Freedom LiTE Installation Manual Revision 14
P a g e
26 | 30
11.3
Storage
The ideal storage temperature for a LiTE in long term storage is 15 to 25 degrees Celsius.
Storage at temperatures higher than 25 degrees Celsius is not recommended. Store in a dry
environment away from corrosion agents.
12.
Troubleshooting Guide
Most issues with the Freedom LiTE can be resolved using the guide below. If a problem
cannot be resolved after referencing this table, please contact Freedom Won or your
approved Freedom Won supplier.
Table 14.1 Troubleshooting Guide (applicable to units with On and OFF buttons)
No Problem Description
Cause/Solution
1
Eye bolts do not screw into hard
point on top of Freedom LiTE
Check that you have the correct eye bolt with the
correct thread pitch
–
M12 x 1,75
2
The rawl bolt head does not fit
into the hole on the back of
Freedom LiTE (wall mounted
models)
Check that you are using the correct size Rawl Bolt as
specified in this manual and that you have after
positively tightening the internal gripping collar turned
the bolt out again so that there is about 5mm of the bolt
shank exposed so that the back plate can fit easily
behind the bolt head. If the wall is uneven, it may be
necessary to turn the bolt head out a little more. Do not
turn it so far out that there is less than the full thread
length engaging on the internal locking collar.
3
The Freedom LiTE has no voltage
on the main output cables
Check that you have switched on the main breaker
switch. Note
–
only turn this on once you are satisfied
that you have completed the installation and that there
are no DC or control wires that can short out or touch
ground or other wires. Also ensure that you are ready to
accept AC voltage onto the inverter output before
switching this breaker on. Also confirm that you have
energised the BMS first by pressing the “ON” button
for
5 seconds and as evidenced by the lights on the SoC
display.
Ensure that the breaker lever is in fact all the way up
and not in he tripped position. If the lever is in the “60%
position
”, push
the lever down all the way before
pushing it up.
If voltage is still not present with the breaker switched
on it is possible the breaker has been damaged
–
please
contact Freedom Won
4
The BMS power (indicated by
battery SoC display lighting up)
does not stay on after the ON
button is pressed
1.
Error on the BMS. Check whether the red error
light is illuminated on the SOC display when the
ON button is held in. You can try to reset the
error by pressing the RESET button for about 2
seconds and release. This should clear the error
and allow the BMS to stay on after releasing the
ON button.