Freedom LiTE Installation Manual Revision 14
P a g e
18 | 30
Enquire from
SMA: Sunny Island
Pin 5
(blue/white)
Pin 4 (blue)
Bridge Pin 3 and Pin 6 on Inverter
end of cable with a 120
Ω
resistor
Solax
Pin 1
(orange/white)
Pin 2 (orange)
This brand requires a special cable
to accommodate pin assignment on
inverter
–
please contact Freedom
Won for more information.
Sofar Solar: 3kW
Pin 2 (orange)
Pin 1 (orange/
white)
Solis / Kodak: 3 to 6kW Models
LiTE to Type 1 RJ45 cable required
for connecting CAN Bus from LiTE to
Inverter
Studer: Variotrack and Xtender
Models
The Studer X-Com CAN can be
configured to suite on of the
options in Table 5.1 using the
jumpers supplied with the X-COM
can unit.
Sunsynk/ Daye: 5kW and 8kW
Hybrid
Pin 5
(blue/white)
Pin 4 (blue)
Type 1 CAN RJ45 cable required
Victron (GX Controllers)
Pin 8 (brown)
Pin 7 (brown/
white)
Note that the Freedom LiTE plug uses pins 7 and 8 for CAN H and CAN L.
If your inverter is not included in this table, please contact Freedom Won for assistance.
All BMS interfaces above operate at 500kbps baud rate except for Ingeteam, which operates
on 250kbps. Please enquire with Freedom Won Technical Support to change the default
500kbps to 250kbps.