VYPER
™
VARIABLE SPEED DRIVE
OPERATION
100-200 IOM (FEB 09)
Page 37
PID SETUP
Press:
[Setpoints
→
PID Setup]
Figure 43 - PID Setup
Drive cooling is set to PID Channel #5. Use the table below to program the proper settings.
Parameter
Value
Name
Drive Cooling
Control
Running
Action
Forward
Control Point
Vyper
™
Coolant*
Device Source
Analog Board #2
Device Channel
1
Setpoint
110°F
Dead Band
0°F
Proportional Band
20°F
Integration Time
30
High Limit
100%
Low Limit
0%
When Running OFF Value