страница 20: ...da This limited warranty applies only if the unit is installed and operated in accordance with FRIEDRICH instructions and in compliance with applicable local installation and building codes and good t...

Страница 21: ...stributor 4 This limited warranty applies only to units remaining at the site of the original installation except for mobile home installations and only to units installed within the continental Unite...

Страница 22: ...22 920 138 02 3 04...

Страница 23: ...23 920 138 02 3 04...

Страница 24: ...2 3 04 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in...

Отзывы: