Pag. 17 / 28
M
A
B
M
3
~
W (3)
V (2)
U (1)
Y (9)
X (8)
Z (7)
TR2
*
F3
TR1
*
L1
L2
L3
N
F1
L1
L2
L3
T00EC45B
N
11
1
L
2
14
N
L1.3
L1.1
PT1
PT2
9
8
6
5
4
3
2
1
7
F2
I-1/0
MR
L1.2
FCS
FS
**
BLUE
BROWN
CB
HT
10
11
12
FCS
Fig.3
*Comply with the wiring sequence:
TR1 - Z(7)X(8)Y(9) and TR2 - U(1) V(2)W(3)
**Standard equipment sent with the compressor.
To avoid false alarms, introduction of delays is required (relays not
supplied by Frascold); at the start, while in operating.
In case of connection inside the electrical box of the flowswitch, see
the wiring diagrams in the next pages.
delays: 20 seconds at startup, 3 seconds at running.
Optional equipment: it can be wired directly to the PLC.
Part Winding Start (standard setting)
6. Electrical connection
FTEC004_07_IE
6. Collegamenti elettrici
Avviamento PWS ( esecuzione standard)
*Rispettare la sequenza di collegamento:
TR1 - Z(7)X(8)Y(9) e TR2 - U(1) V(2)W(3)
**Accessorio fornito standard a corredo del compressore.
E’ necessario che il flussostato abbia gli adeguati ritardi (non
forniti da Frascold) sia in accensione che in funzionamento.
In questo modo si evitano falsi allarmi. Per il collegamento
del flussostato all’interno della scatola elettrica, vedi schemi
elettrici, nelle pagine successive.
Ritardi: 20 secondi in avviamento, 3 secondi in funzionamento.
Accessorio a richiesta: può essere collegato al PLC.