Freedom Lite Marine Installation Manual Revision 3
P a g e
16 | 24
If the breaker trips after attempting to switch it on it is because of an error on the BMS or a
system setup problem, Freedom Won or your authorised distributor should be contacted to
assist with diagnosing and clearing the error.
To switch off the DC input from the LiTE, pull down the breaker lever. To switch off the
power to the BMS, press the “OFF” button situation to the right of the “ON button. This will
also trip the breaker if it is still on at the time. The LiTE must be switched off fully when not
in use to prevent self-discharge.
Figure 6.1 “ON and “OFF Buttons
7.
Settings Required for Setting up Inverters and Charge
Controllers
The maximum and continuous charge and discharge currents for the respective models are
provide in Table 2.1. Ensure that the combination of the mains (shore power) charger,
alternator, and the Solar Charge Controller (SCC) does not exceed the maximum continuous
charge current.
Use the voltage provided in Table 2.3 for the setup of the inverters and charges.
Note that if any of the voltage thresholds are exceeded, the following sequence will occur:
•
The battery will use CAN Bus to stop charge or discharge as applicable
•
If a CAN interface is not available with the other equipment, the battery will trip by
switching off its own breaker.
Frequent trip occurrences are undesirable.