GB
5
The water batteries is offered in 2 sizes with different performances
and dimensions.
1. SL
Fan convector SL-DC is suitable for wall mounting.
Fan convector SL-R1 is suitable for wall and ceiling mounting.
2. SLS
Fan convector SLS-DC is suitable for wall mounting.
Fan convector SLS-R1 is suitable for wall and ceiling mounting for
heating operation. Only wall mounting for cooling operation.
2 pipes
TECHNICAL DATA
SL/SLS
200
400
600
800
1000
Battery water contents SLS
l
0,24
0,4
0,57
0,73
0,9
Battery water contents SL
l
0,47
0,8
1,13
1,46
1,8
Maximum working pressure
bar
10
10
10
10
10
Maximum water inlet temperature
°C
80
80
80
80
80
Minimum inlet water temperature
°C
4
4
4
4
4
Hydraulic fixtures
"
Eurokonus 3/4
Eurokonus 3/4
Eurokonus 3/4
Eurokonus 3/4
Eurokonus 3/4
Power supply
V/ph/Hz 230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
Maximum current absorbed
A
0,11
0,16
0,18
0,26
0,28
Maximum power absorbed
W
11,9
17.6
19,8
26,5
29,7
Weight SL
kg
17
20
23
26
29
Weight SLS
kg
12
14
16
19
23
Product range
Nominal technical features
Art.
nr
Type
76628
SL200DC1
76629
SL400DC1
76630
SL600DC1
76631
SL800DC1
76632
SL1000DC1
Art.
nr
Type
76633
SLS200DC1
76634
SLS400DC1
76635
SLS600DC1
76636
SLS800DC1
76639
SLS1000DC1
Art.
nr
Type
76614
SL200R1
76616
SL400R1
76617
SL600R1
76618
SL800R1
76619
SL1000R1
Art.
nr
Type
76623
SLS200R1
76624
SLS400R1
76625
SLS600R1
76626
SLS800R1
76627
SLS1000R1