VYPER

 VARIABLE SPEED DRIVE

MAINTENANCE

100-200 IOM (FEB 09)

Page 56

The logic board contains a temperature sensor which moni-

tors the unit’s internal ambient temperature. The magnitude of 

the unit’s internal temperature is compared to a limit of 145°F. 

If this limit is exceeded the unit will trip and the Quantum

LX 

panel will display the Fault 35. The fan(s) and water pump 

remain energized until the internal temperature drops below 

137°F. The fan(s) and water pump will be de-energized when 

the internal temperature drops below 137°F.

Some potential causes for this shutdown are: internal Vyper

 

fan failure, Vyper

 water pump failure or an entering con-

denser water temperature which exceeds the allowable limit 

for the job. Additional causes for the shutdown include:

Plugged Heat-Exchanger – The heat exchanger should be 

cleaned once a year and back flushed.

Low Condenser Flow – The Vyper

 system requires 8 feet 

of pressure drop across the heat exchanger to maintain ad-

equate GPM. If the pressure drop is less than 8 feet, it will 

be necessary to correct the flow problem or add a booster 

pump. 

 Fault 36:  Vyper High Inverter Base plate Temperature

Message

Quantum: “Fault 36”

Quantum LX: “VSD High Inverter Base plate Temp Fault”

A thermistor sensor is located inside the IGBT Module on 

the Vyper

 power unit. If at anytime this thermistor detects 

a  temperature  of  175°F  (79°C)  or  higher,  a  shutdown  will 

occur. The cooling fans and coolant pump on the Vyper

will 

continue to run after the shutdown, until the thermistor tem-

perature has dropped to below 165°F (74°C). This shutdown 

requires a manual reset via the Reset push button on the 

Vyper

 logic board.

 Fault 37:  Vyper logic Board Processor

Message

Quantum: “Fault 37”

Quantum LX: “VSD Logic Board Processor Fault”

This  shutdown  is  generated  if  a  communications  problem 

occurs  between  the  two  microprocessors  on  the Vyper

 

Logic  Board.  If  this  shutdown  occurs,  replace  the Vyper

 

Logic board.

 Fault 38:  Vyper Run Signal

Message

Quantum: “ Fault  38“

Quantum LX: “ VSD Run signal Fault“

Upon receipt of either of the two run commands, a 5-second 

timer will start. If the missing run signal is not asserted within 

the 5-second window, the unit will trip and the Quantum

LX 

panel will display the message Fault 38.

Redundant run signals are generated, one via wire #24 and 

the second via the serial communications. Upon receipt of 

either of the two run commands by the Vyper

 Logic board, 

a 5-second timer will begin. If the missing run command is 

not received within the 5-second window, the Vyper

 will shut 

down and the Quantum

LX Panel will display the shutdown 

message. This shutdown could occur if there is a problem with 

the wiring between the Quantum

LX panel and the Vyper

 

Logic board. Check the #24 to #25 horseshoe jumper in the 

Quantum

LX panel, and all other wiring involved in energiz-

ing #24 in the Vyper

 cabinet. Also check to ensure that the 

serial communications wiring between the micro board and 

the Interface board, and Vyper

 Logic board and the Interface 

board are connected properly.

 Fault 39: Vyper High Converter Heat Sink Temperature

Message

Quantum: “Fault 39”

Quantum LX: “VSD High Converter Heat Sink Temp Fault”

A thermistor sensor is located behind the last SCR/Diode 

block on the copper chill plate of the Vyper

 Power Unit. If at 

anytime this thermistor detects a temperature of 170°F (76°C) 

or higher, a shutdown will occur. The cooling fans and coolant 

pump on the Vyper

 will continue to run after the shutdown, 

until the thermistor temperature has dropped to below 160°F 

(71°C). This shutdown requires a manual reset via the Reset 

push button on the Vyper

 Logic board.

 Fault 40:  Vyper Invalid Current Scale Selection

Message

Quantum: “Fault 40”

Quantum LX: “VSD Invalid Current Scale Selection Fault”

The J1 connector on the Vyper

 Logic board contains jump-

ers  along  with  wires  from  the  output  CTs.  Since  the  part 

number of the Logic board is the same on all horsepower 

sizes, the jumpers tell the logic board the size of the Vyper

 

being employed in order to properly scale the output current. 

If the jumper configuration is found by the Logic board to be 

invalid, the system will be shut down and the above message, 

Fault 40, will be generated. The proper jumper configuration 

is shown on the wiring label for the Vyper

.

 Fault 41:  Vyper low Inverter Base plate Temperature

Message

Quantum: “Fault 41”

Quantum

LX: “VSD Low Inverter Base plate Temp Fault”

The phase bank assembly heatsink temperature and the in-

verter module base plate temperature are compared to a lower 

limit of 37°F. If the inverter module base plate temperature falls 

below this limit the unit will trip and the Quantum

LX Panel will 

display the message Fault 41. In addition, if both the inverter 

and converter temperatures fall below the 37°F limit, the unit 

will trip and the fan(s) and water pump will be energized. This 

feature provides the Service Dept. with a means to run the 

water pump while filling the cooling system (by pulling Vyper

 

logic board plug P2). In most case the problem will be broken 

wiring or an open thermistor. Check the circuit for continuity at 

Vyper

 Logic board plug J2. Also make certain that one side 

of the circuit is not shorted to the enclosure.

 Fault 42: Vyperdrive - Serial Communication 

Message

Quantum: “Fault 42”

Quantum LX: “VSD Serial Communications Fault”

When requesting Status data, the response data from the 

Vyper

 includes a bit that indicates whether communications 

were lost from the Frick Interface Board to the Vyper

. If this 

bit is high for 22 consecutive seconds, this fault occurs. This 

fault also occurs whenever a receive, timeout, or checksum 

fault is detected on the Vyper

 communications, for twenty 

continuous seconds. While this fault is active, the Frick In-

terface Board will send Initialize data requests in order to 

reestablish the communications link. All serial input data is 

also cleared.

Содержание Vyper 254

Страница 1: ...3c THIS MANUAL CONTAINS RIGGING ASSEMBLY START UP AND MAINTENANCE INSTRUCTIONS READ THOROUGHLY BEFORE BEGINNING INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN DAMAGE OR IMPROPER OPE...

Страница 2: ...IPMENT 11 INTERFERENCE WITH ELECTRONIC EQUIPMENT 12 SYSTEM OPERATING CONDITIONS 12 PNEUMATIC CONTROLS 12 VYPER SYSTEM OVERVIEW 12 CONFIGURATION 16 VYPER COOLING LOOP 16 Liquid Cooled Vyper P I Diagram...

Страница 3: ...ctronic con trol equipment All safety precautions consistent with opera tion of high current and voltage electrical equipment should be strictly enforced JOB INSPECTION Immediately upon arrival examin...

Страница 4: ...GING AND HANDLING The Vyper cabinet unit is best moved via lifting lugs on the top sides of the cabinet Special care must be exercised not to damage the pump or peripheral equipment on the rear of the...

Страница 5: ...and Frick publication S90 400 SB Verify that all control power 120 VAC communications analog wiring and 460 VAC power are in separate metallic con duits Properly shielded and grounded analog cables a...

Страница 6: ...e the tables in this manual to calculate what they should be 7 Verify proper operation of the motorized coolant mixing valve on the back of the drive Locate the Coolant mixing valve on the back of the...

Страница 7: ...operating frequency range of the drive The unit is started with the compressor fully unloaded until the frequency reaches the minimum operating frequency range In addition the drive is capable of ope...

Страница 8: ...0 feet Adequate service clearances including door swing must be maintained around the Vyper Care should be taken to ensure that the Vyper and it s associated piping and wiring do not obstruct the acce...

Страница 9: ...ER PRESSURE DROP In order to adequately size piping and booster pump require ments the pressure drop of the coolant across the heat Figure 3 Minimum Flow Rates GLYCOL exchanger must be known Figure 4...

Страница 10: ...tions regarding disconnect devices conductor sizes wire types and circuit protection Unshielded cable is acceptable if it can be separated from sensitive circuitry Allow a spacing of 12 inches for eve...

Страница 11: ...r at all operational loads and conditions Capacitors can be located at one or several places on a distribution system Solid state motor controllers may not run or have difficulty starting in that scen...

Страница 12: ...odes One SCR and one diode are contained in each module Three modules are required to covert the three phase input AC voltage to DC voltage 1SCR 3SCR The modules are mounted on a liquid cooled heatsin...

Страница 13: ...SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 13 Figure 6 Vyper Elementary Wiring Diagram NOTE Drawings for specific units can be found in the door of the Vyper drive or check with Frick Engineeri...

Страница 14: ...sure that the IGBT transistor module does not rupture if a failure were to occur on the DC link of the Filter Power Unit THETHREE PHASE INDUCTOR provides some impedance for the filter to work against...

Страница 15: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 15 Figure 8 Harmonic Filter Elementary Wiring Diagram NOTE Typical Check with engineering for latest drawings...

Страница 16: ...nd shutdowns as sociated with theVyper coolant temperature reading These wil also be factory set for a Low Temp alarm and shutdown at 85 F and 80 F with a 90 second delay when running The High Temp Al...

Страница 17: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 17 Liquid Cooled Vyper P I Diagram Economized...

Страница 18: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 18 Liquid Cooled Vyper P I Diagram Noneconomized...

Страница 19: ...The Vyper cabinet is mounted on a rectangular welded steel channel which provides both an attachment point for the cabinet s side brackets and also helps to maintain the rigidity of the cabinet durin...

Страница 20: ...Page 20 BLOWER MOTOR ROTATION The Blower Motor rotation is marked on the blower assembly and is to be such that the blower draws into the assemly through the screen and pushes down and through the mot...

Страница 21: ...Page 21 Dimensions in Inches Drive HP A B C D E F G H J K 305 254 1 63 4 50 9 00 6 38 4 38 35 00 5 50 3 56 6 63 2 00 437 362 6 63 6 75 10 13 2 00 3 25 40 53 2 25 3 00 13 00 2 00 Contact factory for de...

Страница 22: ...in that the Drive has been powered down for at least five minutes This allows the internal capacitors resistors to discharge the DC bus and allow for safe maintenance of the unit Failure to do so may...

Страница 23: ...ion 216 240 in lb ELECTRICAL CONDUITS All power wiring must be contained in metallic conduit All compressor motor wiring must be in a separate metallic conduit Oil pump motor wiring must be in a separ...

Страница 24: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 24 MOTOR RTD THERMAL PROTECTION Figure 17 TEMPERATURE CONTROL VALVE WIRING Figure 18...

Страница 25: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 25 MOTOR COOLING BLOWER WIRING Figure 19 Figure 20 DRAWING NOTES...

Страница 26: ...VYPER VARIABLE SPEED DRIVE INSTALLATION 100 200 IOM FEB 09 Page 26 ANALOG BOARD WIRING Figure 21...

Страница 27: ...ans c Confirm operation of coolant circulation pump d Confirm wiring and operation of the motor blower fans if present Mounting a Verify that the Vyper Drive is properly mounted to the floor or wall f...

Страница 28: ...proper electrical connections as discussed in previous sections The Vyper setup consists of three primary requirements Cooling Loop Fluid Preparation Quantum LX Panel Setup Job FLA Trim Pot Adjustment...

Страница 29: ...ntil the fluid level remains constant about one inch form the top of the manifold See Figure 30 Figure 30 Step 6 Top Off the Cooling System Figure 31 Step 7 Replace the Pipe Plug and Tighten Step 7 Re...

Страница 30: ...fferential pressure the motor speed will increase to meet the capacity requirement When the slide valve reaches the Capacity Control Slide Valve setpoint the motor speed can increase At this point the...

Страница 31: ...r can select either the Vyper or the Har monic Filter setup screens See Figure 35 The flydown menu allows the user to select either theVyper Drive setup or if the Harmonic Filter is installed the disp...

Страница 32: ...aring theVSD memory and resetting the kWh record Standby Time The VSD enters Standby mode when there is no load on the VSD The VSD capacitor banks remain charged and the compressor output is 0 Hz Stan...

Страница 33: ...indicate the status of the field They are displayed as the following 0 no off 1 yes on VSD Operating Mode Harmonic Filter Present Harmonic Filter Operating Mode Water Pump Energized Precharge Relay En...

Страница 34: ...ompressors via the SFS 229 Frick Interface Board This is accomplished through the reception of a Speed Command value in rotations per minute and a Run Command signal from the Quantum LX control panel...

Страница 35: ...on The screen shown in Figure 39 will appear Type 2 into the User Level field Enter Level 2 password Return to the menu and the Home screen The home screen will now provide additional information as s...

Страница 36: ...acity Regulations and Package spe cific information Verify that Screw Compressor with Vyper is selected under the package Drive field This will allow the Vyper specific screens to be displayed See Fig...

Страница 37: ...set to PID Channel 5 Use the table below to program the proper settings Parameter Value Name Drive Cooling Control Running Action Forward Control Point Vyper Coolant Device Source Analog Board 2 Devi...

Страница 38: ...ing the motor and the drive from high currents High Motor Amps Load Inhibit Force Unload Delay Warning 5 SEC Shutdown 5 SEC Applied Motor FLA Calculation IF USE Mtr Nameplate SF 1 0 Mtr Nameplate FLA...

Страница 39: ...Inhibit Applied Motor FLA x 1 1 374 A Force Unload Applied Motor FLA x 1 12 380 A Warning Applied Motor FLA x 1 13 384 A Shutdown Applied Mtr FLA x 1 15 391 A High Motor Amps Load Inhibit 357 Force U...

Страница 40: ...A Shutdown Applied Mtr FLA x 1 15 339 A High Motor Amps Load Inhibit 310 Force Unload 324 Delay Warning 330 5 SEC Shutdown 337 5 SEC Example 4 What are the High Motor Amp setpoints if a 437 HP Vyper...

Страница 41: ...Cycle Time settings and the maximum acceleration rate of 6 08 Hz sec Rate of Decrease The Rate of Decrease parameter set ting determines the speed change step size at which the Vyper will decelerate...

Страница 42: ...wn applications The Variable Speed Minimum Slide Valve Position is a factory default and is related to the Minimum Drive Output setting However an additional control feature is needed to override the...

Страница 43: ...en selecting Setpoints and Compressor Press the ENTER key to advance to the Compressor Safeties Screen Step 2 Refer to Figure 47 Use the cursor arrow and Tab keys to navigate to the Highest Capacity T...

Страница 44: ...re 48 This control strategy is a variation on the generic control strategy described previously Not all applications require or are suitable for the very low speeds obtainable by the Vyper drive Many...

Страница 45: ...proportional component over every 30 sec onds to drive the actual value back to the Capacity Control setpoint If the actual value remains 21 psig the Integration Time Setpoint would increase the drive...

Страница 46: ...2 Motor Service Factor 1 15 3 Multiply Line 1 x Line 2 4 HP Rating of Vyper Drive 5 Vyper Amp Limit If Line 4 is 305 254 HP Value is 380 A If Line 4 is 437 362 HP Value is 565 A 6 Multiply Line 5 x 1...

Страница 47: ...Closed 6 Open 1 Closed 5 Open 4 Open 3 Open Open 2 Open 1 Open FRICK INTERFACE BOARD DIP SWITCH SETTINGS Used before Jan 2008 On the Frick Interface Board Figure 54 on the Vyper right door there is a...

Страница 48: ...ndicators RX TX Logic Board to Quantum LX 8 J16 Communications Cable Logic Board to Quantum LX 9 Communications Indicators RX TX Logic Board to Filter Board 10 J15 Communications Cable Logic Board to...

Страница 49: ...he cooling system and oxidizing the aluminum If any of these conditions exist the coolant may have bacteria growth Take proper health precautions when draining the coolant Drain the coolant and blow t...

Страница 50: ...put current This is due to the power factor at the input to the Vyper being greater than 0 95 and nearly unity when the Harmonic filter option is included Motor FLA must be measured at the motor termi...

Страница 51: ...ick Vyper VYPER ALARMS SHUTDOWNS In addition to the Alarms and Shutdowns that the Quantum LX software generates for the basic compressor package there are warnings and shutdowns that are associated wi...

Страница 52: ...lt 9 Harmonic Filter Logic Board Or Comms Fault 10 Harmonic Filter High Total Demand Distortion 11 High Phase B Inverter Baseplate Temperature 12 High Phase C Inverter Baseplate Temperature 13 Low Pha...

Страница 53: ...ckground message when the chiller is running When this message is displayed all filter related values are unavailable If communications is reestablished normal values will again be displayed If this p...

Страница 54: ...r control board This board monitors the satura tion voltage drop across each IGBT while gated on If the IGBT s saturation voltage exceeds the prescribed limit the gate driver will make the determinati...

Страница 55: ...nput to the logic board can be checked across wires 219 and 220 of the J5 connector of the logic board This message usually means that power to the Vyper was removed If this was not the case check the...

Страница 56: ...24 in the Vyper cabinet Also check to ensure that the serial communications wiring between the micro board and the Interface board andVyper Logic board and the Interface board are connected properly...

Страница 57: ...addition if both temperatures fall below the 37 F limit the unit will trip and the fan s and water pump will be energized This feature provides the Service Dept with a means to run the water pump whi...

Страница 58: ...as Fault 51 except for applying to Phase B Fault 54 Harmonic Filter Phase Locked Loop Message Quantum Fault 54 Quantum LX Harmonic Filter Phase Locked Loop Fault This shutdown indicates that a circui...

Страница 59: ...DC below the filter DC link voltage setpoint The filter DC link voltage setpoint is determined by the filter logic board via the sensing of the three phase input line to line voltage This setpoint is...

Страница 60: ...t to the initial speed command and the Motor Current is monitored every two seconds If the Motor Current rises above 103 the unit enters current limit and a warning condition will be set Thereafter as...

Страница 61: ...RD 639A0211H25 FUSES VOLTAGE TRANSIENT BOARD 639A0211H26 SCR TRIGGER BD 60 HZ 639A0211H27 SCR TRIGGER BD 50 HZ 639A0211H28 VSD DC BALANCING RESISTOR 639A0211H29 COOLANT PUMP 639A0211H30 BUS SNUBBER CA...

Страница 62: ...HZ 639A0211H27 SCR TRIGGER BD 50 HZ 639A0211H28 VSD DC BALANCING RESISTOR 639A0211H29 COOLANT PUMP 639A0211H30 BUS SNUBBER CAPACITOR 639A0211H31 SNUBBER RESISTOR 639A0211H32 SHELL TUBE HEAT EXCHANGER...

Страница 63: ...FILTER RETROFIT 50HZ 639A0211H59 FILTER POWER MODULE COMPLETE KIT 639A0211H66 HARMONIC FILTER SPARE PARTS LISTS1 MODEL 437 Part Description Frick Part BUS ISOLATOR BOARD 639A0211H42 BUS PLATE KIT 639...

Страница 64: ...gh DC Bus Voltage 58 Harmonic Filter Precharge Low DC Bus Voltage 58 Harmonic Filter Run Signal 59 Harmonic Filter Serial Communication 60 High Converter Heat Sink Temperature 56 High DC Current Bus V...

Страница 65: ...URE CONTROL VALVE WIRING 24 transducers 10 WIRING ENTRY LOCATIONS 21 Insulated Gate Bipolar Transistor 12 Integration Time Setpoint 45 Interface board 53 inverter module base plate 56 J Job FLA 46 57...

Страница 66: ...upply Contactor 34 Supply Current 33 Total Demand Distortion 33 Total Harmonic Distortion 33 Total kWh 33 Vyper Level 2 Screen 47 Vyper Level 2 screen 46 Vyper Amp Limit 40 Quantum LX Control panel 3...

Страница 67: ...100 200 IOM FEB 09 Page 67 VYPER VARIABLE SPEED DRIVE NOTES...

Страница 68: ...System integration is what we do Q NET supports open protocols for SCADA systems i e Allen Bradley DF1 Modbus RTU Modbus ASCII and Industrial Ethernet Protocols Q NET connects instantly for local or...

Отзывы: